Mounting the Power System

Location and Environment

Data Power Solutions (rack-mounted and desktop versions) meet the safety and fire enclosure requirements (as specified in AS/NZS 60950.1, EN 60950-1, IEC 60950-1 and UL 60950-1).

Rack-Mounted Versions: APS3-05X and APS6-05X series power systems may be mounted in 19-inch wide host equipment racks (enclosed or open type) securely bolted to the floor.

Desktop Versions: APS3-06X series power systems may be positioned on any surface that supports the weight of the power system.

The location must provide adequate airflow around the unit, (as per Clearance Requirements below) in an atmosphere free from excessive dust, corrosive fumes, or conductive contaminants.

Dust build-up within the DC power system may cause premature failure. In dusty environments filter the ventilation air entering the equipment room. Ensure regular cleaning of the air filters.

VRLA lead acid batteries can emit explosive gases and must be installed with adequate ventilation. Refer to the battery manufacturer or supplier for advice on minimum ventilation levels, or refer to Application Note AN0080 available from Eaton.

Clearance Requirements

All Data Power Solutions (rack-mounted and desktop versions) require the following minimum clearances:

Front and Rear Clearance – 50 mm (2”) from walls and other equipment, required for optimum system cooling and access.

Top and Bottom Clearance – None

Rack Installation (rack-mounted versions only)

" APS3-05X and APS6-05X power systems come pre-assembled with two 19-inch rack-mounting brackets.

# The two rack-mounting brackets can be moved backwards and lined up with alternative bracket-mounting holes, to provide greater mounting flexibility. Ensure the same screws are used.

2

1

3-2

Copyright © 2005-2006 Eaton Corporation. All Rights Reserved.

IPN 997-00012-41D December 2006

 

Image 22
Contents Data Power Solutions Installation Guide Copyright 2005-2006 Eaton Corporation All Rights Reserved About This Guide For Further Information and Technical Assistance About This GuideTable of Contents Table of Contents Chapter OperationsOverview General DescriptionTopic Data Power Solutions Product Range General DescriptionData Power Solutions Product Range APS3-05X Rack-Mounted VersionsAPS3-06X Desktop Versions APS6-05X Rack-Mounted Versions Access Power Rectifiers SM45 Supervisory Module SM45 Supervisory ModuleLow Voltage Disconnect if applicable Pre-Installation Pre-Installation AC InputsBatteries if applicable DC Outputs Servicing Inspecting the Equipment and Reporting Damage Installation Rack Installation rack-mounted versions only Mounting the Power SystemInstallation Location and EnvironmentConnecting the DC Load Cables DC Installation PracticesDC Installation Practices Installation DC Load Cable Specifications APS3-05X and APS6-05X Rack-Mounted VersionsConnecting the DC Load Cables Fit load cable clampsFit cables and sleeves Battery Sizing Installing the External Batteries if applicableInstalling the External Batteries if applicable Battery LocationBattery Cable Specifications Connecting the Battery Cables if applicableBattery Fault Protection Before You StartConnecting the Battery Cables if applicable Prepare cable clampRepeat for other battery cables if required Connecting the Battery Temperature Sensor CableMounting the Battery Temperature Sensor AC Installation Connecting the Power System to the AC SupplyAC Supply Requirements Commissioning Inserting the Access Power Rectifiers CommissioningPre-Power-Up Check Pre-Power-Up CheckChecklist Applying AC Power Configuring the Power System for OperationConfiguring the Power System for Operation Before you start, you needHotlink Click to … LVDPage Applying DC Power to the Load SM45 Operations About the SM45 Front Panel SM45 OperationsAbout the SM45 Front Panel To disable the audible indicator when an alarm is activeTo change the display contrast To scroll within a display mode To enter a display modeTo exit a display mode About Display ModesViewing System Values Main Display Mode Viewing System Values Main Display ModeTo view system values Important note about Rect Comms Lost alarm Viewing Alarms and System Status Messages Status View ModeRules for displaying alarms and system status To view and clear alarmsViewing and Editing Configuration Parameters Viewing and Editing Configuration ParametersTo view and edit a configuration parameter SM45 Operations Communications Communications Communications OptionsDirect Connection Ethernet DCTools Setup DCTools SetupSM45 Ethernet Setup Properties Direct Connection EthernetSetting Up Snmp Traps Parameter Configuration GuidelinesEntering the sysObjectID of a Power System Entering the sysObjectID of a Power SystemTo enter the sysObjectID of a power system using DCTools To synchronize the SM45 real-time clock using DCTools Synchronizing the SM45 Real-time ClockMaintenance Maintenance TroubleshootingProblem Possible Cause/s Required Action Troubleshooting LED Config Error Replacing a Rectifier Removing a RectifierPull out the rectifier Replacing a RectifierInserting a Rectifier Replacing AC Input Fuses Replacing AC Input FusesTo check and replace AC input fuses Replacing the SM45 Real-time Clock Battery Glossary of Alarms Partial AC Fail Rectifier Comms Lost Glossary of AlarmsMultiple Rectifier Fail Rectifier Fail Sensor Fail System OverloadBattery Current Limit BCL Control Function GlossaryLow Volts Disconnect Control Function GlossarySystem DC Output SpecificationsSystem AC Input EnvironmentWeight SpecificationsDimensions H, W, D APR48 RectifiersEquipment Incident Report SG/03 ISS04 Worldwide Support United States of AmericaPage Page Page SM45 Front Panel Menu Structure Configuration Mode Edit Mode