GE A071-0CG Invalid ACK time-out, Invalid AI offset configured, Invalid AO offset configured

Page 26

 

ANSI X3.28/SRIO DPA

GE Energy Services

CONFIGURATION GUIDE

Invalid ACK time-out

Cause:

The configured ACK Timeout is invalid.

Remedy:

Ensure the configured ACK Timeout in A071MAIN is a positive value.

Invalid AI offset configured

Cause:

The configured analog input offset is invalid.

Remedy:

Ensure the configured AI Offset in A071MAIN is a positive value.

Ensure the configured AI Offset is less than the AO Offset.

Invalid Analog Format configured 32 (BIN), 6 or 3 (BCD)

Cause:

The configured Analog Formats is invalid.

Remedy:

Ensure the configured Analog Format in A071MAIN is either 32 Bit Binary (32), 6 Digit BCD (6), or 3 Digit BCD (3).

Invalid AO offset configured

Cause:

The configured analog output offset is invalid.

Remedy:

Ensure the configured AO Offset in A071MAIN is a positive value.

Ensure the configured AO Offset is less than the PD Offset.

Invalid checksum configured (B)cc or (C)rc

Cause:

The configured checksum type is invalid.

Remedy:

Ensure the configured Checksum in A071MAIN is either BCC (B) or CRC (C).

Invalid COMX configuration

Cause:

The configured port name is invalid.

Remedy:

Ensure the configured Port in A071MAIN is in the range "COM1" to "COM7".

A071-0CG-2.02-2Restricted

14

Full

 

Image 26
Contents Ansi X3.28/SRIO DPA Trademark Notices Table of Contents Ansi X3.28/SRIO DPA System Overview Xii Read Access Flags List of FiguresAnsi X3.28/SRIO DPA List of Tables Viii Who Should Use this Guide About this GuidePurpose of this Guide Additional Documentation Overview Product PerspectiveXii Configuring Tables Ansi X3.28/SRIO DPA Configuration TablesConfiguration Sequence Configuring the Main Table A071MAIN Character TimesAnsi X3.28/SRIO DPA GE Energy Services Baud Rate One Character Time ms Configuring the Mapping Tables Mapping Table Configuration Parameters Configuring Wesmaint for the Ansi X3.28/SRIO DPA Log-In User B014USERRead Access Flags Fatal Error Messages Appendix AError MessagesError Messages Ansi Application process diedCant create T071 exchange Cant allocate rx sinksCant create required exchanges. Suspending Cant get enough memory for Ansi Application. SuspendingCant spawn/activate E071 process Cant set communications timersCant set configured bit rate Cant spawn/activate L071 processInvalid AO offset configured Invalid AI offset configuredInvalid Analog Format configured 32 BIN, 6 or 3 BCD Invalid checksum configured Bcc or CrcInvalid do offset configured Invalid DD offset configuredInvalid DI offset configured Invalid embedded response enable Yes or NoInvalid modem enable Yes or No Invalid Evnt offset configuredInvalid EV offset configured Invalid OBJ offset configuredInvalid Retransmit analog configured -1 to Invalid parity configured None, Even, OddInvalid PD offset configured Invalid Retransmit digital configured -1 toMapped AI point not Found. Check config Invalid SYS offset configuredInvalid TM offset configured Mapped AO point not Found. Check configMapped EV point not Found. Check config Mapped DI point not Found. Check configMapped do point not Found. Check config Missing Configuration ... DeletingAnsi X3.28/SRIO DPA Glossary of Terms AsciiWIN List of Acronyms and Abbreviations