INSTALLATION OF SA-S200 OPTIONAL CURRENT SHUNT

Installation of the current shunt requires the SA-SB-01 interface board.

1.The 200 Amp 75mV precision current shunt must be fitted between the negative (black) lead of the SA41 and battery negative, as shown on diagram 1. Please ensure that cables are kept as short as possible. At least 120 Amp continuously rated battery cable should be used.

2.Attach the shunt and insulated base securely to a solid structure.

3.Using the twin flex supplied, wire up the current sensing wires to the SA-SB-01 Interface Board as shown in Diagram 1, terminals 10 and 11 being used for the current sensing. Take careful note of the polarity.

4.Ensure that the SA41 Status is in "RESET" mode, which ensures that the SA41 is not drawing any DC current through the shunt. Also, disable all charging sources, such as Solar Panels and wind generators.

5.Via the SA41 front panel, access the “Settings” menu as described on Page 8 of the manual. Scroll slowly through the screens until the following display is seen:

Ext. Shunt: NO

Set Parameters]

Select YES using the ”UP” key.

6. Scroll to the next screen and the following display will be seen:

Zero DC Amps: OFF

[Set Parameters]

Select ON using the ”UP” key. Note: when this setting is set to ON, a zero DC amps is performed taking about 1 to 2 seconds, after which the display returns to OFF.

Scroll through the remainder of the “Settings” screens until the “Readings” screen is reached.

7.Scroll through the “Readings” screen until the following screen is displayed:

Note that when the battery current is zero, the screen may flicker between IN and OUT; this is quite normal.

Amps: 0.0A OUT

----Battery----

8.Apply an AC load to the inverter's output and verify that the DC current reading is "OUT". If not, then reverse the sensing wires to the current shunt.

28

Image 28
Contents Selectronic Australia Installation Warranty CardIntroduction Connection of AC and DC Wiring SupplyRED = Battery Positive + Black = Battery Negative Status Standby Inverter OFF Inverter on Status Reset OperationEnergy Management StatusWhere the Optional 200 AMP Current Shunt is Installed Minimum Charge Controller Outputs SettingsOn with OFF Set Control On with on On with Time Set Control Lockout DurationMore Settings Buzzer on / OFFBuzzer Lockout SET DAYLockout AC Volts Setting Alarm InputsAlarm Input Current Shunt Settings External ShuntBattery Capacity Charge in BatteryMinimum Charge in Battery LOW Charge AlarmOverload Shutdown and Alarms Fault Finding Alarm 1 ActiveAlarm 2 Active Heatsink TOO HOTInverter Shuts Down with LOW Volts SA41 Maintenance System MaintenanceBattery Maintenance SA41 Electrical Specifications Demand Start SectionRadio Frequency Interference Handy HintAppendix I Diagnostics Transformer TemperatureHeatsink Temperature Demand Start CurrentAppendix II Flow Diagram for Displays and Settings Switching Between READINGS, Minimum CHARGE, and Diagnostics Diagnostic DisplaysMinimum Charge Display Minimum charge DisplaysINV CO, LO A/H or CO+LAHFrom previous General Appendix III SA Inverter OptionsSA-SB-01 Interface KIT Alarm Inputs Examples SA-SB-01 Interface ConnectionsInstallation of SA-KP-01 Optional Keypad Ext. Keypad no Set ParametersInstallation of SA-S200 Optional Current Shunt Amps 0.0A OUT BatteryExt. Shunt no Set Parameters Zero DC Amps OFF Set ParametersProduct Warranty Conditions Mounting Template for SA-KP-01 Keypad