INSTALLATION |
Return to Section TOC
Return to Section TOC
Return to Section TOC
Return to Section TOC
Return to Master TOC
Return to Master TOC
Return to Master TOC
Return to Master TOC
PREMISES WIRING
The POWERARC® 5500
WARNING
Only a licensed, certified, trained electrician should install the machine to a premises or resi- dential electrical system. Be certain that:
•The premises is isolated and no feed backing into the utility system can occur. Certain state and local laws require the premises to be isolat- ed before the generator is linked to the premis- es. Check your state and local requirements.
•A double pole, double throw transfer switch in conjunction with the properly rated double throw circuit breaker is connected between the generator power and the utility meter.
The POWERARC® 5500 does not have a combined 120/240 volt
Remember that the POWERARC® 5500 is intended only for backup, intermittent use power. Oil level must be checked after every 5 hours of use. It cannot with- stand
Certain electrical devices cannot be powered by the
POWERARC® 5500. Refer to Table A.2 for these devices.
CIRCUIT BREAKERS
Auxiliary power is protected by circuit breaker. When the machine is operated in high temperature environ- ments, the breakers may tend to trip at lower loads than normally.
CAUTION
Never bypass the circuit breakers. Without over- load protection, the POWERARC® 5500 could overheat and/or cause damage to the equipment being used.
POWERARC® 5500