Heat Controller DMC36CA-1, DMC24CA-1 manual Evacuation, All amount of refrigerant leaked

Page 49

(3-way) Valve

(2) Evacuation

(All amount of refrigerant leaked)

Indoor unit

Liquid side

 

 

 

 

 

Outdoor unit

 

2-Way

 

 

valve

Open

 

Gas side

 

 

3-Way

 

 

valve

Open

Vacuum pump

 

 

 

Lo

 

OPEN

CLOSE

 

Procedure

1.Confirm that both the liguid side valve and gas side valve are set to the opened position.

2.Connect the vaccum pump to the center hose of the manifold gauge.

3.Connect the service port of the gas side valve to the low side of the gauge.

4.Evacuation for approximately one hour.

-Confirm that the gauge needle has moved toward-76 cmHg (vacuum of 4 mmHg or less).

5.Close the Low handle of the gauge turn off the vacuum pump, and confirm that the gauge nee- dle does not move(approximately 5 minutes after turning off the vacuum pump).

6.Disconnect the charge hose from the vacuum pump.

-Vacuum pump oil.

If the vacuum pump oil becomes dirty or deplet- ed,replenish as needed.

7.Mount the valve caps and the service port caps.

Service Manual 49

Image 49
Contents Ceiling Cassette Type Single-Zone Air Conditioning Table of Contents Installation Safety PrecautionsBe sure the installation area does not deteriorate with age Be cautious when unpacking and installing the productOperational Do not let electric parts of the product get wetBe cautious that water could not enter the product Do not step on or put anyting on the product. outdoor units ThinnerFeatures & Benefits Space Control Swirl SwingAuto Restart Operation Two Thermistor ControlZero Standby Power Time Delay Safety FunctionHigh Ceiling Operation Water Drain PumpCeiling Cassette List of FunctionsWireless LCD Remote Control Function of Remote ControlNd F Button Wired LCD Remote Control DMC36CA-1 SpecificationsOutdoor Unit Indoor Units Dimensional DrawingsModel No. DMC24CA-1 Model No. DMC36CA-1 Indoor Unit Wiring DiagramsDMC24CA-1 / DMC36CA-1 DMC24CA-1 Outdoor UnitDMC36CA-1 Cooling Only Models Refrigerant Cycle DiagramsSelect the best location InstallationIndoor Unit Outdoor UnitSettlement of outdoor unit Indoor Unit InstallationWiring Connection Air conditioner unit Piping side Installation of Decoration PanelHeat Insulation Heat Insulation and pipingsDrain Piping of Ceiling Cassette Drain Pipe WorkDrain test Test running Precautions in Test RUNEvaluation of the performance Connection of power supplyTwo Thermistor System Optional OperationProcedure Adjusting air volume to the height of ceilingWiring design Remote ControllerCycle Troubleshooting Guide Troubleshooting GuideTrouble analysis Trouble Electronic Parts Troubleshooting GuideProduct doesnt operate with the remote controller When cooling does not operate When indoor Fan does not operate Trouble 5 When Vertical Louver does not operate Outdoor Error Indoor ErrorError Indicator Self-diagnosis FunctionCheck Point Troubleshooting CH01, CH02, CH06Troubleshooting CH03 Drain pump Float switch Open Drain pump power input Troubleshooting CH04Troubleshooting CH05, CH53 Troubleshooting CH24, CH25 Inverter Troubleshooting CH32, CH33Constant Troubleshooting CH41, CH44, CH45, CH46, CH47, CH65 Troubleshooting Guide Troubleshooting CH61, CH62 Way Valve Liguid Side Way Valve Gas Side Way ValvePumping down ProcedureAir purging of the charge hose Set the liquid side valve to the closed positionEvacuation Mount the valve caps and the service port capsAll amount of refrigerant leaked Gas Charging Mount the valve stem nuts and the service port nutAfter Evacuation Connect the gauge to the charging cylinderMain P.C.B ASM Electronic Control Device03/19/07