Heat Controller DMC24CA-1, DMC36CA-1 manual Troubleshooting CH01, CH02, CH06, Check Point

Page 38

Troubleshooting Guide

TroubleshootingCH01,CH02,CH06

Display

Title

 

 

 

Cause of error

 

 

 

 

Check point & Normal condition

code

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor air sensor

 

• Open / Short

Normal resistor : 10K

/ at 25°C(77°F) (Unplugged)

01

 

• Soldered poorly

 

Normal voltage : 2.5Vdc / at 25°C(77°F) (plugged)

 

 

 

 

 

 

 

 

• Internal circuit error

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Open / Short

Normal resistor :

5K

/ at 25°C(77°F) (Unplugged)

02

Indoor inlet pipe sensor

 

• Soldered poorly

 

Normal voltage : 2.5Vdc / at 25°C(77°F) (plugged)

 

 

 

 

 

 

 

 

• Internal circuit error

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Open / Short

Normal resistor :

5K

/ at 25°C(77°F) (Unplugged)

06

Indoor outlet pipe sensor

 

• Soldered poorly

 

Normal voltage : 2.5Vdc / at 25°C(77°F) (plugged)

 

 

 

 

 

 

 

 

• Internal circuit error

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10k

Check the resistance

2.5Vdc

V

Check the voltage

Check Point

1.Unplug the sensor on Indoor unit PCB.

2.Estimate the resistance of each sensor.

3. If the resistance of the sensor is 10K/ 5Kat 25°C(77°F), then sensor is normal.

4.If the resistance of the sensor is 0 Kor , then sensor is abnormal. Change the sensor.

5.Plug the sensor on Indoor unit PCB and Power ON.

6.Estimate the voltage of each sensor.

7.If the voltage of the sensor is 2.5Vdc at 25°C(77°F), then sensor is normal.

8.If the resistance of the sensor is 0 or 5Vdc, then sensor is abnormal. Repair or Change the PCB.

38Ceiling Cassette Air Conditioner

Image 38
Contents Ceiling Cassette Type Single-Zone Air Conditioning Table of Contents Safety Precautions InstallationOperational Be cautious when unpacking and installing the productBe sure the installation area does not deteriorate with age Do not let electric parts of the product get wetBe cautious that water could not enter the product Thinner Do not step on or put anyting on the product. outdoor unitsFeatures & Benefits Auto Restart Operation Swirl SwingSpace Control Two Thermistor ControlHigh Ceiling Operation Time Delay Safety FunctionZero Standby Power Water Drain PumpList of Functions Ceiling CassetteNd F Button Function of Remote ControlWireless LCD Remote Control Wired LCD Remote Control Specifications DMC36CA-1Outdoor Unit Dimensional Drawings Indoor UnitsModel No. DMC24CA-1 Model No. DMC36CA-1 DMC24CA-1 / DMC36CA-1 Wiring DiagramsIndoor Unit DMC36CA-1 Outdoor UnitDMC24CA-1 Refrigerant Cycle Diagrams Cooling Only ModelsIndoor Unit InstallationSelect the best location Outdoor UnitIndoor Unit Installation Settlement of outdoor unitWiring Connection Installation of Decoration Panel Air conditioner unit Piping sideHeat Insulation and pipings Heat InsulationDrain test Drain Pipe WorkDrain Piping of Ceiling Cassette Precautions in Test RUN Test runningConnection of power supply Evaluation of the performanceOptional Operation Two Thermistor SystemWiring design Adjusting air volume to the height of ceilingProcedure Remote ControllerTrouble analysis Troubleshooting GuideCycle Troubleshooting Guide Electronic Parts Troubleshooting Guide TroubleProduct doesnt operate with the remote controller When cooling does not operate When indoor Fan does not operate Trouble 5 When Vertical Louver does not operate Error Indicator Indoor ErrorOutdoor Error Self-diagnosis FunctionTroubleshooting CH01, CH02, CH06 Check PointTroubleshooting CH03 Troubleshooting CH04 Drain pump Float switch Open Drain pump power inputTroubleshooting CH05, CH53 Troubleshooting CH24, CH25 Constant Troubleshooting CH32, CH33Inverter Troubleshooting CH41, CH44, CH45, CH46, CH47, CH65 Troubleshooting Guide Troubleshooting CH61, CH62 Way Valve Way Valve Liguid Side Way Valve Gas SideAir purging of the charge hose ProcedurePumping down Set the liquid side valve to the closed positionAll amount of refrigerant leaked Mount the valve caps and the service port capsEvacuation After Evacuation Mount the valve stem nuts and the service port nutGas Charging Connect the gauge to the charging cylinderElectronic Control Device Main P.C.B ASM03/19/07