INPUT CONTACTOR (1CR) CLEANING AND/OR REPLACEMENT
Return to Section
Return to Section TOC
Return to Section TOC
Return to Section TOC
Return to Master
Return to Master TOC
Return to Master TOC
Return to Master TOC
INSTALLATION
1.Install input contactor using a 7/16” socket wrench. Attach the four mounting bolts, nuts, and associat- ed washers (or tighten the two bot- tom bolts and nuts, and attach the top two).
2.Attach leads to contactor interlock. Connect quick connects on leads #211 and #212. See Figure F.21.
3.Attach leads from contactor coil. Attach any cable ties and/or har- ness looms cut at removal. Attach lead #257 at secondary thermostat. See Figure F.20.
4.Using a 11/16” wrench, attach leads L1, L2, L3 and output power leads to 1CR contactor. See Figure F.19.
NOTE: Ensure all leads are connected correctly. See Wiring Diagram.