LOCKOUT
Lockout is a feature which ensures that you are not disturbed during a specified period of time, e.g. you do not want to start a generator in the middle of the night. When set to ON, lockout prevents the controller outputs coming on, or the buzzer sounding during the lockout period.
The lockout start and finish times below affect both controller lockout, and buzzer lockout. (See Buzzer Lockout on page 10.) Buzzer lockout and controller lockout may be set ON or OFF individually.
SET LOCKOUT START TIME
Lockout on : 22:00
[Set Parameters]
This is the time the lockout for the controllers and buzzer commences. After this time, the buzzer will not sound and the controlled outputs will not come on. If a control output is already on, lockout will not turn it off. Use the UP or DOWN keys to set the time.
SET LOCKOUT FINISH TIME
L’out off : 6:00
[Set Parameters]
This is the time the lockout for the controllers and buzzer ends. Use the UP or DOWN keys to set the time.
LOW VOLTAGE TRIP |
| |
|
| When set to YES, the circuit breaker on the front panel will trip to |
Lo Volt Trip : YES | ||
[Set Parameters] |
| completely disconnect the inverter from the batteries when the DC battery |
|
| volts remains below the ‘Lo DC Volts’ setting (described below) for more |
|
| |
|
| than 2 minutes. Use the UP or DOWN keys to change the setting. |
LOW DC VOLTS CUTOUT
Lo DC Volts : 40.0 [Set Parameters]
LOW DC VOLTS ON
Lo DCV on : 48.0 [Set Parameters]
The SA41 will cut out (not tripping the breaker) and a message displayed if the battery voltage falls below this setting for more than 10 seconds, regardless of the setting of ‘Lo Volt Trip’. The inverter will restart if reset or when the battery volts rise above the ‘Lo DCV On’ setting (next setting).
Please note that if the battery volts drop below 35V (regardless of the ‘Lo DC Volts’ setting) then the breaker will trip instantly, disconnecting the
SA41 f | th b tt |
The SA41 will restart after a Low Battery Volts
HIGH DC VOLTS CUTOUT
Hi DC Volts : 68.0 [Set Parameters]
When the battery volts exceeds this setting, the SA41 will cut out instantaneously. Please note that if the battery volts rise above 70V (regardless of the ‘Hi DC Volts’ setting), the breaker will instantly trip and the inverter will be totally disconnected.
11