Heat Controller DMC24CA-1, DMC36CA-1 manual Trouble 5 When Vertical Louver does not operate

Page 36

Troubleshooting Guide

Trouble 5 When Vertical Louver does not operate

Confirm that the Vertical Louver is normally geared with the shaft of Stepping Motor.

If the regular torque is detected when rotating the Vertical Louver with hands Normal

Check the connecting condition of CN-U/D Connector

Check the soldering condition(on PWB) of CN-U/D Connector

Check the operating circuit of the Vertical Louver

Confirm that there is DC +12V between pin (RED) of CN-U/D and GND.

If there are no problems after above checks

Confirm the assembly conditions that are catching and interfering parts in the rotation radial of the Vertical Louver

36Ceiling Cassette Air Conditioner

Image 36
Contents Ceiling Cassette Type Single-Zone Air Conditioning Table of Contents Safety Precautions InstallationBe cautious when unpacking and installing the product Be sure the installation area does not deteriorate with ageOperational Do not let electric parts of the product get wetBe cautious that water could not enter the product Thinner Do not step on or put anyting on the product. outdoor unitsFeatures & Benefits Swirl Swing Space ControlAuto Restart Operation Two Thermistor ControlTime Delay Safety Function Zero Standby PowerHigh Ceiling Operation Water Drain PumpList of Functions Ceiling CassetteFunction of Remote Control Wireless LCD Remote ControlNd F Button Wired LCD Remote Control Specifications DMC36CA-1Outdoor Unit Dimensional Drawings Indoor UnitsModel No. DMC24CA-1 Model No. DMC36CA-1 Wiring Diagrams Indoor UnitDMC24CA-1 / DMC36CA-1 Outdoor Unit DMC24CA-1DMC36CA-1 Refrigerant Cycle Diagrams Cooling Only ModelsInstallation Select the best locationIndoor Unit Outdoor UnitIndoor Unit Installation Settlement of outdoor unitWiring Connection Installation of Decoration Panel Air conditioner unit Piping sideHeat Insulation and pipings Heat InsulationDrain Pipe Work Drain Piping of Ceiling CassetteDrain test Precautions in Test RUN Test runningConnection of power supply Evaluation of the performanceOptional Operation Two Thermistor SystemAdjusting air volume to the height of ceiling ProcedureWiring design Remote ControllerTroubleshooting Guide Cycle Troubleshooting GuideTrouble analysis Electronic Parts Troubleshooting Guide TroubleProduct doesnt operate with the remote controller When cooling does not operate When indoor Fan does not operate Trouble 5 When Vertical Louver does not operate Indoor Error Outdoor ErrorError Indicator Self-diagnosis FunctionTroubleshooting CH01, CH02, CH06 Check PointTroubleshooting CH03 Troubleshooting CH04 Drain pump Float switch Open Drain pump power inputTroubleshooting CH05, CH53 Troubleshooting CH24, CH25 Troubleshooting CH32, CH33 InverterConstant Troubleshooting CH41, CH44, CH45, CH46, CH47, CH65 Troubleshooting Guide Troubleshooting CH61, CH62 Way Valve Way Valve Liguid Side Way Valve Gas SideProcedure Pumping downAir purging of the charge hose Set the liquid side valve to the closed positionMount the valve caps and the service port caps EvacuationAll amount of refrigerant leaked Mount the valve stem nuts and the service port nut Gas ChargingAfter Evacuation Connect the gauge to the charging cylinderElectronic Control Device Main P.C.B ASM03/19/07
Related manuals
Manual 27 pages 9.94 Kb