Heat Controller DMC24CA-1, DMC36CA-1 manual Troubleshooting CH61, CH62

Page 46

Troubleshooting Guide

TroubleshootingCH61,CH62

Display

Title

Cause of error

Check point & Normal condition

code

 

 

 

 

 

 

 

61

Condenser

• Condenser pipe sensor

• Check the load condition.

pipe sensor

detected high

• Check the sensor of Condenser pipe sensor.

 

temp. high

 

temp.(65°C)(149°F)

 

 

 

 

 

 

 

 

 

 

Heat sink sensor

• Heat sink sensor

• Check the fan is locked.

62

detected high

temp. high

• Check the sensor of heat sink.

 

temp.(85°C)(185°F)

 

 

 

 

 

 

 

 

 

Heat Sink temp.

 

 

Toff ° C

 

 

 

 

T2 ° C

 

 

 

 

T1 ° C

 

 

 

 

COMP Frequency

Normal

Normal

OFF

Normal

(Hz)

 

 

 

 

Check Point

• CH 61

1.Check the install condition for over load. (Refrigerant, Pipe length, Blocked, … )

• CH 62

1.Check the fan is locked.

2.Check the Outdoor temp. is very high.

46Ceiling Cassette Air Conditioner

Image 46
Contents Ceiling Cassette Type Single-Zone Air Conditioning Table of Contents Safety Precautions InstallationOperational Be cautious when unpacking and installing the productBe sure the installation area does not deteriorate with age Do not let electric parts of the product get wetBe cautious that water could not enter the product Thinner Do not step on or put anyting on the product. outdoor unitsFeatures & Benefits Auto Restart Operation Swirl SwingSpace Control Two Thermistor ControlHigh Ceiling Operation Time Delay Safety FunctionZero Standby Power Water Drain PumpList of Functions Ceiling CassetteWireless LCD Remote Control Function of Remote ControlNd F Button Wired LCD Remote Control Specifications DMC36CA-1Outdoor Unit Dimensional Drawings Indoor UnitsModel No. DMC24CA-1 Model No. DMC36CA-1 Indoor Unit Wiring DiagramsDMC24CA-1 / DMC36CA-1 DMC24CA-1 Outdoor UnitDMC36CA-1 Refrigerant Cycle Diagrams Cooling Only ModelsIndoor Unit InstallationSelect the best location Outdoor UnitIndoor Unit Installation Settlement of outdoor unitWiring Connection Installation of Decoration Panel Air conditioner unit Piping sideHeat Insulation and pipings Heat InsulationDrain Piping of Ceiling Cassette Drain Pipe WorkDrain test Precautions in Test RUN Test runningConnection of power supply Evaluation of the performanceOptional Operation Two Thermistor SystemWiring design Adjusting air volume to the height of ceilingProcedure Remote ControllerCycle Troubleshooting Guide Troubleshooting GuideTrouble analysis Electronic Parts Troubleshooting Guide TroubleProduct doesnt operate with the remote controller When cooling does not operate When indoor Fan does not operate Trouble 5 When Vertical Louver does not operate Error Indicator Indoor ErrorOutdoor Error Self-diagnosis FunctionTroubleshooting CH01, CH02, CH06 Check PointTroubleshooting CH03 Troubleshooting CH04 Drain pump Float switch Open Drain pump power inputTroubleshooting CH05, CH53 Troubleshooting CH24, CH25 Inverter Troubleshooting CH32, CH33Constant Troubleshooting CH41, CH44, CH45, CH46, CH47, CH65 Troubleshooting Guide Troubleshooting CH61, CH62 Way Valve Way Valve Liguid Side Way Valve Gas SideAir purging of the charge hose ProcedurePumping down Set the liquid side valve to the closed positionEvacuation Mount the valve caps and the service port capsAll amount of refrigerant leaked After Evacuation Mount the valve stem nuts and the service port nutGas Charging Connect the gauge to the charging cylinderElectronic Control Device Main P.C.B ASM03/19/07