SA-SB-01 INTERFACE CONNECTIONS
TO SA41 INVERTER
|
| +48V | |
| FOR ALARM INPUT |
|
|
| APPLICATIONS, |
|
|
REFER BELOW EXAMPLES |
|
| |
INTERFACE BOARD |
| ||
TOP VIEW |
| ||
|
|
|
+48V (INT FUSE) | 1 |
| ||
ALARM INPUTS | IN 2 | 2 |
| |
IN 1 | 3 |
| ||
|
| |||
| 0V | 4 | BLK | |
| GRN | |||
| DO- | 5 | ||
| BLU | |||
| D0+ | 6 | ||
| WH | |||
RIN- | 7 | |||
YELL | ||||
RIN+ | 8 | |||
RED | ||||
|
| |||
| +12V | 9 |
| |
| INV- | 10 | SHIELD | |
| BATT- | 11 |
| |
| OUT 2 | 12 | 50mA MAX | |
CONTROLLER | 50mA MAX | |||
OUT 1 | 13 | |||
OUTPUTS | 1A FUSE INSIDE INVERTER | |||
+48V | 14 | |||
|
|
INVERTER - |
| - | + |
CHARGER - | 48V |
| |
|
| ||
ALL CHARGING | 200 AMP 75mV | BATTERY | |
AND DISCHARGING | CURRENT SHUNT |
|
|
SOURCES, NEG LEAD |
|
| |
|
|
| |
|
| GROUND |
|
REAR VIEW
KEYPAD
1 | RED | |
BLK | ||
2 | ||
YELL | ||
3 | ||
WH | ||
4 | ||
BLU | ||
5 | ||
GRN | ||
6 | ||
|
| TO INVERTER POSITIVE |
| FUSE BATTERY NEGATIVE |
SYSTEM | |
FUSE | IF IT IS NOT EARTHED |
Figure 1
ALARM INPUTS - Examples
(Alarm input 1 shown only)
ALARM FITTED TO BATTERY ROOM DOOR
REED SWITCH (NORMALLY CLOSED)
+48V 1
IN2 2
IN1 3
SET ALARM INPUT 1 = LO
Figure 2.1
Figure 2
GENERATOR OIL PRESSURE MONITOR
+48V | 1 |
|
|
| LAMP |
IN2 | 2 |
|
IN1 | 3 | OIL |
|
| PRESS |
|
| SWITCH |
0V | 4 |
|
SET ALARM INPUT 1 = HI
Figure 2.3
NORMALLY OPEN
+48V 1
IN2 2
IN1 3
SET ALARM INPUT 1 = HI
Figure 2.2
MONITORING OF SWITCH CLOSURE WHERE ONE SIDE COMMITTED TO EARTH
+48V | 1 |
|
IN2 | 2 | 4.7K 2W |
| ||
IN1 | 3 |
|
0V 4
SET ALARM INPUT 1 = LO
Figure 2.4
26