Heat Controller DMC36CA-1, DMC24CA-1 manual Way Valve Liguid Side Way Valve Gas Side

Page 47

(3-way) Valve

(3-way) Valve

3-way Valve (Liguid Side)

3-way Valve (Gas Side)

Valve cap

 

Valve cap

 

 

 

 

 

 

Open position

 

Open position

 

 

Closed position

 

Closed position

 

 

 

 

 

 

 

Pin

 

 

Pin

 

 

 

 

 

To piping

 

 

To piping

Service

Service

Service

Service

connection

connection

 

port cap

port

 

port cap

port

To outdoor unit

 

To outdoor unit

 

 

 

 

 

 

 

Works

Shaft position

Service port

Shaft position

Service port

 

 

 

 

 

 

 

Shipping

Closed

Closed

Closed

Closed

 

 

(with valve cap)

(with cap)

(with valve cap)

(with cap)

 

 

 

 

 

 

 

Air purging

Open

Open

Closed

Open

1.

(Installation)

(counter-clockwise)

(push-pin or with

(clockwise)

(push-pin or with

 

 

 

vacuum pump)

 

vacuum pump)

 

 

 

 

 

 

 

Operation

Open

Closed

Open

Closed

 

 

(with valve cap)

(with cap)

(with valve cap)

(with cap)

 

 

 

 

 

 

2.

Pumping down

Closed

Closed

Open

Open

(Transfering)

(clockwise)

(with cap)

(counter-clockwise)

(connected

 

 

 

 

 

 

manifold gauge)

 

 

 

 

 

 

 

Evacuation

Open

Open

Open

Open

3.

(Servicing)

 

(connected

 

(connected

 

 

 

manifold gauge)

 

manifold gauge)

 

 

 

 

 

 

 

Gas charging

Open

Closed

Open

Open

4.

(Servicing)

 

(with cap)

 

(with charging

 

 

 

 

 

cylinder)

 

 

 

 

 

 

 

Pressure check

Open

Open

Open

Open

5.

(Servicing)

 

(connected

 

(connected

 

 

 

manifold gauge)

 

manifold gauge)

 

 

 

 

 

 

6.

Gas releasing

Open

Open

Open

Open

(Servicing)

 

(connected

 

(connected

 

 

 

manifold gauge)

 

manifold gauge)

 

 

 

 

 

 

Service Manual 47

Image 47
Contents Ceiling Cassette Type Single-Zone Air Conditioning Table of Contents Installation Safety PrecautionsDo not let electric parts of the product get wet Be cautious when unpacking and installing the productBe sure the installation area does not deteriorate with age OperationalBe cautious that water could not enter the product Do not step on or put anyting on the product. outdoor units ThinnerFeatures & Benefits Two Thermistor Control Swirl SwingSpace Control Auto Restart OperationWater Drain Pump Time Delay Safety FunctionZero Standby Power High Ceiling OperationCeiling Cassette List of FunctionsNd F Button Function of Remote ControlWireless LCD Remote Control Wired LCD Remote Control DMC36CA-1 SpecificationsOutdoor Unit Indoor Units Dimensional DrawingsModel No. DMC24CA-1 Model No. DMC36CA-1 DMC24CA-1 / DMC36CA-1 Wiring DiagramsIndoor Unit DMC36CA-1 Outdoor UnitDMC24CA-1 Cooling Only Models Refrigerant Cycle DiagramsOutdoor Unit InstallationSelect the best location Indoor UnitSettlement of outdoor unit Indoor Unit InstallationWiring Connection Air conditioner unit Piping side Installation of Decoration PanelHeat Insulation Heat Insulation and pipingsDrain test Drain Pipe WorkDrain Piping of Ceiling Cassette Test running Precautions in Test RUNEvaluation of the performance Connection of power supplyTwo Thermistor System Optional OperationRemote Controller Adjusting air volume to the height of ceilingProcedure Wiring designTrouble analysis Troubleshooting GuideCycle Troubleshooting Guide Trouble Electronic Parts Troubleshooting GuideProduct doesnt operate with the remote controller When cooling does not operate When indoor Fan does not operate Trouble 5 When Vertical Louver does not operate Self-diagnosis Function Indoor ErrorOutdoor Error Error IndicatorCheck Point Troubleshooting CH01, CH02, CH06Troubleshooting CH03 Drain pump Float switch Open Drain pump power input Troubleshooting CH04Troubleshooting CH05, CH53 Troubleshooting CH24, CH25 Constant Troubleshooting CH32, CH33Inverter Troubleshooting CH41, CH44, CH45, CH46, CH47, CH65 Troubleshooting Guide Troubleshooting CH61, CH62 Way Valve Liguid Side Way Valve Gas Side Way ValveSet the liquid side valve to the closed position ProcedurePumping down Air purging of the charge hoseAll amount of refrigerant leaked Mount the valve caps and the service port capsEvacuation Connect the gauge to the charging cylinder Mount the valve stem nuts and the service port nutGas Charging After EvacuationMain P.C.B ASM Electronic Control Device03/19/07