PowerTec DFS-1 manual Input Debounce Value, Minimum Ratio, Float or Freeze, Master JOG Speed

Page 39

53.INPUT DEBOUNCE VALUE

USE PARAMETER #53 TO SET THE LENGTH OF TIME AN INPUT MUST BE ACTIVE TO BE ACTED UPON.

RANGE OF VALUES: 0000 0000h to 0000 00FFh

0 to 256

(decimal)

Default Value: 0000 0001h

1 (decimal)

Parameter #53 is the length of time, in 10 milliseconds (1 millisecond =.01 second), that a digital input must be active before it is considered legitimate. It is used primarily to eliminate the contact bounce (which may generate multiple commands) from relays used on inputs, but it can also prevent noise problems from push-buttons.

55.MINIMUM RATIO

USE PARAMETER #55 TO SET THE LENGTH OF TIME AN INPUT MUST BE ACTIVE TO BE ACTED UPON.

RANGE OF VALUES: 0000 0000h to 0001 869Fh 0 to 99,999 (decimal)

Default Value: 0000 0000h

0 (decimal)

Parameter #55 is the minimum ratio allowed at any time in SLAVE mode.

NOTE THAT THE RATIO CANNOT GO BELOW THIS VALUE, EVEN IN RESPONSE TO DOWN FUNCTIONS OR WHEN THE FLOAT PARAMETER IS SET. This parameter must be set with these restrictions in mind.

54.FLOAT OR FREEZE

USE PARAMETER #54 TO SELECT WHERE THE SETPOINT WILL BE ON START-UP.

RANGE OF VALUES: 0000 0000h to 0000 0001h

0 to 1

(decimal)

Default Value: 0000 0000h

0 (decimal)

When parameter #54 is set to 0000 0000h, the SETPOINT at start-up (whether after a stop or after a power loss) is always at zero. The speed SETPOINT “floats” down with the motor speed. A new speed SETPOINT must be entered or the UP MOP function may be used to set speed.

When parameter #54 is set to 0000 0001h, the SETPOINT at stop or power loss is “frozen” at the current value, and the DFS-1 will return to this speed when the drive next starts up. It is not necessary to enter a new SETPOINT on start-up if a return to the previous speed is desired.

Parameter #54 also affects the SLAVE mode, but the SETPOINT cannot go to less than the value of the minimum ratio (parameter #55) in FLOAT mode.

56.COMMUNICATIONS TURNAROUND DELAY

SETS THE # OF 500 MICROSECOND DELAYS FROM TRANSFER TO TRANSMIT

RANGE OF VALUES: 0000 0000h to 0000 007Fh 0 to 128 (decimal

57.MASTER JOG SPEED

USE PARAMETER #57 TO SET A JOG SPEED WHICH CAN BE TOGGLED IN AND OUT. RANGE OF VALUES: FFFE 7961h to 0001 869Fh

-99,999 to 99,999

(decimal)

Default Value: 0000 00C8h

100 (decimal)

The MASTER JOG Speed is the speed to which the motor will go when a JOG input is activated on one of the Digital inputs (any of the seven digital inputs may be programmed as a JOG input) when the DFS-1 is in the MASTER mode. If more than one input is programmed as a JOG input, they must both be present to activate the Master Jog Speed function (the inputs are logically ANDed).

Page 34

DFS-1 Manual

Revised 7/95

 

 

POWERTEC Ind. Corp.©

Image 39
Contents Microprocessor Based Brushless D.C Motor Controller DFS-1Subsidiary Powertec Industrial Corporation Errata October Additional InfoMounting -- Read this Entire Section Before Starting InstallationContents DFS 1 Setup Communication Protocol Retrofitting the Model 1000,1000A, or 1000ARMenu and Keypad Hierarchy Revised 7/95 Introduction Summary of Warranty and Disclaimer Connections Power ConnectionsAnalog Inputs Motor Encoder CableAnalog Outputs FrequencyinputFrequencyoutputdigital Inputs Digital Outputs CommunicationsDigital Out #4 Reverse This page WAS Intentionally Left Blank Default Setup Revised 7/95 VDC Power SuppliesInput Setup Function This Supply is for the Motor Encoder onlyOutputs #1 Reference Frequency Output Frequency Inputs OutputsDigital Inputs Input #1 Reference Frequency InputNodes Maximum Standard RS-48519.2K, and 38.4K baud CableThis page WAS Intentionally Left Blank Number Baud Rate Local / Remote ControlUnit ID Baud RateCommunications Protocol Modes of OperationTo 1 decimal Maximum Motor Speed Encoder Pulses PER RevolutionUSE Parameter #6 to SET the Absolute Maximum Motor Speed Slave Ramp Down Time Master Ramp UP TimeMaster Ramp Down Time Slave Ramp UP TimeEngineering Units Master Preset SpeedSlave Ratio Preset To 99,999 decimal Default Value 0000 06D6hAnalog Input #1 Mode Select To 32 decimal Default Value 0000 0001hMaximum Ratio Future use Analog Input #1 Signal ConditioningAnalog Input #1 LOW Engineering Units EGU Center valueAnalog Input #2 LOW Engineering Units EGU Analog Input #2 Mode SelectAnalog Input #2 Signal Conditioning Analog Input #1 High Engineering Units EGUAnalog Output #1 High Engineering Units EGU Analog Output #1 Mode SelectAnalog Output #2 Mode Select Analog Output #1 LOW Engineering Units EGUDefault Value 0000 0096h Analog Output #2 LOW Engineering Units EGUAnalog Output #2 High Engineering Units EGU Digital Input #4 Function Digital Input #1 FunctionDigital Input #2 Function Digital Input #3 FunctionDigital Output #1 Function Digital Input #5 FunctionDigital Input #6 Function Digital Input #7 FunctionDigital Output #3 Function Drive Gain SettingDrive Stability Setting Digital Output #2 FunctionJump or MOP Operation Drive Regenerative Current LimitPulse Multiplier Modulation and Operation ModesSlave Jump Down Amount Master Jump UP AmountMaster Jump Down Amount Slave Jump UP AmountFloat or Freeze Communications Turnaround DelayInput Debounce Value Minimum RatioEGU TAG Select Slave JOG Ratio Slave Preset #2Master Preset #2 ContactordelayThis page WAS Intentionally Left Blank DFS 1 Setup Basic Setup of the DFS-1 Controller Master Mode Setup Slave Mode Setup Inputs and Outputs Setup SET Parameter #3 to Select Which Functions are Remote Communications SetupThis parameter selects the Powertec binary protocol SET Parameter #56 for Communications Turn around DelayError Codes for ON-BOARD Display This page WAS Intentionally Left Blank Communications Protocol Command List Parameter List ERR DlestxuidcmddleetxcsmDLESTXUIDCMDCS4CS3 CS2CS1DLEETXCSM DlestxuidnakerrdleetxcsmDlestxuidcmdprmdleetxcsm Response If no errors and unit i.d. does not equalResponse If no errors DlestxuidackdleetxcsmDLESTXUIDACKDA4DA3 DLESTXUIDCMDPRMVL4Dlestxuidcmdatddleetxcsm DlestxuidcmddtadleetxcsmDlestxuidcmddigdleetxcsm DLESTXUIDCMDDTAVL4BIT PSN SMH Where Is unused Is Jog Is Preset Is Contactor AuxDLESTXUIDCMDDIGVL4 BIT PSN SMLBIT PSN RMH Message DLESTXUIDCMD0000Smhsmldleetxcsm BIT PSN RMLDLESTXUIDCMDAMDVL4 Attachmentb Parameter DescriptionAdditional Info Output Contactor Typical Dynamic Braking Typical This page WAS Intentionally Left Blank DFS-1 Model 1000 series retro-fit kit consists Quantity Quantity Pin Connector CableRevised 7/95 Appendix B Not visible in some modes Revised 7/95 Powertec Ind. Corp Figures 2 DFS-1 Manual Figures DFS-1 Manual Igur DFS-1 Manual Select AI ModeEnterEnter DFS-1 Manual Igur DFS-1 Manual Sel DFS-1 Manual Igures DFS-1 Manual Figures 29 DFS-1 Manual