GE A071-0CG Invalid source number, Invalid SYS offset configured, Invalid TM offset configured

Page 30

 

ANSI X3.28/SRIO DPA

GE Energy Services

CONFIGURATION GUIDE

Invalid source number

Cause:

The configured master station address is invalid.

Remedy:

Ensure the configured Master Address in A071MAIN is not the broadcast address (255).

Invalid SYS offset configured

Cause:

The configured system partition offset is invalid.

Remedy:

Ensure the configured Sys Offset in A071MAIN is a positive value.

Ensure the configured Sys Offset is less than the Obj Offset.

Invalid TM offset configured

Cause:

The configured time partition offset is invalid.

Remedy:

Ensure the configured TM Offset in A071MAIN is a positive value.

Ensure the configured TM Offset is less than the EVNT Offset.

Mapped AI point not Found. Check config

Cause:

One of the mapped analog input points could not be located in the SPABUS configuration.

Remedy:

Ensure none of the Item Table Offsets in A071AIMP are greater than the number of records in the SPABUS item configuration table, A070ITEM.

Ensure all of the Item Table Offsets in A071AIMP refer only to records in the SPABUS item configuration table, A070ITEM, of type AI, PI, or Spare (-1).

Mapped AO point not Found. Check config

Cause:

One of the mapped analog output points could not be located in the SPABUS configuration.

Remedy:

Ensure none of the Item Table Offsets in A071AOMP are greater than the number of records in the SPABUS item configuration table, A070ITEM.

Ensure all of the Item Table Offsets in A071AOMP refer only to records in the SPABUS item configuration table, A070ITEM, of type AO or Spare (-1).

A071-0CG-2.02-2Restricted

18

Full

 

Image 30
Contents Ansi X3.28/SRIO DPA Trademark Notices Table of Contents Ansi X3.28/SRIO DPA System Overview Xii Read Access Flags List of FiguresAnsi X3.28/SRIO DPA List of Tables Viii About this Guide Purpose of this GuideWho Should Use this Guide Additional Documentation Overview Product PerspectiveXii Configuring Tables Ansi X3.28/SRIO DPA Configuration TablesConfiguration Sequence Configuring the Main Table A071MAIN Character TimesAnsi X3.28/SRIO DPA GE Energy Services Baud Rate One Character Time ms Configuring the Mapping Tables Mapping Table Configuration Parameters Configuring Wesmaint for the Ansi X3.28/SRIO DPA Log-In User B014USERRead Access Flags Fatal Error Messages Appendix AError MessagesError Messages Ansi Application process diedCant create T071 exchange Cant allocate rx sinksCant create required exchanges. Suspending Cant get enough memory for Ansi Application. SuspendingCant spawn/activate E071 process Cant set communications timersCant set configured bit rate Cant spawn/activate L071 processInvalid AO offset configured Invalid AI offset configuredInvalid Analog Format configured 32 BIN, 6 or 3 BCD Invalid checksum configured Bcc or CrcInvalid do offset configured Invalid DD offset configuredInvalid DI offset configured Invalid embedded response enable Yes or NoInvalid modem enable Yes or No Invalid Evnt offset configuredInvalid EV offset configured Invalid OBJ offset configuredInvalid Retransmit analog configured -1 to Invalid parity configured None, Even, OddInvalid PD offset configured Invalid Retransmit digital configured -1 toMapped AI point not Found. Check config Invalid SYS offset configuredInvalid TM offset configured Mapped AO point not Found. Check configMapped EV point not Found. Check config Mapped DI point not Found. Check configMapped do point not Found. Check config Missing Configuration ... DeletingAnsi X3.28/SRIO DPA Glossary of Terms AsciiWIN List of Acronyms and Abbreviations