Heat Controller DMC24CA-1, DMC36CA-1 manual Troubleshooting CH04

Page 40

Troubleshooting Guide

TroubleshootingCH04

Display

Title

Cause of error

Check point & Normal condition

code

 

 

 

 

 

 

 

 

 

 

• The connection of wire(Drain pump/ Float switch)

04

Drain pump

• Float switch Open.

• Drain pump power input. (220V)

/ Float switch

(Normal : short)

• Drain tube installation.

 

 

 

 

• Indoor unit installation. (Inclination)

 

 

 

 

CN Float

0

Check the resistance

Check Point

1.Check the wire connection. (Open, Soldered poorly) Repair the connection or change the PCB.

2.Check the resistance of float switch (Abnormal : Open, Normal : short) Check the float switch.

3.Check the level of water

4.Check the volt. Of Drain pump power supply. (AC 230V) Repair or Change the main PCB.

40Ceiling Cassette Air Conditioner

Image 40
Contents Ceiling Cassette Type Single-Zone Air Conditioning Table of Contents Safety Precautions InstallationBe cautious when unpacking and installing the product Be sure the installation area does not deteriorate with ageOperational Do not let electric parts of the product get wetBe cautious that water could not enter the product Thinner Do not step on or put anyting on the product. outdoor unitsFeatures & Benefits Swirl Swing Space ControlAuto Restart Operation Two Thermistor ControlTime Delay Safety Function Zero Standby PowerHigh Ceiling Operation Water Drain PumpList of Functions Ceiling CassetteWireless LCD Remote Control Function of Remote ControlNd F Button Wired LCD Remote Control Specifications DMC36CA-1Outdoor Unit Dimensional Drawings Indoor UnitsModel No. DMC24CA-1 Model No. DMC36CA-1 Indoor Unit Wiring DiagramsDMC24CA-1 / DMC36CA-1 DMC24CA-1 Outdoor UnitDMC36CA-1 Refrigerant Cycle Diagrams Cooling Only ModelsInstallation Select the best locationIndoor Unit Outdoor UnitIndoor Unit Installation Settlement of outdoor unitWiring Connection Installation of Decoration Panel Air conditioner unit Piping sideHeat Insulation and pipings Heat InsulationDrain Piping of Ceiling Cassette Drain Pipe WorkDrain test Precautions in Test RUN Test runningConnection of power supply Evaluation of the performanceOptional Operation Two Thermistor SystemAdjusting air volume to the height of ceiling ProcedureWiring design Remote ControllerCycle Troubleshooting Guide Troubleshooting GuideTrouble analysis Electronic Parts Troubleshooting Guide TroubleProduct doesnt operate with the remote controller When cooling does not operate When indoor Fan does not operate Trouble 5 When Vertical Louver does not operate Indoor Error Outdoor ErrorError Indicator Self-diagnosis FunctionTroubleshooting CH01, CH02, CH06 Check PointTroubleshooting CH03 Troubleshooting CH04 Drain pump Float switch Open Drain pump power inputTroubleshooting CH05, CH53 Troubleshooting CH24, CH25 Inverter Troubleshooting CH32, CH33Constant Troubleshooting CH41, CH44, CH45, CH46, CH47, CH65 Troubleshooting Guide Troubleshooting CH61, CH62 Way Valve Way Valve Liguid Side Way Valve Gas SideProcedure Pumping downAir purging of the charge hose Set the liquid side valve to the closed positionEvacuation Mount the valve caps and the service port capsAll amount of refrigerant leaked Mount the valve stem nuts and the service port nut Gas ChargingAfter Evacuation Connect the gauge to the charging cylinderElectronic Control Device Main P.C.B ASM03/19/07
Related manuals
Manual 27 pages 9.94 Kb