Heat Controller DMC24CA-1, DMC36CA-1 Connection of power supply, Evaluation of the performance

Page 28

Installation

2)Connection of power supply

1.Connect the power supply cord to the independent power supply.

• Circuit breaker is required.

2.Operate the unit for fifteen minutes or more.

3)Evaluation of the performance

1.Measure the temperature of the intake and dis- charge air.

2.Ensure the difference between the intake tempera- ture and the discharge one is more than 8°C(14.4°F).

Thermometer

CAUTION

After the confirmation of the above conditions, prepare the wiring as follows:

1)Always use a dedicated circuit for the air conditioner. As for the method of wiring, see the circuit diagram pasted on the inside of control box cover.

2)Provide a circuit breaker switch between power source and the unit.

3)The screws which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations during transportation. Check them and make sure they are all tight.

(If they are loose, it could give rise to burn-out of the wires.)

4)Specification of power source

5)Confirm that electrical capacity is sufficient.

6)Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate.

7)Confirm that the cable size is selected using the minimum circuit ampacity on label. (Particularly note the relation between cable length and wire gauge.)

8)Use GFCI breaker where it is wet or moist and/or required by local and national codes.

9)The following troubles would be caused by excess voltage drop.

Vibration of a magnetic switch, damage on the contact point there of, fuse blowing, disturbance to the nor- mal function of a overload protection device.

Proper starting power is not given to the compressor.

HAND OVER

Teach the customer the operation and maintenance procedures, using the operation manual (air filter cleaning, temperature control, etc.).

28Ceiling Cassette Air Conditioner

Image 28
Contents Ceiling Cassette Type Single-Zone Air Conditioning Table of Contents Safety Precautions InstallationBe cautious when unpacking and installing the product Be sure the installation area does not deteriorate with ageOperational Do not let electric parts of the product get wetBe cautious that water could not enter the product Thinner Do not step on or put anyting on the product. outdoor unitsFeatures & Benefits Swirl Swing Space ControlAuto Restart Operation Two Thermistor ControlTime Delay Safety Function Zero Standby PowerHigh Ceiling Operation Water Drain PumpList of Functions Ceiling CassetteWireless LCD Remote Control Function of Remote ControlNd F Button Wired LCD Remote Control Specifications DMC36CA-1Outdoor Unit Dimensional Drawings Indoor UnitsModel No. DMC24CA-1 Model No. DMC36CA-1 Indoor Unit Wiring DiagramsDMC24CA-1 / DMC36CA-1 DMC24CA-1 Outdoor UnitDMC36CA-1 Refrigerant Cycle Diagrams Cooling Only ModelsInstallation Select the best locationIndoor Unit Outdoor UnitIndoor Unit Installation Settlement of outdoor unitWiring Connection Installation of Decoration Panel Air conditioner unit Piping sideHeat Insulation and pipings Heat InsulationDrain Piping of Ceiling Cassette Drain Pipe WorkDrain test Precautions in Test RUN Test runningConnection of power supply Evaluation of the performanceOptional Operation Two Thermistor SystemAdjusting air volume to the height of ceiling ProcedureWiring design Remote ControllerCycle Troubleshooting Guide Troubleshooting GuideTrouble analysis Electronic Parts Troubleshooting Guide TroubleProduct doesnt operate with the remote controller When cooling does not operate When indoor Fan does not operate Trouble 5 When Vertical Louver does not operate Indoor Error Outdoor ErrorError Indicator Self-diagnosis FunctionTroubleshooting CH01, CH02, CH06 Check PointTroubleshooting CH03 Troubleshooting CH04 Drain pump Float switch Open Drain pump power inputTroubleshooting CH05, CH53 Troubleshooting CH24, CH25 Inverter Troubleshooting CH32, CH33Constant Troubleshooting CH41, CH44, CH45, CH46, CH47, CH65 Troubleshooting Guide Troubleshooting CH61, CH62 Way Valve Way Valve Liguid Side Way Valve Gas SideProcedure Pumping downAir purging of the charge hose Set the liquid side valve to the closed positionEvacuation Mount the valve caps and the service port capsAll amount of refrigerant leaked Mount the valve stem nuts and the service port nut Gas ChargingAfter Evacuation Connect the gauge to the charging cylinderElectronic Control Device Main P.C.B ASM03/19/07