Troubleshooting Guide

TroubleshootingCH05,CH53

Display

Title

Cause of error

Check point & Normal condition

code

 

 

 

 

 

 

 

 

 

 

• Power input AC 220V. (Outdoor, Indoor)

05

 

 

• The connector for transmission is disconnected.

Communication

 

• The connecting wires are misconnected.

/

• Communication poorly

• The GND1,2 is not connected at main GND.

53

(Indoor Outdoor)

 

• The communication line is shorted at GND.

 

 

 

 

 

• Transmission circuit of outdoor PCB is abnormal.

 

 

 

• Transmission circuit of indoor PCB is abnormal.

 

 

 

 

Check Point

1.Check the input power AC230V. (Outdoor, Indoor unit)

2.Check the communication wires are correctly connected.

Adjust the connection of wire

Confirm the wire of “Live”, “Neutral”

3.Check the resistance between communication line and GND. (Normal : Over 2M)

4.Check the connector for communication is correctly connected.

5.Check the connection of GND1, GND2, and main GND.

6.If one indoor unit is operated normally, outdoor PCB is no problem.

Check the another indoor unit.

* CH05 is displayed at indoor unit, CH53 is displayed at outdoor unit.

Service Manual 41

Image 41
Contents Ceiling Cassette Type Single-Zone Air Conditioning Table of Contents Installation Safety PrecautionsBe sure the installation area does not deteriorate with age Be cautious when unpacking and installing the productOperational Do not let electric parts of the product get wetBe cautious that water could not enter the product Do not step on or put anyting on the product. outdoor units ThinnerFeatures & Benefits Space Control Swirl SwingAuto Restart Operation Two Thermistor ControlZero Standby Power Time Delay Safety FunctionHigh Ceiling Operation Water Drain PumpCeiling Cassette List of FunctionsNd F Button Function of Remote ControlWireless LCD Remote Control Wired LCD Remote Control DMC36CA-1 SpecificationsOutdoor Unit Indoor Units Dimensional DrawingsModel No. DMC24CA-1 Model No. DMC36CA-1 DMC24CA-1 / DMC36CA-1 Wiring DiagramsIndoor Unit DMC36CA-1 Outdoor UnitDMC24CA-1 Cooling Only Models Refrigerant Cycle DiagramsSelect the best location InstallationIndoor Unit Outdoor UnitSettlement of outdoor unit Indoor Unit InstallationWiring Connection Air conditioner unit Piping side Installation of Decoration PanelHeat Insulation Heat Insulation and pipingsDrain test Drain Pipe WorkDrain Piping of Ceiling Cassette Test running Precautions in Test RUNEvaluation of the performance Connection of power supplyTwo Thermistor System Optional OperationProcedure Adjusting air volume to the height of ceilingWiring design Remote ControllerTrouble analysis Troubleshooting GuideCycle Troubleshooting Guide Trouble Electronic Parts Troubleshooting GuideProduct doesnt operate with the remote controller When cooling does not operate When indoor Fan does not operate Trouble 5 When Vertical Louver does not operate Outdoor Error Indoor ErrorError Indicator Self-diagnosis FunctionCheck Point Troubleshooting CH01, CH02, CH06Troubleshooting CH03 Drain pump Float switch Open Drain pump power input Troubleshooting CH04Troubleshooting CH05, CH53 Troubleshooting CH24, CH25 Constant Troubleshooting CH32, CH33Inverter Troubleshooting CH41, CH44, CH45, CH46, CH47, CH65 Troubleshooting Guide Troubleshooting CH61, CH62 Way Valve Liguid Side Way Valve Gas Side Way ValvePumping down ProcedureAir purging of the charge hose Set the liquid side valve to the closed positionAll amount of refrigerant leaked Mount the valve caps and the service port capsEvacuation Gas Charging Mount the valve stem nuts and the service port nutAfter Evacuation Connect the gauge to the charging cylinderMain P.C.B ASM Electronic Control Device03/19/07