Installation

DC Load Cable Specifications

No DC load cables are supplied.

DC load cables are sized differently, depending on whether you connect to 6A or 25A DC outlets. All DC load cables must meet the following specifications and no other cable sizes must be used.

6 A DC Outlets: UL 1015*, 18 AWG (1mm2), multi-strand cable

25 A DC Outlets: UL 1015*, 12 AWG (4mm2), multi-strand cable

Cable Length:

3m (10 feet) maximum

*Required to maintain approval compliance.

APS3-05X and APS6-05X (Rack-Mounted Versions)

3

2

1

4

"

#

Terminate the negative load cable(s) at the (-)terminal block(s) of the DC outlet(s).

Terminate the positive load cable(s) at the (+) terminal block(s) of the DC outlet(s).

Ensure that the polarity at the DC outlet(s) matches the power input polarity of your equipment. Connecting reverse polarity equipment power cables to the DC outlets of a power system might cause damage to your equipment. Such damage is not covered by our warranty.

Ensure that the correct cable sizes have bee used (18 AWG for 6 A outlets and 12 AWG for 25 A outlets).

$To ensure reliable connections at the terminal blocks of the DC outlets, torque the clamp-screws 0.4 – 0.6 Nm (3.5 – 5.3 lb-in).

%Use cable-ties (not supplied) and the provided cable-tie holes on the cable support bracket to tie down the load cables.

3-4

Copyright © 2005-2006 Eaton Corporation. All Rights Reserved.

IPN 997-00012-41D December 2006

 

Image 24
Contents Data Power Solutions Installation Guide Copyright 2005-2006 Eaton Corporation All Rights Reserved About This Guide For Further Information and Technical Assistance About This GuideTable of Contents Table of Contents Chapter OperationsGeneral Description OverviewTopic Data Power Solutions Product Range General DescriptionData Power Solutions Product Range APS3-05X Rack-Mounted VersionsAPS3-06X Desktop Versions APS6-05X Rack-Mounted Versions Access Power Rectifiers SM45 Supervisory Module SM45 Supervisory ModuleLow Voltage Disconnect if applicable Pre-Installation Pre-Installation AC InputsBatteries if applicable DC Outputs Servicing Inspecting the Equipment and Reporting Damage Installation Mounting the Power System InstallationRack Installation rack-mounted versions only Location and EnvironmentDC Installation Practices Connecting the DC Load CablesDC Installation Practices Installation DC Load Cable Specifications APS3-05X and APS6-05X Rack-Mounted VersionsConnecting the DC Load Cables Fit load cable clampsFit cables and sleeves Installing the External Batteries if applicable Installing the External Batteries if applicableBattery Sizing Battery LocationConnecting the Battery Cables if applicable Battery Fault ProtectionBattery Cable Specifications Before You StartConnecting the Battery Cables if applicable Prepare cable clampRepeat for other battery cables if required Connecting the Battery Temperature Sensor CableMounting the Battery Temperature Sensor Connecting the Power System to the AC Supply AC InstallationAC Supply Requirements Commissioning Inserting the Access Power Rectifiers CommissioningPre-Power-Up Check Pre-Power-Up CheckChecklist Applying AC Power Configuring the Power System for OperationConfiguring the Power System for Operation Before you start, you needHotlink Click to … LVDPage Applying DC Power to the Load SM45 Operations About the SM45 Front Panel SM45 OperationsTo disable the audible indicator when an alarm is active About the SM45 Front PanelTo change the display contrast To enter a display mode To exit a display modeTo scroll within a display mode About Display ModesViewing System Values Main Display Mode Viewing System Values Main Display ModeTo view system values Viewing Alarms and System Status Messages Status View Mode Rules for displaying alarms and system statusImportant note about Rect Comms Lost alarm To view and clear alarmsViewing and Editing Configuration Parameters Viewing and Editing Configuration ParametersTo view and edit a configuration parameter SM45 Operations Communications Communications Options CommunicationsDirect Connection Ethernet DCTools Setup SM45 Ethernet SetupDCTools Setup Properties Direct Connection EthernetSetting Up Snmp Traps Parameter Configuration GuidelinesEntering the sysObjectID of a Power System Entering the sysObjectID of a Power SystemTo enter the sysObjectID of a power system using DCTools To synchronize the SM45 real-time clock using DCTools Synchronizing the SM45 Real-time ClockMaintenance Troubleshooting MaintenanceProblem Possible Cause/s Required Action Troubleshooting LED Config Error Replacing a Rectifier Removing a RectifierPull out the rectifier Replacing a RectifierInserting a Rectifier Replacing AC Input Fuses Replacing AC Input FusesTo check and replace AC input fuses Replacing the SM45 Real-time Clock Battery Glossary of Alarms Glossary of Alarms Multiple Rectifier FailPartial AC Fail Rectifier Comms Lost Rectifier Fail Sensor Fail System OverloadBattery Current Limit BCL Control Function GlossaryLow Volts Disconnect Control Function GlossarySpecifications System AC InputSystem DC Output EnvironmentSpecifications Dimensions H, W, DWeight APR48 RectifiersEquipment Incident Report SG/03 ISS04 Worldwide Support United States of AmericaPage Page Page SM45 Front Panel Menu Structure Configuration Mode Edit Mode