Troubleshooting Guide
Troubleshooting Guide
CycleTroubleshooting Guide
Trouble analysis
1. Check temperature difference between intake and discharge air, and operating current.
Temp. Difference
Operating Current
| Temp. difference | : approx. 0°C(0°F) | All amount of refrigerant leaked out. |
| Current | : less than 80% of | |
| Check refrigeration cycle. | ||
| |||
|
| rated current | |
|
|
| |
|
|
| Refrigerant leakage |
|
|
| |
| Temp. difference | : approx. 8°C(14.4°F) | |
| Current | : less than 80% of | Clog of refrigeration cycle |
|
| rated current | Defective compressor |
|
|
|
|
|
|
|
|
| Temp. difference | : less than 8°C(14.4°F) | Excessive amount of refrigerant |
| Current | : near the rated cur- | |
|
| ||
|
| rent |
|
|
|
|
|
Temp. difference : over 8°C(14.4°F)
Normal
Notice:
Temperature difference between intake and discharge air depends on room air humidity. When the room air humidity is relatively higher, temperature difference is smaller. When the room air humidity is relatively lower temperature difference is larger.
2. Check temperature and pressure of refrigeration cycle.
Suction pressure | Temperature |
|
| |
(Compared with | (Compared with | Cause of Trouble | Description | |
the normal value) | the normal value) |
|
| |
|
|
|
| |
| High | Defective compressor | Current is low. | |
Higher |
|
|
| |
Normal | Excessive amount of | High pressure does not quickly | ||
| ||||
|
| refrigerant | rise at the beginning of operation. | |
|
|
|
| |
|
| Insufficient amount of | Current is low. | |
Lower | Higher | refrigerant(Leakage) |
| |
|
| Clogging |
| |
|
|
|
|
Notice:
1.The suction pressure is usually 4.5~6.0 kg/cm2G
2.The temperature can be measured by attaching the thermometer to the low pressure tubing and wrap it with putty.
Service Manual 31