Installation

In case of the Outdoor Unit being installed above position of the Indoor Unit.

2.Tape the Piping and Connecting cable from bot- tom to top.

3.Form the pipings gathered by taping along the exterior wall, and make the trap prevent water from entering into the room.

4.Attach the piping onto the wall by saddle or equiva- lent.

Seal a small opening around the pipings with gum type sealer.

Trap

7. Drain Pipe Work

Drain Piping of Ceiling Cassette

Drain piping must have down-slope (1/50 to 1/100): be sure not to provide up-and-down slope to prevent reversal flow.

During drain piping connection, be careful not to exert extra force on the drain port on the indoor unit.

The outside diameter of the drain connection on the indoor unit is 32mm(1.26inch).

Piping material: Polyvinyl chloride pipe VP-25 and pipe fittings

• Be sure to install heat insulation on the drain piping.

Heat insulation material: Polyethylene foam with thickness more than 8 mm(0.31inch).

Install the drain raising pipes at a right angle to the indoor unit and no more than 300mm(11.81inch) from the unit.

Pipe clamp

Upward

routing

 

 

not allowed

Indoor unit

 

Maintenance

 

drain port

 

300mm

 

1 -1.5m(3.32-4.92ft)

(11.81inch) or less

 

 

700mm

(27.6inch)or less

 

 

Drain raising pipe

 

Clamp metal(attached)

Drain hose(attached)

 

Drain test

The air conditioner uses a drain pump to drain water. Use the following procedure to test the drain pump operation:

Feed water

Flexible drain hose

 

(accessory)

 

Main

 

drain pipe

 

Drain

 

Drain Pump

port

Glue the joint

 

 

 

Drain hose connection

 

Use the clip (accessory)

Drain pan

CAUTION

The supplied flexible drain hose should not be curved, neither screwed. The curved or screwed hose may cause a leakage of water.

Connect the main drain pipe to the exterior and leave it provisionally until the test comes to an end.

Feed water to the flexible drain hose and check the piping for leakage.

Be sure to check the drain pump for normal operat- ing and noise when electrical wiring is complete.

When the test is complete, connect the flexible drain hose to the drain port on the indoor unit.

Flexible drain hose

1/50~1/100

MAX 700mm

(27.6inch)

26Ceiling Cassette Air Conditioner

Image 26
Contents Ceiling Cassette Type Single-Zone Air Conditioning Table of Contents Safety Precautions InstallationOperational Be cautious when unpacking and installing the productBe sure the installation area does not deteriorate with age Do not let electric parts of the product get wetBe cautious that water could not enter the product Thinner Do not step on or put anyting on the product. outdoor unitsFeatures & Benefits Auto Restart Operation Swirl SwingSpace Control Two Thermistor ControlHigh Ceiling Operation Time Delay Safety FunctionZero Standby Power Water Drain PumpList of Functions Ceiling CassetteNd F Button Function of Remote ControlWireless LCD Remote Control Wired LCD Remote Control Specifications DMC36CA-1Outdoor Unit Dimensional Drawings Indoor UnitsModel No. DMC24CA-1 Model No. DMC36CA-1 DMC24CA-1 / DMC36CA-1 Wiring DiagramsIndoor Unit DMC36CA-1 Outdoor UnitDMC24CA-1 Refrigerant Cycle Diagrams Cooling Only ModelsIndoor Unit InstallationSelect the best location Outdoor UnitIndoor Unit Installation Settlement of outdoor unitWiring Connection Installation of Decoration Panel Air conditioner unit Piping sideHeat Insulation and pipings Heat InsulationDrain test Drain Pipe WorkDrain Piping of Ceiling Cassette Precautions in Test RUN Test runningConnection of power supply Evaluation of the performanceOptional Operation Two Thermistor SystemWiring design Adjusting air volume to the height of ceilingProcedure Remote ControllerTrouble analysis Troubleshooting GuideCycle Troubleshooting Guide Electronic Parts Troubleshooting Guide TroubleProduct doesnt operate with the remote controller When cooling does not operate When indoor Fan does not operate Trouble 5 When Vertical Louver does not operate Error Indicator Indoor ErrorOutdoor Error Self-diagnosis FunctionTroubleshooting CH01, CH02, CH06 Check PointTroubleshooting CH03 Troubleshooting CH04 Drain pump Float switch Open Drain pump power inputTroubleshooting CH05, CH53 Troubleshooting CH24, CH25 Constant Troubleshooting CH32, CH33Inverter Troubleshooting CH41, CH44, CH45, CH46, CH47, CH65 Troubleshooting Guide Troubleshooting CH61, CH62 Way Valve Way Valve Liguid Side Way Valve Gas SideAir purging of the charge hose ProcedurePumping down Set the liquid side valve to the closed positionAll amount of refrigerant leaked Mount the valve caps and the service port capsEvacuation After Evacuation Mount the valve stem nuts and the service port nutGas Charging Connect the gauge to the charging cylinderElectronic Control Device Main P.C.B ASM03/19/07