Eaton Electrical SC200 DCTools Setup, SM45 Ethernet Setup, Properties Direct Connection Ethernet

Page 51

DCTools Setup

DCTools Setup

For your chosen communications option, configure the communications settings, in DCTools according to the table below.

Then check that DCTools communicates correctly.

Properties

Direct Connection

Ethernet

Comms Enabled

True

 

True

 

 

 

 

Protocol

S3P

 

S3P

 

 

 

 

Connect Using

COM1

 

Local Network

 

 

 

S3P Address

0

0

 

 

 

 

Server IP Address

 

10.64.129.1 (See Note 1)

 

 

 

Server Port

14000

 

 

 

Telnet

Cleared

Note 1: Allocated by network administrator

SM45 Ethernet Setup

Before an SM45 supervisory module can communicate over an IP network with DCTools, the SM45 must be set up for Ethernet communications.

Use the front panel or DCTools for configuring the SM45 supervisory module for Ethernet communications.

Setup of Ethernet communications requires the following:

The network administrator assigning a unique IP address to each SM45 supervisory module to be connected to the IP network

Setting the assigned IP address for each SM45

Setting the net mask / subnet mask and gateway address for each SM45 as appropriate

To configure the SM45 for Ethernet communications using DCTools

1From the DCTools System Summary (Home) screen, click the Configuration hotlink and then Communications to display the Communications view.

2Under Ethernet, enter the assigned IP address, subnet mask and gateway address.

Copyright © 2005-2006 Eaton Corporation. All Rights Reserved.

6-3

IPN 997-00012-41D December 2006

 

Image 51
Contents Data Power Solutions Installation Guide Copyright 2005-2006 Eaton Corporation All Rights Reserved About This Guide About This Guide For Further Information and Technical AssistanceTable of Contents Chapter Operations Table of ContentsGeneral Description OverviewTopic General Description Data Power Solutions Product RangeAPS3-05X Rack-Mounted Versions Data Power Solutions Product RangeAPS3-06X Desktop Versions APS6-05X Rack-Mounted Versions Access Power Rectifiers SM45 Supervisory Module SM45 Supervisory ModuleLow Voltage Disconnect if applicable Pre-Installation AC Inputs Pre-InstallationBatteries if applicable DC Outputs Servicing Inspecting the Equipment and Reporting Damage Installation Location and Environment Mounting the Power SystemInstallation Rack Installation rack-mounted versions onlyDC Installation Practices Connecting the DC Load CablesDC Installation Practices APS3-05X and APS6-05X Rack-Mounted Versions Installation DC Load Cable SpecificationsFit load cable clamps Connecting the DC Load CablesFit cables and sleeves Battery Location Installing the External Batteries if applicableInstalling the External Batteries if applicable Battery SizingBefore You Start Connecting the Battery Cables if applicableBattery Fault Protection Battery Cable SpecificationsPrepare cable clamp Connecting the Battery Cables if applicableConnecting the Battery Temperature Sensor Cable Repeat for other battery cables if requiredMounting the Battery Temperature Sensor Connecting the Power System to the AC Supply AC InstallationAC Supply Requirements Commissioning Commissioning Inserting the Access Power RectifiersPre-Power-Up Check Pre-Power-Up CheckChecklist Configuring the Power System for Operation Applying AC PowerBefore you start, you need Configuring the Power System for OperationLVD Hotlink Click to …Page Applying DC Power to the Load SM45 Operations SM45 Operations About the SM45 Front PanelTo disable the audible indicator when an alarm is active About the SM45 Front PanelTo change the display contrast About Display Modes To enter a display modeTo exit a display mode To scroll within a display modeViewing System Values Main Display Mode Viewing System Values Main Display ModeTo view system values To view and clear alarms Viewing Alarms and System Status Messages Status View ModeRules for displaying alarms and system status Important note about Rect Comms Lost alarmViewing and Editing Configuration Parameters Viewing and Editing Configuration ParametersTo view and edit a configuration parameter SM45 Operations Communications Communications Options CommunicationsDirect Connection Ethernet Properties Direct Connection Ethernet DCTools SetupSM45 Ethernet Setup DCTools SetupParameter Configuration Guidelines Setting Up Snmp TrapsEntering the sysObjectID of a Power System Entering the sysObjectID of a Power SystemTo enter the sysObjectID of a power system using DCTools Synchronizing the SM45 Real-time Clock To synchronize the SM45 real-time clock using DCToolsMaintenance Troubleshooting MaintenanceProblem Possible Cause/s Required Action Troubleshooting LED Config Error Removing a Rectifier Replacing a RectifierReplacing a Rectifier Pull out the rectifierInserting a Rectifier Replacing AC Input Fuses Replacing AC Input FusesTo check and replace AC input fuses Replacing the SM45 Real-time Clock Battery Glossary of Alarms Rectifier Fail Sensor Fail System Overload Glossary of AlarmsMultiple Rectifier Fail Partial AC Fail Rectifier Comms LostControl Function Glossary Battery Current Limit BCLControl Function Glossary Low Volts DisconnectEnvironment SpecificationsSystem AC Input System DC OutputAPR48 Rectifiers SpecificationsDimensions H, W, D WeightEquipment Incident Report SG/03 ISS04 United States of America Worldwide SupportPage Page Page SM45 Front Panel Menu Structure Configuration Mode Edit Mode