PowerTec DFS-1 manual Unit ID, Local / Remote Control, Number Baud Rate, Not Used

Page 24

3.0DFS-1 PARAMETERS

DFS-1 parameters are stored as DOUBLE WORD values (32 bits), regardless of the actual size of the data. This method is used to simplify the entire system at a cost of a little extra data storage.

A double word consists of four BYTES (8 bits). Each byte is a hexadecimal (base 16) value which ranges from 00h (0 decimal) to FFh (255 decimal). The largest number used in the DFS-1 parameters is 99,999 decimal, which, in hexadecimal notation is 0001 869Fh.

In many cases, information other than numbers is passed and stored in the parameters. The left byte is the most significant and the last byte is the least significant. The arrangement of the bytes for this purpose is: VL4 VL3 VL2 VL1 where VL4 is the Most Significant Bit (MSB) and VL1 is the Least Significant Bit (LSB). Each parameter breaks down the bytes accordingly.

All four bytes are required in communications. A number which must be either 0 or 1 must be passed as either 0000 0000h or 0000 0001h.

1.UNIT ID

USE PARAMETER #1 TO IDENTIFY THE AD- DRESS OF THE UNIT ON A NETWORK. RANGE OF VALUES: 0000 0001h to 0000 00FFh

1 to 255 (decimal)

Default Value: 0000 0001h

1 (decimal)

The Unit ID number is installed in parameter #1. This serves as an address on the external communica- tions link. Two DFS-1 units cannot have the same address while installed on the same communications link.

There are 254 possible addresses if the default value of 1 is not used as an address. Since the default value is 1, there could be a problem if a new unit is installed without changing the #1 parameter.

2.BAUD RATE

USE PARAMETER #2 TO SET THE COMMUNI- CATIONS SPEED OF THE NETWORK. RANGE OF VALUES: 0000 0000h to 0000 0007h

0 to 7 (decimal)

Default Value: 0000 0002h

2 (decimal)

This establishes the rate at which data is ex- changed in the communications link. Every DFS-1 in the communications link must have the same baud

rate set up in parameter #2. The parameter selects from among eight industry standard baud rates:

NUMBER

BAUD RATE

 

0000 0000h

38.4 Kilobaud

(38,400 baud)

. . . . 01

19.2 Kilobaud

(19,200 baud)

. . . . 02

9,600

baud

 

. . . . 03

4,800

baud

 

. . . . 04

2,400

baud

 

. . . . 05

1,200

baud

 

. . . . 06

600

baud

 

. . . . 07

300

baud

 

3.LOCAL / REMOTE CONTROL

USE PARAMETER #3 TO SET UP WHICH FUNCTIONS ARE CONTROLLED REMOTELY. RANGE OF VALUES: 0000 0000h to 0000 007Fh

0 to 127 (decimal)

Default Value: 0000 0000h

0 (decimal)

Parameter #3 is first broken down into bytes, and then VL1 is further broken down into bits.

When broken down into bits, 00h = 0000 0000b, and 7Fh = 0111 1111b.

VL4 is always 00h. VL3 is always 00h. VL2 is always 00h.

VL1 is broken down into eight bits, which are numbered from right to left: 7654 3210h.

Functions are assigned as follows: Bit Position Function

7 NOT USED

6Master/Slave (not presently functional)

5Frequency Mode

4Reverse

3Down

2Up

1Preset

0Run

A zero in a bit position means that function may be controlled from an input terminal assigned to it. A one in a bit position means that the function may only be controlled via a communications link, such as the operator’s station connection or the external RS- 485 communications link.

For instance, if VL1 is given a value of 01 (0000

Revised 7/95

DFS-1 Manual

Page 19

POWERTEC Ind. Corp.©

 

 

Image 24
Contents DFS-1 Microprocessor Based Brushless D.C Motor ControllerSubsidiary Powertec Industrial Corporation Errata Additional Info OctoberInstallation Mounting -- Read this Entire Section Before StartingContents DFS 1 Setup Communication Protocol Retrofitting the Model 1000,1000A, or 1000ARMenu and Keypad Hierarchy Revised 7/95 Introduction Summary of Warranty and Disclaimer Power Connections ConnectionsMotor Encoder Cable Analog InputsFrequencyinput Analog OutputsFrequencyoutputdigital Inputs Digital Outputs CommunicationsDigital Out #4 Reverse This page WAS Intentionally Left Blank Default Setup Revised 7/95 Power Supplies Input Setup FunctionThis Supply is for the Motor Encoder only VDCFrequency Inputs Outputs Digital InputsInput #1 Reference Frequency Input Outputs #1 Reference Frequency OutputStandard RS-485 19.2K, and 38.4K baudCable Nodes MaximumThis page WAS Intentionally Left Blank Local / Remote Control Unit IDBaud Rate Number Baud RateCommunications Protocol Modes of OperationTo 1 decimal Maximum Motor Speed Encoder Pulses PER RevolutionUSE Parameter #6 to SET the Absolute Maximum Motor Speed Master Ramp UP Time Master Ramp Down TimeSlave Ramp UP Time Slave Ramp Down TimeMaster Preset Speed Slave Ratio PresetTo 99,999 decimal Default Value 0000 06D6h Engineering UnitsAnalog Input #1 Mode Select To 32 decimal Default Value 0000 0001hMaximum Ratio Analog Input #1 Signal Conditioning Analog Input #1 LOW Engineering Units EGUCenter value Future useAnalog Input #2 Mode Select Analog Input #2 Signal ConditioningAnalog Input #1 High Engineering Units EGU Analog Input #2 LOW Engineering Units EGUAnalog Output #1 Mode Select Analog Output #2 Mode SelectAnalog Output #1 LOW Engineering Units EGU Analog Output #1 High Engineering Units EGUDefault Value 0000 0096h Analog Output #2 LOW Engineering Units EGUAnalog Output #2 High Engineering Units EGU Digital Input #1 Function Digital Input #2 FunctionDigital Input #3 Function Digital Input #4 FunctionDigital Input #5 Function Digital Input #6 FunctionDigital Input #7 Function Digital Output #1 FunctionDrive Gain Setting Drive Stability SettingDigital Output #2 Function Digital Output #3 FunctionDrive Regenerative Current Limit Pulse MultiplierModulation and Operation Modes Jump or MOP OperationMaster Jump UP Amount Master Jump Down AmountSlave Jump UP Amount Slave Jump Down AmountCommunications Turnaround Delay Input Debounce ValueMinimum Ratio Float or FreezeSlave JOG Ratio Slave Preset #2 Master Preset #2Contactordelay EGU TAG SelectThis page WAS Intentionally Left Blank DFS 1 Setup Basic Setup of the DFS-1 Controller Master Mode Setup Slave Mode Setup Inputs and Outputs Setup Communications Setup This parameter selects the Powertec binary protocolSET Parameter #56 for Communications Turn around Delay SET Parameter #3 to Select Which Functions are RemoteError Codes for ON-BOARD Display This page WAS Intentionally Left Blank Communications Protocol Command List Parameter List Dlestxuidcmddleetxcsm DLESTXUIDCMDCS4CS3 CS2CS1DLEETXCSMDlestxuidnakerrdleetxcsm ERRResponse If no errors and unit i.d. does not equal Response If no errorsDlestxuidackdleetxcsm DlestxuidcmdprmdleetxcsmDLESTXUIDCMDPRMVL4 DlestxuidcmdatddleetxcsmDlestxuidcmddtadleetxcsm DLESTXUIDACKDA4DA3DLESTXUIDCMDDTAVL4 DlestxuidcmddigdleetxcsmWhere Is unused Is Jog Is Preset Is Contactor Aux DLESTXUIDCMDDIGVL4BIT PSN SML BIT PSN SMHMessage DLESTXUIDCMD0000 SmhsmldleetxcsmBIT PSN RML BIT PSN RMHAttachmentb Parameter Description DLESTXUIDCMDAMDVL4Additional Info Output Contactor Typical Dynamic Braking Typical This page WAS Intentionally Left Blank Quantity Pin Connector Cable DFS-1 Model 1000 series retro-fit kit consists QuantityRevised 7/95 Appendix B Not visible in some modes Revised 7/95 Powertec Ind. Corp Figures 2 DFS-1 Manual Figures DFS-1 Manual Igur DFS-1 Manual Select AI ModeEnterEnter DFS-1 Manual Igur DFS-1 Manual Sel DFS-1 Manual Igures DFS-1 Manual Figures 29 DFS-1 Manual