Specifications

 

 

Outdoor Unit

 

DMC24CA-1

DMC36CA-1

 

 

 

 

 

 

Rated Capacity

 

Cooling

kW

7.03

9.96

 

 

 

Btu/h

24,000

34,000

 

 

Heating

kW

-

-

 

 

 

Btu/h

-

-

Rated Input

 

Cooling

kW

2.5

3.6

 

 

Heating

kW

-

-

Energy Label

 

 

-

-

Testing combination

 

 

-

-

Running current

 

Cooling

A

11.5

17

 

 

Heating

A

-

-

Starting current

 

(Cooling/Heating)

A

24

38

Power supply

 

Phase / Volts / Hz

1 / 208-230 / 60

2 / 208-230 / 60

Power supply Cable(outdoor)

No. * mm2(No. AWG)

3 * 2.1(14)

3 * 3.3(12)

Power and transmission cable

No. * mm2(No. AWG)

4 * 2.1(14)

4 * 2.1(14)

Dimensions

 

W * H * D

mm(inch)

870 * 800 * 320(341/2 * 311/2 * 1219/32)

900 * 1160 * 370(357/16 * 4511/16 * 149/16)

Net weight

 

 

kg(lbs)

73(160)

86(190)

Gross weight

 

kg(lbs)

78(172)

93(205)

Maximum number of connectable unit

 

1

1

Compressor

 

Type

 

ROTARY

ROTARY

(constant)

 

Qty * model

 

2*GK120KAA

GJ151KAA + GJ208KAA

 

 

Motor Type

 

Induction

Induction

 

 

Oil charge volume

cc

700

1200

 

 

Oil type

 

PVE

PVE

Refrigerant

 

Charge(at 7.5m(25ft))

g(oz)

2100(74.1)

2500(88.2)

 

 

Type

 

R410A

R410A

 

 

Control

 

EEV

EEV

Heat Exchanger

 

Rows * Column * FPI

2R * 36C * 20

2R * 52C * 18

 

 

Defrosting method

 

-

-

Fan

 

Capacitor

mF/Vac

6 / 370

6 / 370

 

 

Drive

 

Direct Drive

Direct Drive

 

 

Discharge Direction

Side / Top

Side discharge

Side discharge

 

 

Air flow rate

cmm(cfm)

51(1801)

105(3708)

Noise level(H)

 

Sound press, 1m

db (A) + 3

55

58

Piping connections

 

Liquid

mm(inch)

6.35(1/4)

6.35(1/4)

 

 

Gas

mm(inch)

12.7(1/2)

15.88(5/8)

Max. piping length

 

Main piping

m(ft)

30(100)

35(115)

Max. elevation

 

Indoor unit - Outdoor unit

m(ft)

15(50)

20(66)

Note :

1. Capacities are based on the following conditions:

Cooling: - Indoor Temperature 26.7°C(80°F) DB /19.4°C(66.9°F) WB

-Outdoor Temperature 35°C(95°F) DB /23.9°C(75°F) WB Piping Length - Interconnecting Piping Length 7.5m(25ft)

-Level Difference of Zero.

Conversion Formula

kW = Btu/h 0.0002931

CFM = CMM 35.3

14Ceiling Cassette Air Conditioner

Image 14
Contents Ceiling Cassette Type Single-Zone Air Conditioning Table of Contents Safety Precautions InstallationOperational Be cautious when unpacking and installing the productBe sure the installation area does not deteriorate with age Do not let electric parts of the product get wetBe cautious that water could not enter the product Thinner Do not step on or put anyting on the product. outdoor unitsFeatures & Benefits Auto Restart Operation Swirl SwingSpace Control Two Thermistor ControlHigh Ceiling Operation Time Delay Safety FunctionZero Standby Power Water Drain PumpList of Functions Ceiling CassetteNd F Button Function of Remote ControlWireless LCD Remote Control Wired LCD Remote Control Specifications DMC36CA-1Outdoor Unit Dimensional Drawings Indoor UnitsModel No. DMC24CA-1 Model No. DMC36CA-1 DMC24CA-1 / DMC36CA-1 Wiring DiagramsIndoor Unit DMC36CA-1 Outdoor UnitDMC24CA-1 Refrigerant Cycle Diagrams Cooling Only ModelsIndoor Unit InstallationSelect the best location Outdoor UnitIndoor Unit Installation Settlement of outdoor unitWiring Connection Installation of Decoration Panel Air conditioner unit Piping sideHeat Insulation and pipings Heat InsulationDrain test Drain Pipe WorkDrain Piping of Ceiling Cassette Precautions in Test RUN Test runningConnection of power supply Evaluation of the performanceOptional Operation Two Thermistor SystemWiring design Adjusting air volume to the height of ceilingProcedure Remote ControllerTrouble analysis Troubleshooting GuideCycle Troubleshooting Guide Electronic Parts Troubleshooting Guide TroubleProduct doesnt operate with the remote controller When cooling does not operate When indoor Fan does not operate Trouble 5 When Vertical Louver does not operate Error Indicator Indoor ErrorOutdoor Error Self-diagnosis FunctionTroubleshooting CH01, CH02, CH06 Check PointTroubleshooting CH03 Troubleshooting CH04 Drain pump Float switch Open Drain pump power inputTroubleshooting CH05, CH53 Troubleshooting CH24, CH25 Constant Troubleshooting CH32, CH33Inverter Troubleshooting CH41, CH44, CH45, CH46, CH47, CH65 Troubleshooting Guide Troubleshooting CH61, CH62 Way Valve Way Valve Liguid Side Way Valve Gas SideAir purging of the charge hose ProcedurePumping down Set the liquid side valve to the closed positionAll amount of refrigerant leaked Mount the valve caps and the service port capsEvacuation After Evacuation Mount the valve stem nuts and the service port nutGas Charging Connect the gauge to the charging cylinderElectronic Control Device Main P.C.B ASM03/19/07