Eaton Electrical SC200 manual Inserting the Access Power Rectifiers, Commissioning

Page 34

Commissioning

Inserting the Access Power Rectifiers

Do NOT switch on the AC supply at this stage.

Step 1 – Unpack the rectifiers

Unpack the rectifiers and inspect them carefully for possible damage that may have occurred in transit. Report any damage immediately, using a copy of the Equipment Incident Report (located at the back of this guide) to supply all relevant details. Fax the completed form to your local Powerware DC product representative.

Keep the original packaging. You will need this if any equipment needs to be returned to your nearest authorized service agent for replacement or repair.

Step 2 – Align the rectifier with the burst-out guides in the shelf

Step 3 – Push in the rectifier

To avoid injury to your hands, keep your fingers clear, as shown in the diagram below.

1Slowly push in the rectifier, sliding it along the burst-out guides, as shown below, until it plugs firmly into the backplane connector.

2Tighten the rectifier retaining screw with a Pozidriv® screwdriver.

4-2

Copyright © 2005-2006 Eaton Corporation. All Rights Reserved.

IPN 997-00012-41D December 2006

 

Image 34
Contents Data Power Solutions Installation Guide Copyright 2005-2006 Eaton Corporation All Rights Reserved About This Guide For Further Information and Technical Assistance About This GuideTable of Contents Table of Contents Chapter OperationsOverview General DescriptionTopic Data Power Solutions Product Range General DescriptionData Power Solutions Product Range APS3-05X Rack-Mounted VersionsAPS3-06X Desktop Versions APS6-05X Rack-Mounted Versions Access Power Rectifiers SM45 Supervisory Module SM45 Supervisory ModuleLow Voltage Disconnect if applicable Pre-Installation Pre-Installation AC InputsBatteries if applicable DC Outputs Servicing Inspecting the Equipment and Reporting Damage Installation Rack Installation rack-mounted versions only Mounting the Power SystemInstallation Location and EnvironmentConnecting the DC Load Cables DC Installation PracticesDC Installation Practices Installation DC Load Cable Specifications APS3-05X and APS6-05X Rack-Mounted VersionsConnecting the DC Load Cables Fit load cable clampsFit cables and sleeves Battery Sizing Installing the External Batteries if applicableInstalling the External Batteries if applicable Battery LocationBattery Cable Specifications Connecting the Battery Cables if applicableBattery Fault Protection Before You StartConnecting the Battery Cables if applicable Prepare cable clampRepeat for other battery cables if required Connecting the Battery Temperature Sensor CableMounting the Battery Temperature Sensor AC Installation Connecting the Power System to the AC SupplyAC Supply Requirements Commissioning Inserting the Access Power Rectifiers CommissioningPre-Power-Up Check Pre-Power-Up CheckChecklist Applying AC Power Configuring the Power System for OperationConfiguring the Power System for Operation Before you start, you needHotlink Click to … LVDPage Applying DC Power to the Load SM45 Operations About the SM45 Front Panel SM45 OperationsAbout the SM45 Front Panel To disable the audible indicator when an alarm is activeTo change the display contrast To scroll within a display mode To enter a display modeTo exit a display mode About Display ModesViewing System Values Main Display Mode Viewing System Values Main Display ModeTo view system values Important note about Rect Comms Lost alarm Viewing Alarms and System Status Messages Status View ModeRules for displaying alarms and system status To view and clear alarmsViewing and Editing Configuration Parameters Viewing and Editing Configuration ParametersTo view and edit a configuration parameter SM45 Operations Communications Communications Communications OptionsDirect Connection Ethernet DCTools Setup DCTools SetupSM45 Ethernet Setup Properties Direct Connection EthernetSetting Up Snmp Traps Parameter Configuration GuidelinesEntering the sysObjectID of a Power System Entering the sysObjectID of a Power SystemTo enter the sysObjectID of a power system using DCTools To synchronize the SM45 real-time clock using DCTools Synchronizing the SM45 Real-time ClockMaintenance Maintenance TroubleshootingProblem Possible Cause/s Required Action Troubleshooting LED Config Error Replacing a Rectifier Removing a RectifierPull out the rectifier Replacing a RectifierInserting a Rectifier Replacing AC Input Fuses Replacing AC Input FusesTo check and replace AC input fuses Replacing the SM45 Real-time Clock Battery Glossary of Alarms Partial AC Fail Rectifier Comms Lost Glossary of AlarmsMultiple Rectifier Fail Rectifier Fail Sensor Fail System OverloadBattery Current Limit BCL Control Function GlossaryLow Volts Disconnect Control Function GlossarySystem DC Output SpecificationsSystem AC Input EnvironmentWeight SpecificationsDimensions H, W, D APR48 RectifiersEquipment Incident Report SG/03 ISS04 Worldwide Support United States of AmericaPage Page Page SM45 Front Panel Menu Structure Configuration Mode Edit Mode