PowerTec DFS-1 manual Master Mode Setup

Page 44

4.2MASTER MODE SETUP

1.SET PARAMETER #5 FOR THE MASTER MODE.

Set the basic operation in this parameter to

MASTER.

This parameter also has options for current control (see page 16). Selecting MASTER into the parameter takes care of the normal MASTER mode operation case because the default is normal current limits.

Other choices are torque limiting (either motoring or regenerative) and horsepower control. If one of these choices is made, it will be necessary to either:

1.Set up one analog input for a reference (see INPUTS and OUTPUTS), or

2.Make provision to supply reference through communications (see page 16).

2.SET PARAMETER #17 OR PARAMETER #21

IF AN ANALOG INPUT IS TO BE USED.

If an analog speed reference is to be used, either Analog Input #1 (see page 20) or Analog Input #2 (see page 22) must be set to Speed Reference Input. By default, Analog Input #1 is set up as a Speed Reference Input and Analog Input #2 is a General Purpose Input.

You must also set parameter #18 (0 to 10VDC by default) or parameter #22 (4 to 20 milliamps default) for the type of input. Then set up the scaling (Engineering units) in parameters #19 and #20 for Analog Input #1, or parameters #22 and #23 for Analog Input #2.

If neither analog input is set up as a speed reference, then the speed reference must be supplied from the optional front panel control or from the communications.

3.SET PARAMETER #8 FOR THE MASTER ACCELERATION RATE.

Set the master speed acceleration time in milliseconds (1 millisecond = .001 second). The range is from 0 (speed changes are step functions) to 255 seconds.

4.SET PARAMETER #9 FOR THE MASTER DECELERATION RATE.

Set the master speed deceleration time in milliseconds (1 millisecond = .001 second). The range is from 0 (speed changes are step functions) to 255 seconds.

5.SET PARAMETER #12 FOR A MASTER PRESET SPEED.

This step is optional, if you wish to use a preset speed which can be toggled by the PRESET function. Enter the speed in Engineering Units.

6.SET PARAMETER #54 FOR SETPOINT CONDITION (FLOAT OR FREEZE) AT START-UP.

If you want the motor to return to the speed at which it was running prior to shutdown or power loss, set this parameter to Freeze.

If you want the motor to wait for the speed to be reentered after a stop or power loss, enter Float in this parameter. See page 30.

7.SET PARAMETER #48 FOR JUMP OR MOP MODE.

Jump mode operation is to make UP/DOWN speed changes temporary. MOP mode makes the DFS-1 act like a Motor Operated Potentiometer. See page 28.

8.SET PARAMETER #49 FOR MASTER JUMP UP AMOUNT.

This is the amount (in Engineering Units) by which the speed command will increase when the UP function is activated. See page 29.

9.SET PARAMETER #50 FOR MASTER JUMP DOWN AMOUNT.

This is the amount (in Engineering Units) by which the speed command will decrease when the DOWN function is activated. See page 29.

Revised 7/95

DFS-1 Manual

Page 39

POWERTEC Ind. Corp.©

 

 

Image 44
Contents DFS-1 Microprocessor Based Brushless D.C Motor ControllerSubsidiary Powertec Industrial Corporation Errata Additional Info OctoberInstallation Mounting -- Read this Entire Section Before StartingContents DFS 1 Setup Menu and Keypad Hierarchy Communication ProtocolRetrofitting the Model 1000,1000A, or 1000AR Revised 7/95 Introduction Summary of Warranty and Disclaimer Power Connections ConnectionsMotor Encoder Cable Analog InputsFrequencyinput Analog OutputsFrequencyoutputdigital Inputs Digital Out #4 Reverse Digital OutputsCommunications This page WAS Intentionally Left Blank Default Setup Revised 7/95 Power Supplies Input Setup FunctionThis Supply is for the Motor Encoder only VDCFrequency Inputs Outputs Digital InputsInput #1 Reference Frequency Input Outputs #1 Reference Frequency OutputStandard RS-485 19.2K, and 38.4K baudCable Nodes MaximumThis page WAS Intentionally Left Blank Local / Remote Control Unit IDBaud Rate Number Baud RateTo 1 decimal Communications ProtocolModes of Operation USE Parameter #6 to SET the Absolute Maximum Motor Speed Maximum Motor SpeedEncoder Pulses PER Revolution Master Ramp UP Time Master Ramp Down TimeSlave Ramp UP Time Slave Ramp Down TimeMaster Preset Speed Slave Ratio PresetTo 99,999 decimal Default Value 0000 06D6h Engineering UnitsMaximum Ratio Analog Input #1 Mode SelectTo 32 decimal Default Value 0000 0001h Analog Input #1 Signal Conditioning Analog Input #1 LOW Engineering Units EGUCenter value Future useAnalog Input #2 Mode Select Analog Input #2 Signal ConditioningAnalog Input #1 High Engineering Units EGU Analog Input #2 LOW Engineering Units EGUAnalog Output #1 Mode Select Analog Output #2 Mode SelectAnalog Output #1 LOW Engineering Units EGU Analog Output #1 High Engineering Units EGUAnalog Output #2 High Engineering Units EGU Default Value 0000 0096hAnalog Output #2 LOW Engineering Units EGU Digital Input #1 Function Digital Input #2 FunctionDigital Input #3 Function Digital Input #4 FunctionDigital Input #5 Function Digital Input #6 FunctionDigital Input #7 Function Digital Output #1 FunctionDrive Gain Setting Drive Stability SettingDigital Output #2 Function Digital Output #3 FunctionDrive Regenerative Current Limit Pulse MultiplierModulation and Operation Modes Jump or MOP OperationMaster Jump UP Amount Master Jump Down AmountSlave Jump UP Amount Slave Jump Down AmountCommunications Turnaround Delay Input Debounce ValueMinimum Ratio Float or FreezeSlave JOG Ratio Slave Preset #2 Master Preset #2Contactordelay EGU TAG SelectThis page WAS Intentionally Left Blank DFS 1 Setup Basic Setup of the DFS-1 Controller Master Mode Setup Slave Mode Setup Inputs and Outputs Setup Communications Setup This parameter selects the Powertec binary protocolSET Parameter #56 for Communications Turn around Delay SET Parameter #3 to Select Which Functions are RemoteError Codes for ON-BOARD Display This page WAS Intentionally Left Blank Communications Protocol Command List Parameter List Dlestxuidcmddleetxcsm DLESTXUIDCMDCS4CS3 CS2CS1DLEETXCSMDlestxuidnakerrdleetxcsm ERRResponse If no errors and unit i.d. does not equal Response If no errorsDlestxuidackdleetxcsm DlestxuidcmdprmdleetxcsmDLESTXUIDCMDPRMVL4 DlestxuidcmdatddleetxcsmDlestxuidcmddtadleetxcsm DLESTXUIDACKDA4DA3DLESTXUIDCMDDTAVL4 DlestxuidcmddigdleetxcsmWhere Is unused Is Jog Is Preset Is Contactor Aux DLESTXUIDCMDDIGVL4BIT PSN SML BIT PSN SMHMessage DLESTXUIDCMD0000 SmhsmldleetxcsmBIT PSN RML BIT PSN RMHAttachmentb Parameter Description DLESTXUIDCMDAMDVL4Additional Info Output Contactor Typical Dynamic Braking Typical This page WAS Intentionally Left Blank Quantity Pin Connector Cable DFS-1 Model 1000 series retro-fit kit consists QuantityRevised 7/95 Appendix B Not visible in some modes Revised 7/95 Powertec Ind. Corp Figures 2 DFS-1 Manual Figures DFS-1 Manual Igur DFS-1 Manual Select AI ModeEnterEnter DFS-1 Manual Igur DFS-1 Manual Sel DFS-1 Manual Igures DFS-1 Manual Figures 29 DFS-1 Manual