Installation
Avoid:
•Installing the batteries next to any heating source or under air ducts.
•Exposing part of a battery string to direct sunlight.
•Any other locations that would cause temperature variations within the batteries.
Battery Fault Protection
A fault protection device (such as a circuit breaker or fuse) must be fitted in series with one of the battery cables of each battery string.
The fault protection device must be:
•Located as close as practical to the corresponding battery string output terminal and
•Capable of disconnecting the potential fault current of the battery string.
The battery circuit breaker(s) of the power system can not be considered as the fault protection device for the battery string(s) and associated wiring.
The interrupt rating of the battery circuit breaker(s) fitted within the power systems is 10 kA. Therefore, the maximum potential
If a smaller rated external fault protection device is used, then batteries with appropriate internal impedance need to be selected.
Connecting the Battery Cables (if applicable)
This section applies to
Before You Start
Ensure that all the circuit breakers at the front of the power system and the external battery circuit breaker (close to the battery output terminals) are switched OFF.
Before proceeding check you have:
•Battery cable clamp(s) (one for APS3 models, three for
•2 x 25mm blunt ended screws per clamp
•1 x 16mm cable sleeve (50mm long) per clamp
•Battery cable (see specifications below).
Battery Cable Specifications
No battery cables are supplied with
Cable Style and Size: UL 1283*, 4 AWG (25mm2),
Cable Length: 3m (10 feet) maximum
*Required to maintain approval compliance.
Copyright © | ||
IPN | ||
|