Heat Controller DMC36CA-1, DMC24CA-1 manual Troubleshooting CH03

Page 39

Troubleshooting Guide

TroubleshootingCH03

Display

Title

 

Cause of error

 

Check point & Normal condition

code

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Communication

Open / Short

 

 

 

• Connection of wire

03

 

 

 

• Main PCB Volt. DC12V

Wired R/C

Wrong connection

 

 

 

• Noise interference

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Wired R/C

 

 

Indoor Unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12V

 

S GND

12V

S GND

12Vdc

V

Check the Volt.

12Vdc

V

Check the Volt.

Check Point

1.Check the wire connection. (Open / Short) Repair the connection

2.Check the soldering state of connector. (Soldered poorly) Repair or Change the PCB.

3.Check the volt. Of main PCB power source. (DC 12V, DC 5V) Repair or Change the main PCB.

4.Check the installation of wired remote controller. (Noise interference) Adjust the state of installation

Service Manual 39

Image 39
Contents Ceiling Cassette Type Single-Zone Air Conditioning Table of Contents Installation Safety PrecautionsDo not let electric parts of the product get wet Be cautious when unpacking and installing the productBe sure the installation area does not deteriorate with age OperationalBe cautious that water could not enter the product Do not step on or put anyting on the product. outdoor units ThinnerFeatures & Benefits Two Thermistor Control Swirl SwingSpace Control Auto Restart OperationWater Drain Pump Time Delay Safety FunctionZero Standby Power High Ceiling OperationCeiling Cassette List of FunctionsFunction of Remote Control Wireless LCD Remote ControlNd F Button Wired LCD Remote Control DMC36CA-1 SpecificationsOutdoor Unit Indoor Units Dimensional DrawingsModel No. DMC24CA-1 Model No. DMC36CA-1 Wiring Diagrams Indoor UnitDMC24CA-1 / DMC36CA-1 Outdoor Unit DMC24CA-1DMC36CA-1 Cooling Only Models Refrigerant Cycle DiagramsOutdoor Unit InstallationSelect the best location Indoor UnitSettlement of outdoor unit Indoor Unit InstallationWiring Connection Air conditioner unit Piping side Installation of Decoration PanelHeat Insulation Heat Insulation and pipingsDrain Pipe Work Drain Piping of Ceiling CassetteDrain test Test running Precautions in Test RUNEvaluation of the performance Connection of power supplyTwo Thermistor System Optional OperationRemote Controller Adjusting air volume to the height of ceilingProcedure Wiring designTroubleshooting Guide Cycle Troubleshooting GuideTrouble analysis Trouble Electronic Parts Troubleshooting GuideProduct doesnt operate with the remote controller When cooling does not operate When indoor Fan does not operate Trouble 5 When Vertical Louver does not operate Self-diagnosis Function Indoor ErrorOutdoor Error Error IndicatorCheck Point Troubleshooting CH01, CH02, CH06Troubleshooting CH03 Drain pump Float switch Open Drain pump power input Troubleshooting CH04Troubleshooting CH05, CH53 Troubleshooting CH24, CH25 Troubleshooting CH32, CH33 InverterConstant Troubleshooting CH41, CH44, CH45, CH46, CH47, CH65 Troubleshooting Guide Troubleshooting CH61, CH62 Way Valve Liguid Side Way Valve Gas Side Way ValveSet the liquid side valve to the closed position ProcedurePumping down Air purging of the charge hoseMount the valve caps and the service port caps EvacuationAll amount of refrigerant leaked Connect the gauge to the charging cylinder Mount the valve stem nuts and the service port nutGas Charging After EvacuationMain P.C.B ASM Electronic Control Device03/19/07
Related manuals
Manual 27 pages 9.94 Kb