Baldor MIN1853 manual Wire Size and Protection Devices, Delay a, Europe, Baldor, LinStep+

Page 15

Table 3-1 Wire Size and Protection Devices

Catalog Number

Incoming Power

Nominal Input

Continuous

Input

Input Fuse

Wire Gauge

Output

Breaker

Time

AWG

mm2

Voltage

Amps (RMS)

(A)

Delay (A)

(USA)

(Europe)

 

 

 

 

 

 

 

LX1P1A07F9

115V (1f)

7.9A

30

30

14

2.5

LX1P2A06

115V (1f)

6.0A

20

20

14

2.5

 

 

 

 

 

 

 

LX1P1A03

230V (1f)

3.9A

20

20

14

2.5

Note: All wire sizes are based on 75° C copper wire. Higher temperature smaller gauge wire may be used per NEC and local codes. Recommended fuses/breakers are based on 25° C ambient, maximum continuous driver output current and no harmonic current.

Power Connections Power connections are shown in Figures 3-3 and 3-4.

Figure 3-3 115VAC Single Phase AC Power Connections

 

 

 

L1

Neutral

Earth

 

 

 

Alternate *

L1

 

 

 

 

 

 

 

 

 

 

Note 3 & 4

 

 

 

 

 

 

 

 

 

 

 

 

 

Fuse

 

 

Note 1

Note 1

* Circuit

 

 

 

 

 

 

 

 

Connection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Note 2

Breaker

 

 

 

 

Note 5

* Components not provided with driver.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Notes:

 

 

 

 

 

 

L

 

N

 

GND

 

 

 

 

 

 

 

 

 

 

 

1.

See “Protection Devices” described in this section.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.Metal conduit or shielded cable should be used. Connect

Baldor

conduits so the use of a Reactor or RC Device does not

LinStep+

interrupt EMI/RFI shielding.

3.

Use same gauge wire for Earth ground as is used for L and N.

 

 

(VDE (Germany) requires 10mm2 minimum, 6AWG). For CE

 

 

Compliance, connect Earth to the backplane of the enclosure.

 

4.

Reference EMC wiring in Section 8.

 

5.

GND is located on the motor terminal strip.

Figure 3-4 230VAC Single Phase AC Power Connections

 

 

 

L1

L2

Earth

 

 

 

 

Alternate *

L1

 

L2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Note 3 & 4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fuse

 

 

 

 

 

Note 1

Note 1 * Circuit

 

 

 

 

 

 

 

 

Connection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Breaker

 

 

 

Note 5

 

 

 

 

 

 

 

 

Note 2

 

 

 

 

* Components not provided with driver.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Notes:

 

L1

 

 

L2

 

GND

 

 

 

 

 

 

 

 

 

1.

See “Protection Devices” described in this section.

 

 

 

 

 

 

 

 

 

 

 

 

2.

Metal conduit or shielded cable should be used. Connect

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Baldor

 

 

 

 

 

 

 

conduits so the use of a Reactor or RC Device does not

 

 

LinStep+

 

 

 

 

 

 

 

interrupt EMI/RFI shielding.

 

 

 

 

3.Use same gauge wire for Earth ground as is used for L and N. (VDE (Germany) requires 10mm2 minimum, 6AWG). For CE Compliance, connect Earth to the backplane of the enclosure.

4.Reference EMC wiring in Section 8.

5.GND is located on the motor terminal strip.

3-4Receiving & Installation

MN1853

Image 15
Contents LinStep+ Single-Axis Microstepping Indexer/Driver Table of Contents Prog POSProg To PAD From Troubleshooting Iv Table of Contents MN1853 Limited Warranty Section General InformationCE Compliance Product Notice Intended use Could result in injury or deathCould result in damage to property Voltages that are conducted to its power input terminals. Do not touch any circuit board, power device or electricalConnection before you first ensure that power has been Do not apply AC power before you ensure that grounds areDriver should have specifications compatible to the drive Extend more than 0.2 5 into keypad assemblyInstead, we recommend using a four wire Wye Power is removed from the driveSection Product Overview OverviewMotors Product Overview MN1853 Receiving & Inspection Section Receiving and InstallationPower Dissipation Mechanical InstallationRecommended System Grounding for UL Recommended System Grounding 1 phase for CESystem Grounding Ungrounded Distribution System Input Power ConditioningBaldor Wire Size and Protection DevicesDelay a EuropeConnection Locations 115VAC, 1 Axis Tools Required Keypad Nullmodem ConnectionsRS-232 PC Connections 9 & 25 Pin RS-232 Cable Connections for UL InstallationsRules for Daisy Chain Operation Daisy Chain ConnectionsHow many resistors should my system have? What is a termination resistor?Where are these resistors placed? RS485 PC Connections13 RS485 4 Wire Multi-Drop for UL Installations Discrete I/O Connections Limits ConnectionsET± Encoder Signal PVS100 Danaher 9-Pin D Encoder Color Code+5VDC Ground GND Motor ConnectorAY0165A00 Leadwire Connection 9 pin to flying leads Interlock Intlk21 Opto Racks DB25 Pin to Screw Terminal Converter PNP ConverterPNP Action Display Comments Start-Up ProcedurePower Off Checks Power On ChecksSection Keypad Operation OverviewF1, F2, F3 Menus Menu KeyMain Menu JOG F2Decimal Point CommaAlpha New Program Edit MenuEdit an existing program Save the programExample of Naming a Program Naming a programUse the =O keys for additional alpha characters Entering Characters with the Alpha Key In edit modeSubmenu Setup Parameter Description of Setup Parameter Edit, Setup SubmenuPress EDIT, POS F3 Press YES F1 or no F3 Sequentially Eeprom message disappears Pressing Help in the Main MenuPressing Help in Menus and Sub-Menus Pressing Help In the Program Edit functionCOPY, to PAD Submenu Keypad Operation MN1853 Procedure Format Definition Section SetupValue Range AR unloaded + 12.987 x log + log 155 Tm * JrFine-Tuning Offsets Value HighValue OFF Range N/A ValueApplication Notes Configuring Encoder Resolution ERi Configure Your Application Mechanics Value inch Char Keypad Display Input Character Description Configure the I/ONo additional interrupts will be seen By one-half Over Current AMP FaultFault BrakeConfigure the Output States Configure the Optional Lxopto 44/88Configure JOG Parameters Configure End of Travel Switch PolarityConfigure Home Parameters Configuring Home Edge HEi Configure Power-up Program Value Enabled Range Enabled, Disabled Configure Serial CommunicationsVEL1 Configure Miscellaneous Setup ParametersData Type Description of Display Data Type POS1Password Type Description Gives access to these menus General Password RulesSetup MN1853 Examples Keypad Program Command ListSection Keypad Programming Value UnitsValue Units Range ExampleAC2 DE.5 VE12 DA3 GO DA3 GO DA3 GO DC Distance to Change Examples of DC move profiles, AC = seconds, VE=ips Example Distance to ChangeAC.1 VE60 DI2 GO DI1 GO DI-4 GO Value Units Range N/A LP2 DI3 GO EBIF2,1 EN EB DI2 GO Copy DEL =12 =13 =17 =18 =22 =23=26 =27 =28 RUN EditExample 3-Screen Menu Program GH Start Home Value N/A Units N/A Range N/A Units Range N/A Value N/A Units N/A Range i=1-16IF10 Gtpart a EB =1-400, name = any legal program nameIFPARTS=25 GS20 EB Units RangeIV12,LENGTH LppiecesDilength Value Units N/A Range N/A Syntax MC+ MC Move Continuous Move Continuous MS27,COUNT VE5 DA20 GO Powerup ONL,GTON EOTGthome Main= starting output number Syntax RGr RG Registration Value N/A Units seconds SQRESULT=0 SQ27.96,SQRESULTValue N/A Units N/A ST1 AC1 DE1 VE25 DA6 GO VE50 DA0 GO ENSyntax VEr VE Velocity Summary of Expressions, Operators and Functions Helpful Hints Programming your applicationProgramming Overview Variable Names Example of Hosted ModeVariables ProgramVariable Name Description of Built-in Variable Type Built-in VariablesUsing Built-in Variable Arowrel Non-Volatile Variables PartsLpnumber AO15=VOLTAGE + Error Arithmetic Operands and EquationsBoolean Operators WTAI12MAX Temp Logical OperatorsIncrement/Decrement Variables Expressions Other Programming SamplesCreate a Message and Read an Input Variable Setting an Output=On on-the-flyDigit BCD=4 Digit BCD+2TW Read a 4 Digit BCD number, 2 Digits at a timeReading an Analog Input Value GET 4 BcdsSection Troubleshooting 1Operating Mode Indications, 1 AxisAdditional Information General Additional Information Serial Communications Problems Troubleshooting MN1853 Section Specifications & Product Data IdentificationLinStep+ LX 1 P 1 A- 0xF9 VDC General SpecificationsProtection & Indicators Description VACDimensions Specifications & Product Data MN1853 EMC Conformity and CE Marking Wiring of Shielded Screened CablesSection CE Guidelines CE Declaration of ConformityGrounding Earth EMC Wiring TechniqueCable Screens Grounding EMC Installation InstructionsInput Signal Cable Grounding Simulated Encoder Output Cable GroundingEncoder Cable Grounding Programming Template Appendix aAppendix MN1853 MN1853 Appendix A-3 Remote Keypad Mounting Template Baldor Electric Company MN1853 01 C&J Baldor Electric CompanyLinStep+ Single-Axis Microstepping Indexer/Driver