APPENDIX III: SA INVERTER OPTIONS
GENERAL
The SA41 employs a rear
The full range of features are:
(a) Remote Keypad: | A low profile keypad with |
| be located up to 500 metres from your SA41. |
| Wiring requirements - 6 conductor shielded cable. |
(b)DC Current Shunt: Consists of a 200 Amp 75mV current shunt, mounted on an insulated
base, and a twin flex loom for current sensing.
(c)Controller Outputs: Two external relay or contactor coils can be energised for various AC or DC switching applications.
(d) Alarm Inputs: | Two digital inputs that can be programmed to monitor switch contact |
| status or voltage levels (refer to following circuits for examples) |
SA-SB-01 INTERFACE KIT
The Interface Kit
TERMINAL NO | DESCRIPTION | |
|
|
|
1 | & 14 | +48V with 1A internal fuse |
2 |
| Alarm input 2 |
3 |
| Alarm input 1 |
4 |
| 0V |
5 | - 8 | Keypad data lines |
9 |
| Keypad +12V |
10 & 11 | 200A current shunt connections | |
12 | Controller output 2 | |
13 | Controller output 1 |
Please refer also to Diagram 1 overleaf.