Schneider Electric Altivar 212 Configuration of the control source, Control by the Modbus network

Page 21

Configuration

Configuration of the control source

The Altivar 212 can receive commands and setpoint from the Modbus network or from the terminals (F, R, RES, VIA, VIB). In the default configuration, both commands and setpoint come from the terminals.

The LOC/REM key of the operation panel is available to switch the control to the operation panel. The inputs F, R or RES can be configured to switch the control from the Modbus network to the terminals.

Different usual possibilities are described in the chapters below:

Control from the Modbus network,

Control from the terminals, monitoring from the Modbus network,

Control from the Modbus network or the terminals, switched via Modbus,

Command from the Modbus network, setpoint from the Modbus network or the terminals switched to by a

logic input.

Refer to these examples.

Control by the Modbus network

The commands and the setpoint come from the Modbus network. The signals wired on the terminals are ignored. The LOC/REM key is valid.

Below is the list of parameters that must be configured.

Access to the parameters

Parameters

Location

 

 

[Command mode sel] (CMOd)

[PROGRAMMING MENU] Programming mode

[Frequency mode sel] (FMOd)

 

 

 

Other parameters

[COMMUNICATION MENU] COM submenu of

 

[PROGRAMMING MENU] Programming mode.

 

 

Description

 

Parameters

 

 

 

 

 

 

 

Modbus

 

Setting

Default

 

Valid

 

 

 

 

 

 

 

 

 

address

 

 

 

 

setting

 

after

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[Command mode sel] (CMOd)

 

3

 

2

[Communication]

0

 

 

Setting

 

Remote mode start/stop control

 

16#3

 

Serial communication

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[Frequency mode sel] (FMOd)

 

4

 

4

[Serial com ref.]

1

 

 

Setting

 

Remote mode primary speed reference source

16#4

 

Serial communication

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[Com channel choice] (F807)

 

2055

 

0

[RJ45] or

1

 

 

Setting

 

Communication channel selection

 

16#807

 

1

[Open style]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[Network protocol] (F829)

 

2089

 

1

[Modbus-RTU protocol]

1

 

 

Power

 

Communication Network protocol selection

 

16#829

 

 

 

 

 

 

 

cycle

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bit 15 of

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

command word FA00

 

 

LOC

 

Commands CMOd

 

Serial com. command priority bit

 

 

 

Modbus commands

ON

 

REM

 

Terminals

 

 

0

 

 

 

REM

 

Commands

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operation panel

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Modbus

2

OFF

Operation

LOC

 

panel

commands

 

 

 

 

Setpoint FMOd

 

 

 

VIA

 

1

 

Modbus setpoint

ON

 

 

 

 

 

 

VIB

 

2

 

 

 

 

 

 

 

 

 

Operation panel

3

 

 

Operation

Modbus

4

 

OFF

setpoint

 

Bit 14 of

panel

UP/DOWN

5

Communication

 

command word FA00

 

 

F807

Serial com. setpoint priority bit

 

 

 

RJ45 channel: Modbus

 

0

 

Network channel:

 

1

Paremeter F829

 

REM

LOC

Setpoint

S1A53844 01/2011

21

Image 21
Contents Altivar S1A53844 01/2011 Table of Contents Table of Contents Important Information Safety InformationAt a Glance About the BookHazard of Electric SHOCK, Explosion or ARC Flash S1A53844 01/2011 Introduction Introduction Hardware setup Whats in this Chapter?Topic RJ45 Pin out of the Open Style Modbus connectorCross section Tightening torquePin out of the RJ45 Modbus connector Connection via Open Style wiring systemPin Signal Open Style ReferenceConnection accessories Connection via RJ45 wiring systemConnecting cables RJ45 ReferenceProtection Against Interference PTC resistor value F646 Description of terminalsGND Hardware setup Configuration Access to the parameters Configuration of the communication parametersParameters Modbus Adjustment range Default Valid Address AfterParameters Modbus Setting Configuration of the control sourceControl by the Modbus network CommunicationSetting Default Valid Control by the terminals, monitoring by the Modbus networkParameters Parameters Modbus Setting Default Valid Com channel choice F807 Communication Menu COM submenu Parameters Modbus Setting Default Valid AddressLI R selection F112 LI R selectionRemote spd ref 2 F207 Parameters LocationFrequency source VIA VIACommands CMOd Complete control diagramConfiguration Configuration of the indirect blocksConfiguration of the communication interruption Parameter Modbus Setting Default Valid Address Configure the drive behaviourCommunication detected fault 16#851 2129Configuration Modbus services Principle of the Modbus protocol RTU modeSlave Slave j Slave k Slave address Function code DataModbus functions available Read one wordFunction 3, quantity = Read indirect block Function 3, quantity = 1Status info Read indirect block of 2 parameters Write Single Register Function 16 = 16#10, quantity =1 Write multiple registersCommand word Frequency Setpoint Write indirect blockSpeed Setpoint Request 6C 7E Response Read Device Identification 43/14 Exception code Error responseModbus services Parameter list Setting of Max frequency FH Auto ramp AUI Disabled ManualReferring to the Altivar 212 programming manual GeneralList of control parameters Commands from serial communicationSetpoints from serial communication Outputs control from serial communicationStatus List of monitoring parametersFrequency and speed Current and torqueMaintenance Power and energyTrip and alarm codes ValuesCommands Command word FA00Bit Specifications Remarks Energy reset bit Command word 2 FA20Examples Over-current stall level change bitSetpoints Frequency setpoint FA01Speed setpoint FA13 Status word FE0I Fd01 StatusSetpoint mode status FE46 Command mode status FE45Status word 2 FE42 Fd42 Status word 3 FE49 Fd49Trip and alarm codes Alarm code FC91Alarm of run time FE79 Code Value Description Hexadecimal number Decimal number Digital inputs status Fd06, FE06 Monitoring and control of I/O from communicationDigital outputs status Fd07, FE07 Bit Terminal name Function parameter titleAnalog outputs command FA51 Digital outputs command FA50Damper opening command Analog inputs values FE35, FE36F580 = 3 Model Voltage Power Rating Code FB05 Class FB72bit8 IdentificationDrive model code F805 ATV212WU15N4C S1A53844 01/2011 Appendix Modbus 2-wire standard schematic Schematic diagramRS485 standard Migration Migration ATV21 ATV212 For exampleCommissioning ATV212Modbus manualENS1A5384401 S1A53844 01/2011