Heat Controller DMC36CA-1, DMC24CA-1 manual Product doesnt operate with the remote controller

Page 33

Troubleshooting Guide

Trouble 2

Product doesn't operate with the remote controller.

 

 

 

 

 

 

Turn on main power.

 

 

 

 

 

While the compressor has been stopped, the compressor does not operate

owing to the delaying function for 3 minutes after stopped.

When the compressor stopped Indoor Fan is driven by a low speed. At this point the wind speed is not controlled by the remote controller.

(When operated in the Sleeping Mode, the wind speed is set to the low speed as force.)

Caused by the remote controller.

When the mark ( ) is displayed in LCD

screen, replace battery.

When the detect switch (double key) inside the remote controller door is fault, it is impossible to operate temperature regulating(/ ) and wind speed selecting.

Caused by other parts except

the remote controller

Check the contact of CN-DISP 1 connector

Check DISP PWB Ass'y -Voltage between CN1 - : DC +5V

Check the Display PWB Ass'y

• Check receiver ass'y

Service Manual 33

Image 33
Contents Ceiling Cassette Type Single-Zone Air Conditioning Table of Contents Installation Safety PrecautionsBe sure the installation area does not deteriorate with age Be cautious when unpacking and installing the productOperational Do not let electric parts of the product get wetBe cautious that water could not enter the product Do not step on or put anyting on the product. outdoor units ThinnerFeatures & Benefits Space Control Swirl SwingAuto Restart Operation Two Thermistor ControlZero Standby Power Time Delay Safety FunctionHigh Ceiling Operation Water Drain PumpCeiling Cassette List of FunctionsFunction of Remote Control Wireless LCD Remote ControlNd F Button Wired LCD Remote Control DMC36CA-1 SpecificationsOutdoor Unit Indoor Units Dimensional DrawingsModel No. DMC24CA-1 Model No. DMC36CA-1 Wiring Diagrams Indoor UnitDMC24CA-1 / DMC36CA-1 Outdoor Unit DMC24CA-1DMC36CA-1 Cooling Only Models Refrigerant Cycle DiagramsSelect the best location InstallationIndoor Unit Outdoor UnitSettlement of outdoor unit Indoor Unit InstallationWiring Connection Air conditioner unit Piping side Installation of Decoration PanelHeat Insulation Heat Insulation and pipingsDrain Pipe Work Drain Piping of Ceiling CassetteDrain test Test running Precautions in Test RUNEvaluation of the performance Connection of power supplyTwo Thermistor System Optional OperationProcedure Adjusting air volume to the height of ceilingWiring design Remote ControllerTroubleshooting Guide Cycle Troubleshooting GuideTrouble analysis Trouble Electronic Parts Troubleshooting GuideProduct doesnt operate with the remote controller When cooling does not operate When indoor Fan does not operate Trouble 5 When Vertical Louver does not operate Outdoor Error Indoor ErrorError Indicator Self-diagnosis FunctionCheck Point Troubleshooting CH01, CH02, CH06Troubleshooting CH03 Drain pump Float switch Open Drain pump power input Troubleshooting CH04Troubleshooting CH05, CH53 Troubleshooting CH24, CH25 Troubleshooting CH32, CH33 InverterConstant Troubleshooting CH41, CH44, CH45, CH46, CH47, CH65 Troubleshooting Guide Troubleshooting CH61, CH62 Way Valve Liguid Side Way Valve Gas Side Way ValvePumping down ProcedureAir purging of the charge hose Set the liquid side valve to the closed positionMount the valve caps and the service port caps EvacuationAll amount of refrigerant leaked Gas Charging Mount the valve stem nuts and the service port nutAfter Evacuation Connect the gauge to the charging cylinderMain P.C.B ASM Electronic Control Device03/19/07