PowerTec DFS-1 manual Analog Input #1 High Engineering Units EGU, Analog Input #2 Mode Select

Page 31

20.ANALOG INPUT #1 HIGH ENGINEERING UNITS (EGU)

USE PARAMETER #18 TO SELECT THE MAXI- MUM ANALOG INPUT #1 EFFECT.

RANGE OF VALUES: FFFE 7961h to 0001 869Fh -99,999 to +99,999 (dec.)

Default Value: 0000 06D6h

1750 (decimal)

(See Parameter 14 for the definition

and purpose of EGU) Parameter #20 sets the maximum level for

effectiveness of Analog Input #1 at the highest signal level.

Assume that the maximum speed of the 1750 RPM motor is set to 12500 EGU’s in parameter #14 (representing, perhaps, 125.00 RPM on an extruder screw) and the Analog input is set for a Speed Reference Input of 0 to +10VDC. The default value of parameter 20 is 1750. This means that when 10VDC is present at Analog Input #1, the resulting speed will be 1750/12500 = 14 percent of maximum speed, or 245 RPM.

Now, if we want to set the maximum speed of this system at 100.00, we set a value of 10000 in parameter #20. This means that when 10VDC is present at Analog Input #1, the motor will run at a speed of 10000/12500 = 80 percent of the maximum speed of the motor, or 1400 RPM. (see also param- eter #19).

21.ANALOG INPUT #2 MODE SELECT

USE PARAMETER #21 TO SELECT THE PUR- POSE OF A SIGNAL AT ANALOG INPUT #2. RANGE OF VALUES: 0000 0000h to 0000 001Fh

0 TO 32 (decimal)

Default Value: 0000 0000h

0 (decimal)

See parameter #17. The operation of Analog Input #2 is identical to the operation of Analog Input #1, EXCEPT the parameters which set the form of the input signal (#22) and low and high EGU’s ( #23 and #24).

Both Analog Inputs #1 and #2 may be set up as General Purpose Inputs, but all other modes are mutually exclusive. If one of the Analog Inputs is set up as a Speed Reference Input, the other Analog

Input may not be set up as a Speed Reference Input. Attempting to set up a second Analog Input as a Speed Reference Input when one is already set up in that mode will cause the second input to be inopera- tive.

22.ANALOG INPUT #2 SIGNAL CONDITIONING

USE PARAMETER #17 TO SELECT THE FORM OF THE SIGNAL AT ANALOG INPUT #1. RANGE OF VALUES: 0000 0000h to 0000 001Fh

0 TO 32 (decimal)

Default Value: 0000 0000h

0 (decimal)

See parameter #18. Signal conditioning selection for Analog Input #2 is identical to Analog Input #1.

23.ANALOG INPUT #2 LOW ENGINEERING UNITS (EGU)

USE PARAMETER #23 TO SELECT THE MAXIMUM ANALOG INPUT #2 EFFECT. RANGE OF VALUES: FFFE 7961h to 0001 869Fh

-99,999 to +99,999 (dec.)

Default Value: 0000 0000h

0 (decimal)

Analog Input #2 works exactly the same way that Analog Input #1 works. Parameter #23 does for Analog Input #2 what parameter #19 does for Analog Input #1. Refer to parameter #19.

24.ANALOG INPUT #2 HIGH ENGINEERING UNITS (EGU)

USE PARAMETER #24 TO SELECT THE MAXIMUM ANALOG INPUT #2 EFFECT. RANGE OF VALUES: FFFE 7961h to 0001 869Fh

-99,999 to +99,999 (dec.)

Default Value: 0000 0000h

0 (decimal)

Analog Input #2 works exactly the same way that Analog Input #1 works. Parameter #24 does for Analog Input #2 what parameter #20 does for Analog Input #1. Refer to parameter #20.

Page 26

DFS-1 Manual

Revised 7/95

 

 

POWERTEC Ind. Corp.©

Image 31
Contents Microprocessor Based Brushless D.C Motor Controller DFS-1Subsidiary Powertec Industrial Corporation Errata October Additional InfoMounting -- Read this Entire Section Before Starting InstallationContents DFS 1 Setup Retrofitting the Model 1000,1000A, or 1000AR Communication ProtocolMenu and Keypad Hierarchy Revised 7/95 Introduction Summary of Warranty and Disclaimer Connections Power ConnectionsAnalog Inputs Motor Encoder CableAnalog Outputs FrequencyinputFrequencyoutputdigital Inputs Communications Digital OutputsDigital Out #4 Reverse This page WAS Intentionally Left Blank Default Setup Revised 7/95 VDC Power SuppliesInput Setup Function This Supply is for the Motor Encoder onlyOutputs #1 Reference Frequency Output Frequency Inputs OutputsDigital Inputs Input #1 Reference Frequency InputNodes Maximum Standard RS-48519.2K, and 38.4K baud CableThis page WAS Intentionally Left Blank Number Baud Rate Local / Remote ControlUnit ID Baud RateModes of Operation Communications ProtocolTo 1 decimal Encoder Pulses PER Revolution Maximum Motor SpeedUSE Parameter #6 to SET the Absolute Maximum Motor Speed Slave Ramp Down Time Master Ramp UP TimeMaster Ramp Down Time Slave Ramp UP TimeEngineering Units Master Preset SpeedSlave Ratio Preset To 99,999 decimal Default Value 0000 06D6hTo 32 decimal Default Value 0000 0001h Analog Input #1 Mode SelectMaximum Ratio Future use Analog Input #1 Signal ConditioningAnalog Input #1 LOW Engineering Units EGU Center valueAnalog Input #2 LOW Engineering Units EGU Analog Input #2 Mode SelectAnalog Input #2 Signal Conditioning Analog Input #1 High Engineering Units EGUAnalog Output #1 High Engineering Units EGU Analog Output #1 Mode SelectAnalog Output #2 Mode Select Analog Output #1 LOW Engineering Units EGUAnalog Output #2 LOW Engineering Units EGU Default Value 0000 0096hAnalog Output #2 High Engineering Units EGU Digital Input #4 Function Digital Input #1 FunctionDigital Input #2 Function Digital Input #3 FunctionDigital Output #1 Function Digital Input #5 FunctionDigital Input #6 Function Digital Input #7 FunctionDigital Output #3 Function Drive Gain SettingDrive Stability Setting Digital Output #2 FunctionJump or MOP Operation Drive Regenerative Current LimitPulse Multiplier Modulation and Operation ModesSlave Jump Down Amount Master Jump UP AmountMaster Jump Down Amount Slave Jump UP AmountFloat or Freeze Communications Turnaround DelayInput Debounce Value Minimum RatioEGU TAG Select Slave JOG Ratio Slave Preset #2Master Preset #2 ContactordelayThis page WAS Intentionally Left Blank DFS 1 Setup Basic Setup of the DFS-1 Controller Master Mode Setup Slave Mode Setup Inputs and Outputs Setup SET Parameter #3 to Select Which Functions are Remote Communications SetupThis parameter selects the Powertec binary protocol SET Parameter #56 for Communications Turn around DelayError Codes for ON-BOARD Display This page WAS Intentionally Left Blank Communications Protocol Command List Parameter List ERR DlestxuidcmddleetxcsmDLESTXUIDCMDCS4CS3 CS2CS1DLEETXCSM DlestxuidnakerrdleetxcsmDlestxuidcmdprmdleetxcsm Response If no errors and unit i.d. does not equalResponse If no errors DlestxuidackdleetxcsmDLESTXUIDACKDA4DA3 DLESTXUIDCMDPRMVL4Dlestxuidcmdatddleetxcsm DlestxuidcmddtadleetxcsmDlestxuidcmddigdleetxcsm DLESTXUIDCMDDTAVL4BIT PSN SMH Where Is unused Is Jog Is Preset Is Contactor AuxDLESTXUIDCMDDIGVL4 BIT PSN SMLBIT PSN RMH Message DLESTXUIDCMD0000Smhsmldleetxcsm BIT PSN RMLDLESTXUIDCMDAMDVL4 Attachmentb Parameter DescriptionAdditional Info Output Contactor Typical Dynamic Braking Typical This page WAS Intentionally Left Blank DFS-1 Model 1000 series retro-fit kit consists Quantity Quantity Pin Connector CableRevised 7/95 Appendix B Not visible in some modes Revised 7/95 Powertec Ind. Corp Figures 2 DFS-1 Manual Figures DFS-1 Manual Igur DFS-1 Manual Select AI ModeEnterEnter DFS-1 Manual Igur DFS-1 Manual Sel DFS-1 Manual Igures DFS-1 Manual Figures 29 DFS-1 Manual