Toro SA41 owner manual Settings, Controller Outputs

Page 8

SETTINGS

There are a number of settings within the SA41 that can be changed via the front panel push keys (push buttons). These allow you to tailor the SA41 inverter and ENERGY MANAGEMENT sections to suit your system requirements.

Settings are accessed by holding down the NEXT DISPLAY key for at least 1 second whilst in any "Readings" display. The value of the parameter displayed can be modified by pressing the UP or DOWN keys.

Pressing the NEXT DISPLAY key will take you to the next parameter to be set. Pressing the NEXT DISPLAY key after the last parameter is displayed will take you back to the "Readings" displays.

Please note: If DC power is disconnected from the inverter, the "Settings" which have been entered will be saved and held in permanent memory. However these settings are not saved until the display is returned to "Readings".

CONTROLLER OUTPUTS

The SA41 ENERGY MANAGEMENT has 2 control outputs, as mentioned on page 25, each of which can be activated with time, inverter cutout and/or low ampere-hours. The six settings are

displayed as OFF, ON, TIME, INV CO, LO A/H and CO+LAH respectively

For simplicity, the displays shown are for control output 1 only. Control output 2 settings are identical to control output 1. Pressing the UP or DOWN keys will change the setting.

On with : OFF [Set Control 1]

On with : ON

[Set Control 1]

On with : TIME [Set Control 1]

The control 1 output will remain off at all times.

The control 1 output will remain on at all times.

The control 1 output will come on at the Start Day, Start Hour and Start Minute that is set in the three screens below.

The Start Day can be set to ALL which will turn the output on every day at the set time. Pressing the UP or DOWN keys will change the setting. The output will remain on for the time set in "Duration". (see next page)

Start Day : SUN [Set Control 1]

Start Hour : 16 [Set Control 1]

Start Min : 30 [Set Control 1]

8

Image 8
Contents Selectronic Australia Introduction Warranty CardInstallation Connection of AC and DC Wiring SupplyRED = Battery Positive + Black = Battery Negative Status Standby Inverter OFF Inverter on Status Reset OperationEnergy Management StatusWhere the Optional 200 AMP Current Shunt is Installed Minimum Charge On with OFF Set Control On with on On with Time Set Control SettingsController Outputs Lockout DurationMore Settings Buzzer on / OFFBuzzer Lockout SET DAYLockout AC Volts Setting Alarm InputsAlarm Input Current Shunt Settings External ShuntBattery Capacity Charge in BatteryMinimum Charge in Battery LOW Charge AlarmOverload Shutdown and Alarms Fault Finding Alarm 1 ActiveAlarm 2 Active Heatsink TOO HOTInverter Shuts Down with LOW Volts Battery Maintenance System MaintenanceSA41 Maintenance SA41 Electrical Specifications Demand Start SectionRadio Frequency Interference Handy HintAppendix I Diagnostics Transformer TemperatureHeatsink Temperature Demand Start CurrentAppendix II Flow Diagram for Displays and Settings Switching Between READINGS, Minimum CHARGE, and Diagnostics Diagnostic DisplaysMinimum Charge Display Minimum charge DisplaysINV CO, LO A/H or CO+LAHFrom previous SA-SB-01 Interface KIT Appendix III SA Inverter OptionsGeneral Alarm Inputs Examples SA-SB-01 Interface ConnectionsInstallation of SA-KP-01 Optional Keypad Ext. Keypad no Set ParametersInstallation of SA-S200 Optional Current Shunt Amps 0.0A OUT BatteryExt. Shunt no Set Parameters Zero DC Amps OFF Set ParametersProduct Warranty Conditions Mounting Template for SA-KP-01 Keypad