PowerTec DFS-1 manual Slave Mode Setup

Page 45

4.3SLAVE MODE SETUP

1.SET PARAMETER #5 FOR THE SLAVE MODE.

Set basic operation in this parameter to 1 for SLAVE mode. For INVERSE SLAVE mode enter 2. INVERSE SLAVE mode affects the way a setpoint is entered.

This parameter also has options for current control (see page 16). Setting a 1 takes care of the normal SLAVE mode because the default is normal current limits.

Other choices are torque limiting (either motoring or regenerative) and horsepower control. For these options see page 16.

2.SET PARAMETER #17 OR PARAMETER #21

IF AN ANALOG INPUT IS TO BE USED.

If an analog speed reference is to be followed in SLAVE mode, either Analog Input #1 (see page 20) or Analog Input #2 (see page 22) must be set to 1 (Speed Reference Input). By default, Analog Input #1 is set up as a Speed Reference Input.

You must also set parameter #18 (0 to 10VDC by default) or parameter #22 for the type of input. Then set up the scaling parameters #19 and #20, or #22 and #23.

If neither analog input is set up as a speed reference input, then the speed reference to be followed must be supplied from the Frequency Reference In.

3.SET PARAMETER #15 FOR THE BASE RATIO.

This is the number which is used to allow the SETPOINT to be set at a desired number instead of at a number dictated by gear ratios, motor speeds, and other factors. See page 19.

4.SET PARAMETER #16 FOR THE MAXIMUM RATIO.

This setting is the highest ratio allowed under any circumstances.

5.SET PARAMETER #55 FOR THE MINIMUM RATIO.

This setting is the smallest ratio allowed under any circumstances.

6.SET PARAMETER #10 FOR THE SLAVE ACCELERATION RATE.

Set slave speed acceleration time in milliseconds (1 millisecond = .001 second). The range is from 0 (speed changes are step functions) to 255 seconds. See page 18.

7.SET PARAMETER #11 FOR THE SLAVE DECELERATION RATE.

Set the slave speed deceleration time in milliseconds (1 millisecond = .001 sec). The range is from 0 (speed changes are step functions) to 255 seconds. See page 18.

8.SET PARAMETER #13 FOR A SLAVE PRESET RATIO.

This step is optional, if you wish to use a preset ratio which can be toggled by the PRESET function. Enter the speed in Engineering Units.

9.SET PARAMETER #54 FOR SETPOINT CONDITION AT START-UP.

If you want the motor to return to the ratio at which it was running prior to shutdown or power loss, set this parameter to 1. If you want the motor to wait for the ratio to be reentered after a stop or power loss, enter 0. See page 30.

10.SET PARAMETER #48 FOR JUMP OR MOP MODE.

Jump mode operation is to make UP/DOWN ratio changes temporary. MOP mode makes the DFS-1 act like a Motor Operated Potentiometer. See page 28.

11.SET PARAMETERS #51 AND #52 FOR SLAVE JUMP UP/DOWN AMOUNTS.

These are the amounts (in Engineering Units) by which the ratio command will increase or decrease when the UP or DOWN functions are activated. See page 29.

Page 40

DFS-1 Manual

Revised 7/95

 

 

POWERTEC Ind. Corp.©

Image 45
Contents Microprocessor Based Brushless D.C Motor Controller DFS-1Subsidiary Powertec Industrial Corporation Errata October Additional InfoMounting -- Read this Entire Section Before Starting InstallationContents DFS 1 Setup Communication Protocol Retrofitting the Model 1000,1000A, or 1000ARMenu and Keypad Hierarchy Revised 7/95 Introduction Summary of Warranty and Disclaimer Connections Power ConnectionsAnalog Inputs Motor Encoder CableAnalog Outputs FrequencyinputFrequencyoutputdigital Inputs Digital Outputs CommunicationsDigital Out #4 Reverse This page WAS Intentionally Left Blank Default Setup Revised 7/95 Input Setup Function Power SuppliesThis Supply is for the Motor Encoder only VDCDigital Inputs Frequency Inputs OutputsInput #1 Reference Frequency Input Outputs #1 Reference Frequency Output19.2K, and 38.4K baud Standard RS-485Cable Nodes MaximumThis page WAS Intentionally Left Blank Unit ID Local / Remote ControlBaud Rate Number Baud RateCommunications Protocol Modes of OperationTo 1 decimal Maximum Motor Speed Encoder Pulses PER RevolutionUSE Parameter #6 to SET the Absolute Maximum Motor Speed Master Ramp Down Time Master Ramp UP TimeSlave Ramp UP Time Slave Ramp Down TimeSlave Ratio Preset Master Preset SpeedTo 99,999 decimal Default Value 0000 06D6h Engineering UnitsAnalog Input #1 Mode Select To 32 decimal Default Value 0000 0001hMaximum Ratio Analog Input #1 LOW Engineering Units EGU Analog Input #1 Signal ConditioningCenter value Future useAnalog Input #2 Signal Conditioning Analog Input #2 Mode SelectAnalog Input #1 High Engineering Units EGU Analog Input #2 LOW Engineering Units EGUAnalog Output #2 Mode Select Analog Output #1 Mode SelectAnalog Output #1 LOW Engineering Units EGU Analog Output #1 High Engineering Units EGUDefault Value 0000 0096h Analog Output #2 LOW Engineering Units EGUAnalog Output #2 High Engineering Units EGU Digital Input #2 Function Digital Input #1 FunctionDigital Input #3 Function Digital Input #4 FunctionDigital Input #6 Function Digital Input #5 FunctionDigital Input #7 Function Digital Output #1 FunctionDrive Stability Setting Drive Gain SettingDigital Output #2 Function Digital Output #3 FunctionPulse Multiplier Drive Regenerative Current LimitModulation and Operation Modes Jump or MOP OperationMaster Jump Down Amount Master Jump UP AmountSlave Jump UP Amount Slave Jump Down AmountInput Debounce Value Communications Turnaround DelayMinimum Ratio Float or FreezeMaster Preset #2 Slave JOG Ratio Slave Preset #2Contactordelay EGU TAG SelectThis page WAS Intentionally Left Blank DFS 1 Setup Basic Setup of the DFS-1 Controller Master Mode Setup Slave Mode Setup Inputs and Outputs Setup This parameter selects the Powertec binary protocol Communications SetupSET Parameter #56 for Communications Turn around Delay SET Parameter #3 to Select Which Functions are RemoteError Codes for ON-BOARD Display This page WAS Intentionally Left Blank Communications Protocol Command List Parameter List DLESTXUIDCMDCS4CS3 CS2CS1DLEETXCSM DlestxuidcmddleetxcsmDlestxuidnakerrdleetxcsm ERRResponse If no errors Response If no errors and unit i.d. does not equalDlestxuidackdleetxcsm DlestxuidcmdprmdleetxcsmDlestxuidcmdatddleetxcsm DLESTXUIDCMDPRMVL4Dlestxuidcmddtadleetxcsm DLESTXUIDACKDA4DA3Dlestxuidcmddigdleetxcsm DLESTXUIDCMDDTAVL4DLESTXUIDCMDDIGVL4 Where Is unused Is Jog Is Preset Is Contactor AuxBIT PSN SML BIT PSN SMHSmhsmldleetxcsm Message DLESTXUIDCMD0000BIT PSN RML BIT PSN RMHDLESTXUIDCMDAMDVL4 Attachmentb Parameter DescriptionAdditional Info Output Contactor Typical Dynamic Braking Typical This page WAS Intentionally Left Blank DFS-1 Model 1000 series retro-fit kit consists Quantity Quantity Pin Connector CableRevised 7/95 Appendix B Not visible in some modes Revised 7/95 Powertec Ind. Corp Figures 2 DFS-1 Manual Figures DFS-1 Manual Igur DFS-1 Manual Select AI ModeEnterEnter DFS-1 Manual Igur DFS-1 Manual Sel DFS-1 Manual Igures DFS-1 Manual Figures 29 DFS-1 Manual