Eaton Electrical SC200 Configuring the Power System for Operation, Before you start, you need

Page 37

Configuring the Power System for Operation

Using DCTools

Before you start, you need

A PC (preferably a laptop) with the latest version of DCTools installed.

A null modem cable

Step 1 – Connect a PC to the RS-232 port of the APS DC power system

1Connect the null modem cable between the RS-232 port of the power system and the serial port of your laptop or PC.

2Start DCTools by double clicking on the DCTools icon on the desktop.

Step 2 – Check that your PC port is specified correctly

1Double-click on the DCTools icon in the Windowstask bar to display the DCTools Connection List. The default connection is COM1.

2If the port properties are correct, enable the connection by selecting the

Active check box of that connection.

The correct port properties are, (Protocol: S3P and S3P Address: 0).

If the port properties are incorrect, select the relevant connection from the Connection List and click the toolbar button. In the Comms Properties dialog, edit the properties as necessary and click OK.

If the connection is successful, the DCTools System Summary (Home) screen is displayed as shown.

Copyright © 2005-2006 Eaton Corporation. All Rights Reserved.

4-5

IPN 997-00012-41D December 2006

 

Image 37
Contents Data Power Solutions Installation Guide Copyright 2005-2006 Eaton Corporation All Rights Reserved About This Guide About This Guide For Further Information and Technical AssistanceTable of Contents Chapter Operations Table of ContentsOverview General DescriptionTopic General Description Data Power Solutions Product RangeAPS3-05X Rack-Mounted Versions Data Power Solutions Product RangeAPS3-06X Desktop Versions APS6-05X Rack-Mounted Versions Access Power Rectifiers SM45 Supervisory Module SM45 Supervisory ModuleLow Voltage Disconnect if applicable Pre-Installation AC Inputs Pre-InstallationBatteries if applicable DC Outputs Servicing Inspecting the Equipment and Reporting Damage Installation Installation Mounting the Power SystemRack Installation rack-mounted versions only Location and EnvironmentConnecting the DC Load Cables DC Installation PracticesDC Installation Practices APS3-05X and APS6-05X Rack-Mounted Versions Installation DC Load Cable SpecificationsFit load cable clamps Connecting the DC Load CablesFit cables and sleeves Installing the External Batteries if applicable Installing the External Batteries if applicableBattery Sizing Battery LocationBattery Fault Protection Connecting the Battery Cables if applicableBattery Cable Specifications Before You StartPrepare cable clamp Connecting the Battery Cables if applicableConnecting the Battery Temperature Sensor Cable Repeat for other battery cables if requiredMounting the Battery Temperature Sensor AC Installation Connecting the Power System to the AC SupplyAC Supply Requirements Commissioning Commissioning Inserting the Access Power RectifiersPre-Power-Up Check Pre-Power-Up CheckChecklist Configuring the Power System for Operation Applying AC PowerBefore you start, you need Configuring the Power System for OperationLVD Hotlink Click to …Page Applying DC Power to the Load SM45 Operations SM45 Operations About the SM45 Front PanelAbout the SM45 Front Panel To disable the audible indicator when an alarm is activeTo change the display contrast To exit a display mode To enter a display modeTo scroll within a display mode About Display ModesViewing System Values Main Display Mode Viewing System Values Main Display ModeTo view system values Rules for displaying alarms and system status Viewing Alarms and System Status Messages Status View ModeImportant note about Rect Comms Lost alarm To view and clear alarmsViewing and Editing Configuration Parameters Viewing and Editing Configuration ParametersTo view and edit a configuration parameter SM45 Operations Communications Communications Communications OptionsDirect Connection Ethernet SM45 Ethernet Setup DCTools SetupDCTools Setup Properties Direct Connection EthernetParameter Configuration Guidelines Setting Up Snmp TrapsEntering the sysObjectID of a Power System Entering the sysObjectID of a Power SystemTo enter the sysObjectID of a power system using DCTools Synchronizing the SM45 Real-time Clock To synchronize the SM45 real-time clock using DCToolsMaintenance Maintenance TroubleshootingProblem Possible Cause/s Required Action Troubleshooting LED Config Error Removing a Rectifier Replacing a RectifierReplacing a Rectifier Pull out the rectifierInserting a Rectifier Replacing AC Input Fuses Replacing AC Input FusesTo check and replace AC input fuses Replacing the SM45 Real-time Clock Battery Glossary of Alarms Multiple Rectifier Fail Glossary of AlarmsPartial AC Fail Rectifier Comms Lost Rectifier Fail Sensor Fail System OverloadControl Function Glossary Battery Current Limit BCLControl Function Glossary Low Volts DisconnectSystem AC Input SpecificationsSystem DC Output EnvironmentDimensions H, W, D SpecificationsWeight APR48 RectifiersEquipment Incident Report SG/03 ISS04 United States of America Worldwide SupportPage Page Page SM45 Front Panel Menu Structure Configuration Mode Edit Mode