Appendix C
Specifications
System AC Input
| AC Input Voltage Range | APU48 rectifiers: 95 – 275 Vrms | ||
|
|
|
| APR48 rectifiers: 185 – 275 Vrms |
|
|
|
|
|
| Rated AC Input Current |
| ||
|
| @ 120 Vrms with APU48 rectifiers | APS3: 21 A (7 A per AC power cord) | |
|
|
|
| APS6: 42 A (7 A per AC power cord) |
|
|
|
|
|
|
| @ 240 Vrms with APU48 rectifiers | APS3: 10.5 A (3.5 A per AC power cord) | |
|
|
|
| APS6: 21 A (3.5 A per AC power cord) |
|
|
|
|
|
|
| @ | APS3: 24 A (8 A per AC power cord) | |
|
|
|
| APS6: 48 A (8 A per AC power cord) |
|
|
|
| |
| Frequency Range | |||
|
|
|
| |
| Maximum Earth Leakage Current | 1.5 mA (per Access Power Rectifier) | ||
System DC Output |
| |||
|
|
|
| |
| DC Output Voltage (nominal) | 48 V | ||
|
|
|
| |
| DC Output Power (maximum) |
| ||
|
|
| 2.16 kW (with 3 APU48 rectifiers) | |
|
|
|
| 4.50 kW (with 3 APR48 rectifiers) |
|
|
|
|
|
|
|
| 1.70 kW (with 3 APU48 rectifiers) | |
|
|
|
| 3.00 kW (with 3 APR48 rectifiers) |
|
|
|
|
|
|
|
| 4.32 kW (with 6 APU48 rectifiers) | |
|
|
|
| 9.00 kW (with 6 APR48 rectifiers) |
|
|
|
|
|
|
|
| 3.40 kW (with 6 APU48 rectifiers) | |
|
|
|
| 7.10 kW (with 6 APR48 rectifiers) |
|
|
| ||
| DC Output Voltage Range | 43 - 57.5 V | ||
|
|
| ||
| Over Voltage Shutdown Trip Point | 58 V | ||
Environment |
| |||
|
|
| ||
| Ambient Temperature Range (operating) | |||
|
|
| ||
| Relative Humidity (operating and storage) | <95% (non condensing) |
Copyright © | ||
IPN | ||
|