Toro SA41 owner manual SA-SB-01 Interface Connections, Alarm Inputs Examples

Page 26

SA-SB-01 INTERFACE CONNECTIONS

TO SA41 INVERTER

 

 

+48V

 

FOR ALARM INPUT

 

 

 

APPLICATIONS,

 

 

SA-SB-01

REFER BELOW EXAMPLES

 

 

INTERFACE BOARD

 

RELAY-SPDT

TOP VIEW

 

 

 

 

RELAY-SPDT

+48V (INT FUSE)

1

 

ALARM INPUTS

IN 2

2

 

IN 1

3

 

 

 

 

0V

4

BLK

 

GRN

 

DO-

5

 

BLU

 

D0+

6

 

WH

DB25-M

RIN-

7

YELL

RIN+

8

RED

 

 

 

+12V

9

 

 

INV-

10

SHIELD

 

BATT-

11

 

 

OUT 2

12

50mA MAX

CONTROLLER

50mA MAX

OUT 1

13

OUTPUTS

1A FUSE INSIDE INVERTER

+48V

14

 

 

INVERTER -

 

-

+

CHARGER -

SA-S200

48V

 

 

 

ALL CHARGING

200 AMP 75mV

BATTERY

AND DISCHARGING

CURRENT SHUNT

 

 

SOURCES, NEG LEAD

 

 

 

 

 

 

 

GROUND

 

REAR VIEW

SA-KP-01

KEYPAD

1

RED

BLK

2

YELL

3

WH

4

BLU

5

GRN

6

 

 

TO INVERTER POSITIVE

 

FUSE BATTERY NEGATIVE

SYSTEM

FUSE

IF IT IS NOT EARTHED

Figure 1

ALARM INPUTS - Examples

(Alarm input 1 shown only)

ALARM FITTED TO BATTERY ROOM DOOR

REED SWITCH (NORMALLY CLOSED)

+48V 1

IN2 2

IN1 3

SET ALARM INPUT 1 = LO

Figure 2.1

Figure 2

GENERATOR OIL PRESSURE MONITOR

+48V

1

 

 

 

LAMP

IN2

2

 

IN1

3

OIL

 

 

PRESS

 

 

SWITCH

0V

4

 

SET ALARM INPUT 1 = HI

Figure 2.3

NORMALLY OPEN

+48V 1

IN2 2

IN1 3

SET ALARM INPUT 1 = HI

Figure 2.2

MONITORING OF SWITCH CLOSURE WHERE ONE SIDE COMMITTED TO EARTH

+48V

1

 

IN2

2

4.7K 2W

 

IN1

3

 

0V 4

SET ALARM INPUT 1 = LO

Figure 2.4

26

Image 26
Contents Selectronic Australia Introduction Warranty CardInstallation Connection of AC and DC Wiring SupplyRED = Battery Positive + Black = Battery Negative Energy Management Status Standby Inverter OFF Inverter on Status ResetOperation StatusWhere the Optional 200 AMP Current Shunt is Installed Minimum Charge On with OFF Set Control On with on On with Time Set Control SettingsController Outputs Lockout DurationBuzzer Lockout More SettingsBuzzer on / OFF SET DAYLockout Alarm Input AC Volts SettingAlarm Inputs Current Shunt Settings External ShuntMinimum Charge in Battery Battery CapacityCharge in Battery LOW Charge AlarmOverload Shutdown and Alarms Alarm 2 Active Fault FindingAlarm 1 Active Heatsink TOO HOTInverter Shuts Down with LOW Volts Battery Maintenance System MaintenanceSA41 Maintenance SA41 Electrical Specifications Demand Start SectionRadio Frequency Interference Handy HintHeatsink Temperature Appendix I DiagnosticsTransformer Temperature Demand Start CurrentAppendix II Flow Diagram for Displays and Settings Minimum Charge Display Switching Between READINGS, Minimum CHARGE, and DiagnosticsDiagnostic Displays Minimum charge DisplaysINV CO, LO A/H or CO+LAHFrom previous SA-SB-01 Interface KIT Appendix III SA Inverter OptionsGeneral Alarm Inputs Examples SA-SB-01 Interface ConnectionsInstallation of SA-KP-01 Optional Keypad Ext. Keypad no Set ParametersExt. Shunt no Set Parameters Installation of SA-S200 Optional Current ShuntAmps 0.0A OUT Battery Zero DC Amps OFF Set ParametersProduct Warranty Conditions Mounting Template for SA-KP-01 Keypad