Heat Controller DMC36CA-1, DMC24CA-1 manual Troubleshooting CH32, CH33, Inverter, Constant

Page 43

Troubleshooting Guide

TroubleshootingCH32,CH33

Display

Title

 

Cause of error

Check point & Normal condition

code

 

 

 

 

 

 

 

 

 

 

 

D-pipe (Inverter)

 

• Check the discharge pipe sensor for INV.

 

• Discharge sensor

• Check the install condition for over load.

32

temp. high

 

 

(105°C(221°F)

)

(Inverter) temp. high

• Check the leakage of refrigerant.

 

 

• Check the SVC V/V open.

 

 

 

 

 

 

 

 

 

 

D-pipe (Constant)

 

• Check the discharge pipe sensor for Cons.

 

• Discharge sensor

• Check the install condition for over load.

33

temp. high

 

 

(Cons.) temp. high

• Check the leakage of refrigerant.

 

(105°C(221°F)

)

 

 

• Check the SVC V/V open.

 

 

 

 

 

 

 

 

 

 

105° C

COMP OFF

 

(221° F)

 

 

 

95° C

LEV OPEN/Hz down

 

(203° F)

LEV OPEN/Hz down

 

90° C

 

 

 

(194° F)

NORMAL

 

 

 

 

 

 

 

Inverter

Check Point

• CH 32

1.Check the install condition for over load.

2.Check the SVC V/V open.

3.Check the leakage of refrigerant.

105° C

COMP OFF

(221° F)

 

90° C

LEV OPEN

(194° F)

LEV OPEN

80° C

 

(176° F)

NORMAL

 

 

Constant

• CH 33

1.Check the install condition for over load.

2.Check the SVC V/V open.

3.Check the leakage of refrigerant.

4.Check the constant compressor. (same with CH21)

Service Manual 43

Image 43
Contents Ceiling Cassette Type Single-Zone Air Conditioning Table of Contents Installation Safety PrecautionsDo not let electric parts of the product get wet Be cautious when unpacking and installing the productBe sure the installation area does not deteriorate with age OperationalBe cautious that water could not enter the product Do not step on or put anyting on the product. outdoor units ThinnerFeatures & Benefits Two Thermistor Control Swirl SwingSpace Control Auto Restart OperationWater Drain Pump Time Delay Safety FunctionZero Standby Power High Ceiling OperationCeiling Cassette List of FunctionsWireless LCD Remote Control Function of Remote ControlNd F Button Wired LCD Remote Control DMC36CA-1 SpecificationsOutdoor Unit Indoor Units Dimensional DrawingsModel No. DMC24CA-1 Model No. DMC36CA-1 Indoor Unit Wiring DiagramsDMC24CA-1 / DMC36CA-1 DMC24CA-1 Outdoor UnitDMC36CA-1 Cooling Only Models Refrigerant Cycle DiagramsOutdoor Unit InstallationSelect the best location Indoor UnitSettlement of outdoor unit Indoor Unit InstallationWiring Connection Air conditioner unit Piping side Installation of Decoration PanelHeat Insulation Heat Insulation and pipingsDrain Piping of Ceiling Cassette Drain Pipe WorkDrain test Test running Precautions in Test RUNEvaluation of the performance Connection of power supplyTwo Thermistor System Optional OperationRemote Controller Adjusting air volume to the height of ceilingProcedure Wiring designCycle Troubleshooting Guide Troubleshooting GuideTrouble analysis Trouble Electronic Parts Troubleshooting GuideProduct doesnt operate with the remote controller When cooling does not operate When indoor Fan does not operate Trouble 5 When Vertical Louver does not operate Self-diagnosis Function Indoor ErrorOutdoor Error Error IndicatorCheck Point Troubleshooting CH01, CH02, CH06Troubleshooting CH03 Drain pump Float switch Open Drain pump power input Troubleshooting CH04Troubleshooting CH05, CH53 Troubleshooting CH24, CH25 Inverter Troubleshooting CH32, CH33Constant Troubleshooting CH41, CH44, CH45, CH46, CH47, CH65 Troubleshooting Guide Troubleshooting CH61, CH62 Way Valve Liguid Side Way Valve Gas Side Way ValveSet the liquid side valve to the closed position ProcedurePumping down Air purging of the charge hoseEvacuation Mount the valve caps and the service port capsAll amount of refrigerant leaked Connect the gauge to the charging cylinder Mount the valve stem nuts and the service port nutGas Charging After EvacuationMain P.C.B ASM Electronic Control Device03/19/07