Baldor MIN1853 manual Section Troubleshooting, Additional Information General

Page 92

Section 7

Troubleshooting

Overview

 

The system troubleshooting procedures involve observing the status of the LED’s.

 

 

 

The tables in this section provide information related to the indications provided by

 

 

 

these devices.

 

 

 

 

Table 7-1Operating Mode Indications, 1 Axis

 

 

 

 

 

LED

 

Color

Status

Comments

ON

 

Green

Power is applied.

Not a failure.

 

 

Yellow

Power is applied and “Shutdown” was issued.

Not a failure if Indexer issued a valid shutdown

 

 

 

 

command.

 

 

Red

Power is applied and “Overtemperature” condition

Allow driver to cool down. Determine reason for

 

 

 

exists.

overtemperature, high ambient temperature, lack

 

 

 

 

of air flow, motor current too high, adjust standby

 

 

 

 

current.

Step

 

Green

Incoming Steps, Direction CW

Not a failure.

 

 

Yellow

Incoming Steps, Direction CCW

Not a failure.

 

 

Red

 

 

Bus

 

Green

 

 

 

 

Yellow

Continuous on=overvoltage condition

Verify input voltage is proper. Not a failure.

 

 

 

Flashing = Regen condition

Regen operation is not a failure.

 

 

 

 

 

 

 

Red

Undervoltage condition

Verify input voltage is proper

FLT

 

Green

 

 

 

 

Yellow

Interlock condition.

Verify motor connections.

 

 

Red

Motor short.

Replace motor.

Additional Information (General)

Symptom

Possible Cause

Possible Remedies

The keypad is blank

The keypad is not receiving +5VDC.

Verify all wiring is correct.

with no backlight.

 

Verify that the +5VDC is between 4.8 and 5.2V.

 

 

 

Display is difficult to

Contrast ratio is incorrectly set

Adjust the contrast with the pot on the back of the keypad.

read

 

 

The ON LED is yellow.

FLASH memory is corrupt.

The operating system and user programs must be reloaded.

The ON LED is red.

A Fault has occurred.

The fault can be determined with the keypad or by using

 

 

serial status commands (SS, SA, SD).

Motor moves the wrong

Wrong Gear Ratio.

Check distance units

distance

 

 

Motor stalled.

Check motor current, inductance, anti–resonance settings

 

 

Check Speed Torque required for move, reduce

 

 

acceleration.

Motor stalls

Acceleration and/or velocity too high.

Reduce acceleration and/or velocity.

 

Motor configured incorrectly.

Check motor current, inductance and anti–resonance

 

 

settings.

Motor direction is wrong

The motor phases are miswired.

Verify connections, or swap A+ with A–.

 

The system real direction is reversed.

Change the control’s direction parameter.

The control does not re-

The keypad is disabled.

Check the switch settings on the back of the keypad.

spond to keypad input.

 

 

The motor “whines”

The inductance or anti–resonance

Verify the Inductance setting. Operation is best with motors

 

setting is incorrect.

4 mH or above. If this does not help, verify the

 

 

anti–resonance setting.

MN1853

Troubleshooting 7-1

Image 92
Contents LinStep+ Single-Axis Microstepping Indexer/Driver Table of Contents Prog To PAD From ProgPOS Troubleshooting Iv Table of Contents MN1853 CE Compliance Limited WarrantySection General Information Could result in damage to property Product Notice Intended useCould result in injury or death Do not touch any circuit board, power device or electrical Connection before you first ensure that power has beenDo not apply AC power before you ensure that grounds are Voltages that are conducted to its power input terminals.Extend more than 0.2 5 into keypad assembly Instead, we recommend using a four wire WyePower is removed from the drive Driver should have specifications compatible to the driveMotors Section Product OverviewOverview Product Overview MN1853 Section Receiving and Installation Power DissipationMechanical Installation Receiving & InspectionRecommended System Grounding 1 phase for CE Recommended System Grounding for ULInput Power Conditioning System Grounding Ungrounded Distribution SystemWire Size and Protection Devices Delay aEurope BaldorConnection Locations 115VAC, 1 Axis Keypad Nullmodem Connections Tools Required9 & 25 Pin RS-232 Cable Connections for UL Installations RS-232 PC ConnectionsDaisy Chain Connections Rules for Daisy Chain OperationWhat is a termination resistor? Where are these resistors placed?RS485 PC Connections How many resistors should my system have?13 RS485 4 Wire Multi-Drop for UL Installations ET± Discrete I/O ConnectionsLimits Connections +5VDC Encoder Signal PVS100 Danaher 9-Pin DEncoder Color Code Motor Connector AY0165A00 Leadwire Connection 9 pin to flying leadsInterlock Intlk Ground GND21 Opto Racks PNP DB25 Pin to Screw Terminal ConverterPNP Converter Start-Up Procedure Power Off ChecksPower On Checks Action Display CommentsF1, F2, F3 Section Keypad OperationOverview Menu Key Main MenuJOG F2 MenusAlpha Decimal PointComma Edit Menu New ProgramSave the program Edit an existing programNaming a program Example of Naming a ProgramEntering Characters with the Alpha Key In edit mode Use the =O keys for additional alpha charactersEdit, Setup Submenu Submenu Setup Parameter Description of Setup ParameterPress EDIT, POS F3 Press YES F1 or no F3 Pressing Help in the Main Menu Pressing Help in Menus and Sub-MenusPressing Help In the Program Edit function Sequentially Eeprom message disappearsCOPY, to PAD Submenu Keypad Operation MN1853 Section Setup Procedure Format DefinitionAR unloaded + 12.987 x log + log 155 Tm * Jr Value RangeValue OFF Fine-Tuning OffsetsValue High Application Notes Range N/AValue Configuring Encoder Resolution ERi Configure Your Application Mechanics Value inch Configure the I/O Char Keypad Display Input Character DescriptionNo additional interrupts will be seen By one-half AMP Fault FaultBrake Over CurrentConfigure the Optional Lxopto 44/88 Configure the Output StatesConfigure End of Travel Switch Polarity Configure JOG ParametersConfigure Home Parameters Configuring Home Edge HEi Configure Power-up Program Configure Serial Communications Value Enabled Range Enabled, DisabledConfigure Miscellaneous Setup Parameters Data Type Description of Display Data TypePOS1 VEL1General Password Rules Password Type Description Gives access to these menusSetup MN1853 Keypad Program Command List Section Keypad ProgrammingValue Units ExamplesAC2 DE.5 VE12 DA3 GO DA3 GO DA3 GO Value Units RangeExample DC Distance to Change Example Distance to Change Examples of DC move profiles, AC = seconds, VE=ipsAC.1 VE60 DI2 GO DI1 GO DI-4 GO IF2,1 EN EB DI2 GO Value Units Range N/ALP2 DI3 GO EB =12 =13 =17 =18 =22 =23 =26 =27 =28RUN Edit Copy DELExample 3-Screen Menu Program GH Start Home Value N/A Units N/A Range N/A Value N/A Units N/A Range i=1-16 Units Range N/A=1-400, name = any legal program name IF10 Gtpart a EBUnits Range IFPARTS=25 GS20 EBDilength IV12,LENGTHLppieces Value Units N/A Range N/A Syntax MC+ MC Move Continuous Move Continuous MS27,COUNT Powerup ONL,GTON EOT GthomeMain VE5 DA20 GO= starting output number Syntax RGr RG Registration SQRESULT=0 SQ27.96,SQRESULT Value N/A Units N/AST1 AC1 DE1 VE25 DA6 GO VE50 DA0 GO EN Value N/A Units secondsSyntax VEr VE Velocity Programming Overview Summary of Expressions, Operators and FunctionsHelpful Hints Programming your application Example of Hosted Mode VariablesProgram Variable NamesBuilt-in Variables Variable Name Description of Built-in Variable TypeUsing Built-in Variable Arowrel Lpnumber Non-Volatile VariablesParts Boolean Operators AO15=VOLTAGE + ErrorArithmetic Operands and Equations Logical Operators Increment/Decrement VariablesExpressions Other Programming Samples WTAI12MAX TempSetting an Output=On on-the-fly Create a Message and Read an Input VariableRead a 4 Digit BCD number, 2 Digits at a time Reading an Analog Input ValueGET 4 Bcds Digit BCD=4 Digit BCD+2TWAdditional Information General Section Troubleshooting1Operating Mode Indications, 1 Axis Additional Information Serial Communications Problems Troubleshooting MN1853 LinStep+ LX 1 P 1 A- 0xF9 Section Specifications & Product DataIdentification General Specifications Protection & Indicators DescriptionVAC VDCDimensions Specifications & Product Data MN1853 Wiring of Shielded Screened Cables Section CE GuidelinesCE Declaration of Conformity EMC Conformity and CE MarkingEMC Wiring Technique Grounding EarthEMC Installation Instructions Cable Screens GroundingEncoder Cable Grounding Input Signal Cable GroundingSimulated Encoder Output Cable Grounding Appendix a Programming TemplateAppendix MN1853 MN1853 Appendix A-3 Remote Keypad Mounting Template Baldor Electric Company Baldor Electric Company MN1853 01 C&JLinStep+ Single-Axis Microstepping Indexer/Driver