Toro owner manual SA41 Electrical Specifications, Demand Start Section

Page 18

SA41 ELECTRICAL SPECIFICATIONS

INVERTER TYPE PWM Full bridge power stage, with true sine wave AC output.

DEMAND START SECTION

 

 

Type:

 

Pulsing AC

Minimum Load Power to start (User adjustable):

 

3W to 20W

Maximum response time:

 

1 sec

Standby current from battery (Average):

 

60mA

BATTERY VOLTAGE RANGE

 

 

Low DC Volts Disconnect (Instantaneous):

 

34V

Low DC Volts Cutout (Delayed, User Adjustable):

38-44V

Low DC Volts Cut-in (Delayed, User Adjustable):

44.4-52V

High DC Volts Cutout (Instantaneous, User Adjustable):

60-68V

High DC Volts Disconnect (Instantaneous):

 

70V

TOTAL APPLIANCE RATING AT

25°C

40°C

Continuous:

3000W

2800W

30 Minute rating:

4700W

4400W

5 Minute rating:

5300W

 

1 Minute rating:

6500W

 

Surge rating:

8500W

 

INVERTER EFFICIENCY

 

 

Peak (at 500W):

 

91%

No load power consumption (C0NT mode):

 

0.66 A

MISCELLANEOUS SPECIFICATIONS

 

 

Output Frequency Accuracy:

 

50Hz ± 0.001 %

Output Voltage Accuracy (0 - 2200W)

 

240V ± 4 %

Total Harmonic Distortion (THD)

 

< 4 %

Control Outputs 1 & 2, max DC sinking current:

 

50 mA

Alarm Inputs 1 & 2, input switching level:

 

HI > 3 V

 

 

LO < 1 V

Operating temperature range:

 

-10°C to 50°C

Weight:

 

32 kg

DC Input is Electrically Isolated from AC Output

Note: Through a policy of continued development, specifications are subject to change without notice.

The above specifications are based on unity power factor.

18

Image 18
Contents Selectronic Australia Warranty Card InstallationIntroduction Connection of AC and DC Wiring SupplyRED = Battery Positive + Black = Battery Negative Energy Management Status Standby Inverter OFF Inverter on Status ResetOperation StatusWhere the Optional 200 AMP Current Shunt is Installed Minimum Charge Settings Controller OutputsOn with OFF Set Control On with on On with Time Set Control Lockout DurationBuzzer Lockout More SettingsBuzzer on / OFF SET DAYLockout Alarm Input AC Volts SettingAlarm Inputs Current Shunt Settings External ShuntMinimum Charge in Battery Battery CapacityCharge in Battery LOW Charge AlarmOverload Shutdown and Alarms Alarm 2 Active Fault FindingAlarm 1 Active Heatsink TOO HOTInverter Shuts Down with LOW Volts System Maintenance SA41 MaintenanceBattery Maintenance SA41 Electrical Specifications Demand Start SectionRadio Frequency Interference Handy HintHeatsink Temperature Appendix I DiagnosticsTransformer Temperature Demand Start CurrentAppendix II Flow Diagram for Displays and Settings Minimum Charge Display Switching Between READINGS, Minimum CHARGE, and DiagnosticsDiagnostic Displays Minimum charge DisplaysINV CO, LO A/H or CO+LAHFrom previous Appendix III SA Inverter Options GeneralSA-SB-01 Interface KIT Alarm Inputs Examples SA-SB-01 Interface ConnectionsInstallation of SA-KP-01 Optional Keypad Ext. Keypad no Set ParametersExt. Shunt no Set Parameters Installation of SA-S200 Optional Current ShuntAmps 0.0A OUT Battery Zero DC Amps OFF Set ParametersProduct Warranty Conditions Mounting Template for SA-KP-01 Keypad