OPERATION |
Return to Master TOC
Return to Master TOC
STOPPING THE ENGINE
1.Remove all welding and generator power loads and let the engine cool by running it for several minutes.
2.Stop the engine by placing the “ON/OFF” switch in the “OFF”(O) position.
3.Close the fuel shutoff valve.
WARNING
Close the fuel valve when the machine is trans- ported to prevent fuel leakage from the carburetor. Drain the tank before transporting the machine in a vehicle.
For long periods of storage, turn off the fuel shut- off valve and let the engine run until there is no more fuel in the line. Use a fuel additive such as
GENERATOR OPERATION
CAUTION
Be sure that any electrical equipment plugged into the generator’s AC power receptacles can withstand a ±10% voltage and a ±4% frequency variation. Some electronic devices cannot be powered by the POWERARC® 5500. Refer to Table A.2, ELECTRICAL DEVICE USE WITH THE POWERARC® 5500, in the INSTALLATION section of this manual.
GENERAL INFORMATION
The POWERARC® 5500 generator is rated at 4000 continuous watts (5500 surge watts). It provides both 120 volt and 240 volt power. You can draw up to 20 amps from either side of the 120 volt duplex recepta- cle, but no more than 33.3 amps from both sides at once. Up to 16.7 amps can be drawn from the single 240 volt receptacle.
Return to Section TOC
Return to Section TOC
Return to Section TOC
Return to Section TOC
Return to Master TOC
Return to Master TOC
RUNNING THE ENGINE
The engine is set at the factory to run at high idle speed when not under load. You should not adjust this setting yourself.
BREAK-IN PERIOD
The engine will use a greater amount of oil during its
CAUTION
During
Electrical loads in watts are calculated by multiplying the voltage rating of the load by the number of amps it draws. (This information is given on the load device nameplate.) For example, a device rated 120 volts, 2 amps will need 240 watts of power (120 x 2 = 240).
You can use Table B.3, GENERATOR POWER APPLI- CATIONS, to determine the wattage requirements of the most common types of loads you can power with the POWERARC® 5500. Be sure to read the notes at the bottom of the table.
TO USE THE POWERARC® 5500 AS AN AUXIL-
IARY POWER SUPPLY:
1.Start the gasoline engine. See ENGINE OPERA - TION in this section of the manual and the engine owner’s manual.
2.Set the current control dial on the output control panel to “GENERATOR.” See Figure B.1.
3.Plug the load(s) into the appropriate 120 volt or 240 volt power receptacle.
NOTE: During welding, the maximum generator out- put for auxiliary loads is 100 watts.
NOTE: You can supply multiple loads as long as the total load does not exceed 5,500 surge watts or 4,000 Continuous watts. Be sure to start the largest loads first.