ANSI X3.28/SRIO DPA |
|
CONFIGURATION GUIDE | GE Energy Services |
Invalid DD offset configured
Cause:
•The configured direct data offset is invalid.
Remedy:
•Ensure the configured DD Offset in A071MAIN is a positive value.
•Ensure the configured DD Offset is less than the Sys Offset.
Invalid destination number
Cause:
•The configured RTU address is invalid.
Remedy:
•Ensure the configured RTU Address in A071MAIN is not the broadcast address (255).
Invalid DI offset configured
Cause:
•The configured digital input offset is invalid.
Remedy:
•Ensure the configured DI Offset in A071MAIN is a positive value.
•Ensure the configured DI Offset is less than the DO Offset.
Invalid DO offset configured
Cause:
•The configured digital output offset is invalid.
Remedy:
•Ensure the configured DO Offset in A071MAIN is a positive value.
•Ensure the configured DO Offset is less than the EV Offset.
Invalid embedded response enable (Y)es or (N)o
Cause:
•The configured embedded response enable parameter is invalid.
Remedy:
•Ensure the configured Embedded Rsp in A071MAIN is either Yes (Y) or No (N).
Invalid event timeout configured
Cause:
•The configured spontaneous event timeout is invalid.
Remedy:
•Ensure the configured Spontaneous Event Timeout in A071MAIN is a positive value.