Page 25

Connecting the DC Load Cables

APS3-06X (Desktop Versions)

Before proceeding check you have:

4 x load cable clamps

8 x 25mm blunt ended screws

8 x 5mm and 4 x 10mm cable sleeves (50mm long)

Depending on the cables sizes, not all sleeves will be required.

1mm2 (18 AWG) cable for connection to 6A outlets

4mm2 (12 AWG) cable for connection to 25A outlets

Step 1 - Fit load cable clamps

Insert the square ends of the load cable clamps into the holes in the back of the system.

Engage two turns of each retaining screw. This will ensure that the clamp does not move when the wires and sleeves are inserted.

Fit all clamps even if you do not use them all. Tighten unused clamps to prevent access to the DC outputs.

Step 2 - Strip cable ends

Strip approximately 10mm (3/8”) from the cable ends. We recommend fitting cable ferrules over the cable ends.

Copyright © 2005-2006 Eaton Corporation. All Rights Reserved.

3-5

IPN 997-00012-41D December 2006

 

Image 25
Contents Data Power Solutions Installation Guide Copyright 2005-2006 Eaton Corporation All Rights Reserved About This Guide About This Guide For Further Information and Technical AssistanceTable of Contents Chapter Operations Table of ContentsOverview General DescriptionTopic General Description Data Power Solutions Product RangeAPS3-05X Rack-Mounted Versions Data Power Solutions Product RangeAPS3-06X Desktop Versions APS6-05X Rack-Mounted Versions Access Power Rectifiers SM45 Supervisory Module SM45 Supervisory ModuleLow Voltage Disconnect if applicable Pre-Installation AC Inputs Pre-InstallationBatteries if applicable DC Outputs Servicing Inspecting the Equipment and Reporting Damage Installation Installation Mounting the Power SystemRack Installation rack-mounted versions only Location and EnvironmentConnecting the DC Load Cables DC Installation PracticesDC Installation Practices APS3-05X and APS6-05X Rack-Mounted Versions Installation DC Load Cable SpecificationsFit load cable clamps Connecting the DC Load CablesFit cables and sleeves Installing the External Batteries if applicable Installing the External Batteries if applicableBattery Sizing Battery LocationBattery Fault Protection Connecting the Battery Cables if applicableBattery Cable Specifications Before You StartPrepare cable clamp Connecting the Battery Cables if applicableConnecting the Battery Temperature Sensor Cable Repeat for other battery cables if requiredMounting the Battery Temperature Sensor AC Installation Connecting the Power System to the AC SupplyAC Supply Requirements Commissioning Commissioning Inserting the Access Power RectifiersPre-Power-Up Check Pre-Power-Up CheckChecklist Configuring the Power System for Operation Applying AC PowerBefore you start, you need Configuring the Power System for OperationLVD Hotlink Click to …Page Applying DC Power to the Load SM45 Operations SM45 Operations About the SM45 Front PanelAbout the SM45 Front Panel To disable the audible indicator when an alarm is activeTo change the display contrast To exit a display mode To enter a display modeTo scroll within a display mode About Display ModesViewing System Values Main Display Mode Viewing System Values Main Display ModeTo view system values Rules for displaying alarms and system status Viewing Alarms and System Status Messages Status View ModeImportant note about Rect Comms Lost alarm To view and clear alarmsViewing and Editing Configuration Parameters Viewing and Editing Configuration ParametersTo view and edit a configuration parameter SM45 Operations Communications Communications Communications OptionsDirect Connection Ethernet SM45 Ethernet Setup DCTools SetupDCTools Setup Properties Direct Connection EthernetParameter Configuration Guidelines Setting Up Snmp TrapsEntering the sysObjectID of a Power System Entering the sysObjectID of a Power SystemTo enter the sysObjectID of a power system using DCTools Synchronizing the SM45 Real-time Clock To synchronize the SM45 real-time clock using DCToolsMaintenance Maintenance TroubleshootingProblem Possible Cause/s Required Action Troubleshooting LED Config Error Removing a Rectifier Replacing a RectifierReplacing a Rectifier Pull out the rectifierInserting a Rectifier Replacing AC Input Fuses Replacing AC Input FusesTo check and replace AC input fuses Replacing the SM45 Real-time Clock Battery Glossary of Alarms Multiple Rectifier Fail Glossary of AlarmsPartial AC Fail Rectifier Comms Lost Rectifier Fail Sensor Fail System OverloadControl Function Glossary Battery Current Limit BCLControl Function Glossary Low Volts DisconnectSystem AC Input SpecificationsSystem DC Output EnvironmentDimensions H, W, D SpecificationsWeight APR48 RectifiersEquipment Incident Report SG/03 ISS04 United States of America Worldwide SupportPage Page Page SM45 Front Panel Menu Structure Configuration Mode Edit Mode