Eaton Electrical SC200 manual Specifications, System AC Input, System DC Output, Environment

Page 69

Appendix C

Specifications

System AC Input

 

AC Input Voltage Range

APU48 rectifiers: 95 – 275 Vrms (L-N)

 

 

 

 

APR48 rectifiers: 185 – 275 Vrms (L-N)

 

 

 

 

 

 

Rated AC Input Current

 

 

 

@ 120 Vrms with APU48 rectifiers

APS3: 21 A (7 A per AC power cord)

 

 

 

 

APS6: 42 A (7 A per AC power cord)

 

 

 

 

 

 

 

@ 240 Vrms with APU48 rectifiers

APS3: 10.5 A (3.5 A per AC power cord)

 

 

 

 

APS6: 21 A (3.5 A per AC power cord)

 

 

 

 

 

 

 

@ 208-240 Vrms with APR48 rectifiers

APS3: 24 A (8 A per AC power cord)

 

 

 

 

APS6: 48 A (8 A per AC power cord)

 

 

 

 

 

Frequency Range

45-66 Hz

 

 

 

 

 

Maximum Earth Leakage Current

1.5 mA (per Access Power Rectifier)

System DC Output

 

 

 

 

 

 

DC Output Voltage (nominal)

48 V

 

 

 

 

 

DC Output Power (maximum)

 

 

 

 

APS3-058 & APS3-060

2.16 kW (with 3 APU48 rectifiers)

 

 

 

 

4.50 kW (with 3 APR48 rectifiers)

 

 

 

 

 

 

 

 

APS3-059 & APS3-061

1.70 kW (with 3 APU48 rectifiers)

 

 

 

 

3.00 kW (with 3 APR48 rectifiers)

 

 

 

 

 

 

 

 

APS6-058

4.32 kW (with 6 APU48 rectifiers)

 

 

 

 

9.00 kW (with 6 APR48 rectifiers)

 

 

 

 

 

 

 

 

APS6-059

3.40 kW (with 6 APU48 rectifiers)

 

 

 

 

7.10 kW (with 6 APR48 rectifiers)

 

 

 

 

DC Output Voltage Range

43 - 57.5 V

 

 

 

 

Over Voltage Shutdown Trip Point

58 V

Environment

 

 

 

 

 

Ambient Temperature Range (operating)

-10°C to +40°C [+14°F to +104°F]

 

 

 

 

Relative Humidity (operating and storage)

<95% (non condensing)

Copyright © 2005-2006 Eaton Corporation. All Rights Reserved.

C-1

IPN 997-00012-41D December 2006

 

Image 69
Contents Data Power Solutions Installation Guide Copyright 2005-2006 Eaton Corporation All Rights Reserved About This Guide About This Guide For Further Information and Technical AssistanceTable of Contents Chapter Operations Table of ContentsGeneral Description OverviewTopic General Description Data Power Solutions Product RangeAPS3-05X Rack-Mounted Versions Data Power Solutions Product RangeAPS3-06X Desktop Versions APS6-05X Rack-Mounted Versions Access Power Rectifiers SM45 Supervisory Module SM45 Supervisory ModuleLow Voltage Disconnect if applicable Pre-Installation AC Inputs Pre-InstallationBatteries if applicable DC Outputs Servicing Inspecting the Equipment and Reporting Damage Installation Installation Mounting the Power SystemRack Installation rack-mounted versions only Location and EnvironmentDC Installation Practices Connecting the DC Load CablesDC Installation Practices APS3-05X and APS6-05X Rack-Mounted Versions Installation DC Load Cable SpecificationsFit load cable clamps Connecting the DC Load CablesFit cables and sleeves Installing the External Batteries if applicable Installing the External Batteries if applicableBattery Sizing Battery LocationBattery Fault Protection Connecting the Battery Cables if applicableBattery Cable Specifications Before You StartPrepare cable clamp Connecting the Battery Cables if applicableConnecting the Battery Temperature Sensor Cable Repeat for other battery cables if requiredMounting the Battery Temperature Sensor Connecting the Power System to the AC Supply AC InstallationAC Supply Requirements Commissioning Commissioning Inserting the Access Power RectifiersPre-Power-Up Check Pre-Power-Up CheckChecklist Configuring the Power System for Operation Applying AC PowerBefore you start, you need Configuring the Power System for OperationLVD Hotlink Click to …Page Applying DC Power to the Load SM45 Operations SM45 Operations About the SM45 Front PanelTo disable the audible indicator when an alarm is active About the SM45 Front PanelTo change the display contrast To exit a display mode To enter a display modeTo scroll within a display mode About Display ModesViewing System Values Main Display Mode Viewing System Values Main Display ModeTo view system values Rules for displaying alarms and system status Viewing Alarms and System Status Messages Status View ModeImportant note about Rect Comms Lost alarm To view and clear alarmsViewing and Editing Configuration Parameters Viewing and Editing Configuration ParametersTo view and edit a configuration parameter SM45 Operations Communications Communications Options CommunicationsDirect Connection Ethernet SM45 Ethernet Setup DCTools SetupDCTools Setup Properties Direct Connection EthernetParameter Configuration Guidelines Setting Up Snmp TrapsEntering the sysObjectID of a Power System Entering the sysObjectID of a Power SystemTo enter the sysObjectID of a power system using DCTools Synchronizing the SM45 Real-time Clock To synchronize the SM45 real-time clock using DCToolsMaintenance Troubleshooting MaintenanceProblem Possible Cause/s Required Action Troubleshooting LED Config Error Removing a Rectifier Replacing a RectifierReplacing a Rectifier Pull out the rectifierInserting a Rectifier Replacing AC Input Fuses Replacing AC Input FusesTo check and replace AC input fuses Replacing the SM45 Real-time Clock Battery Glossary of Alarms Multiple Rectifier Fail Glossary of Alarms Partial AC Fail Rectifier Comms Lost Rectifier Fail Sensor Fail System OverloadControl Function Glossary Battery Current Limit BCLControl Function Glossary Low Volts DisconnectSystem AC Input SpecificationsSystem DC Output EnvironmentDimensions H, W, D SpecificationsWeight APR48 RectifiersEquipment Incident Report SG/03 ISS04 United States of America Worldwide SupportPage Page Page SM45 Front Panel Menu Structure Configuration Mode Edit Mode