OVERLOAD SHUTDOWN AND ALARMS

The SA41 has eight alarm and overload conditions. These result from high or low battery volts, high AC volts, AC output overloaded, transformer too hot, heatsink too hot, either of the two alarm inputs being active, or low battery charge. If any of these conditions occur, a message will be displayed. If there is more than one alarm condition the display will alternate between messages.

The alarm message will remain on the display until a key is pressed, even if the alarm condition ends. (i.e. after a high voltage condition the battery volts comes back down again) This allows you to determine the cause of the shutdown even if the inverter comes on again before you are able to read the display. To reset the inverter after it has shutdown, set the inverter Status to RESET, and then back to STANDBY. (See page 5.)

DC VOLTS HIGH

Hi DC Volts : 66.0 * * Press a Key * *

DC VOLTS LOW

This message is displayed and the inverter shuts down if the battery voltage rises above the ‘Hi DC Volts’ setting. The inverter will automatically restart when the battery voltage drops below this value. The present battery voltage is also displayed.

Lo DC Volts : 38.0 * * Press a Key * *

AC VOLTS HIGH

AC Volts Hi : 0

* * Press a Key * *

This message is displayed and the inverter shuts down if the battery voltage drops below the ‘Lo DC Volts’ setting for more than 10 seconds. The inverter will automatically come on again when the battery voltage rises above the ‘Lo DCV ON’ voltage or if the inverter is manually reset (via the STATUS display, see page 5). The present battery voltage is also displayed.

If a system fault causes the AC voltage to go too high, then this message is displayed.

INVERTER OVERLOAD

Inverter O/L : 0

* * Press a Key * *

An AC current overload or a short circuit on the AC output will cause the inverter to shut down and display this message. If the shutdown was due to an overload, the SA41 will automatically reset after 1 minute, or when a key is pressed. If the shutdown was due to a short circuit, the SA41 will have to be reset (via the STATUS display, see page 5) on the front panel.

TRANSFORMER TOO HOT

TX Too Hot : 122C * * Press a Key * *

If the transformer reaches its maximum operating temperature, the SA41 will shut down to protect the internal components. The SA41 will restart again only when the temperature drops to a safe level. The present temperature of the transformer is also displayed.

14

Image 14
Contents Selectronic Australia Introduction Warranty CardInstallation Connection of AC and DC Wiring SupplyRED = Battery Positive + Black = Battery Negative Energy Management Status Standby Inverter OFF Inverter on Status ResetOperation StatusWhere the Optional 200 AMP Current Shunt is Installed Minimum Charge On with OFF Set Control On with on On with Time Set Control SettingsController Outputs Lockout DurationBuzzer Lockout More SettingsBuzzer on / OFF SET DAY Lockout Alarm Input AC Volts SettingAlarm Inputs Current Shunt Settings External ShuntMinimum Charge in Battery Battery CapacityCharge in Battery LOW Charge AlarmOverload Shutdown and Alarms Alarm 2 Active Fault FindingAlarm 1 Active Heatsink TOO HOTInverter Shuts Down with LOW Volts Battery Maintenance System MaintenanceSA41 Maintenance SA41 Electrical Specifications Demand Start SectionRadio Frequency Interference Handy HintHeatsink Temperature Appendix I DiagnosticsTransformer Temperature Demand Start CurrentAppendix II Flow Diagram for Displays and Settings Minimum Charge Display Switching Between READINGS, Minimum CHARGE, and DiagnosticsDiagnostic Displays Minimum charge DisplaysINV CO, LO A/H or CO+LAHFrom previous SA-SB-01 Interface KIT Appendix III SA Inverter OptionsGeneral Alarm Inputs Examples SA-SB-01 Interface ConnectionsInstallation of SA-KP-01 Optional Keypad Ext. Keypad no Set ParametersExt. Shunt no Set Parameters Installation of SA-S200 Optional Current ShuntAmps 0.0A OUT Battery Zero DC Amps OFF Set ParametersProduct Warranty Conditions Mounting Template for SA-KP-01 Keypad