Modbus services

Read Device Identification (43/14)

Function 43/14 = 16#2B/0E

Request:

 

Function code

MEI type

Read Device Id

Object Id

 

CRC16

Slave no.

 

code

 

 

 

 

 

 

 

 

 

 

 

2B

0E

01 ... 03

00

Lo

 

Hi

 

 

 

 

 

 

 

 

1 byte

1 byte

1 byte

1 byte

1 byte

 

2 bytes

Response:

Slave no.

Function code

MEI type

Read Device Id code

Conformity level

2B

0E

01 ... 03

01

 

 

 

 

 

 

1 byte

1 byte

1 byte

1 byte

1 byte

-------

-------

More follows

Next object Id

Number of objects

00

00

03

 

 

 

1 byte

1 byte

1 byte

-------

-------

Id of object no. 1

Length of object no. 1

Value of object no. 1

-------

 

00

0D

“Télémécanique”

 

 

1 byte

1 byte

13 bytes

-------

Id of object no. 2

 

Length of object no. 2

Value of object no. 2

 

01

 

 

 

0D

“ATV212H075M3X”

 

1 byte

 

 

1 byte

13 bytes

-------

 

 

 

 

Id of object no. 3

 

Length of object no. 3

Value of object no. 3

 

02

 

 

 

04

“0182”

 

1 byte

 

 

1 byte

4 bytes

-------

 

 

 

 

 

 

CRC16

 

 

 

 

 

Lo

 

Hi

 

 

 

1 byte

1 byte

 

 

-------

-------

The total response size given in this example equals 46 bytes.

The response contains the following four objects:

Object no. 1: Manufacturer name (always "Télémécanique", i.e., 13 bytes).

Object no. 2: Device catalog number (ASCII string; for example: “ATV212H075M3X”, i.e., 13 bytes).

The length of this object varies according to drive type. Use the “Length of object no. 2” field to determine the length.

Object no. 3: Control version, in "MMmm" format where "MM" represents the major revision and "mm" the minor revision (4-byte ASCII string; for example: "0182" for version 1.82).

Error response:

Slave no.

Function code

Exception code

 

CRC16

Lo

 

Hi

 

AB

 

 

 

 

 

 

 

 

 

 

1 byte

1 byte

1 byte

1 byte

 

1 byte

Refer to "Error response", page 41.

40

S1A53844 01/2011

Image 40
Contents Altivar S1A53844 01/2011 Table of Contents Table of Contents Safety Information Important InformationAbout the Book At a GlanceHazard of Electric SHOCK, Explosion or ARC Flash S1A53844 01/2011 Introduction Introduction Whats in this Chapter? Hardware setupTopic Pin out of the Open Style Modbus connector RJ45Cross section Tightening torqueConnection via Open Style wiring system Pin out of the RJ45 Modbus connectorPin Signal Open Style ReferenceConnection via RJ45 wiring system Connection accessoriesConnecting cables RJ45 ReferenceProtection Against Interference Description of terminals PTC resistor value F646GND Hardware setup Configuration Configuration of the communication parameters Access to the parametersParameters Modbus Adjustment range Default Valid Address AfterConfiguration of the control source Parameters Modbus SettingControl by the Modbus network CommunicationControl by the terminals, monitoring by the Modbus network Setting Default ValidParameters Parameters Modbus Setting Default Valid Parameters Modbus Setting Default Valid Address Com channel choice F807 Communication Menu COM submenuLI R selection F112 LI R selectionParameters Location Remote spd ref 2 F207Frequency source VIA VIAComplete control diagram Commands CMOdConfiguration of the indirect blocks ConfigurationConfiguration of the communication interruption Configure the drive behaviour Parameter Modbus Setting Default Valid AddressCommunication detected fault 16#851 2129Configuration Modbus services RTU mode Principle of the Modbus protocolSlave Slave j Slave k Slave address Function code DataRead one word Modbus functions availableFunction 3, quantity = Function 3, quantity = 1 Read indirect blockStatus info Read indirect block of 2 parameters Write Single Register Write multiple registers Function 16 = 16#10, quantity =1Write indirect block Command word Frequency SetpointSpeed Setpoint Request 6C 7E Response Read Device Identification 43/14 Error response Exception codeModbus services Parameter list Auto ramp AUI Disabled Manual Setting of Max frequency FHReferring to the Altivar 212 programming manual GeneralCommands from serial communication List of control parametersSetpoints from serial communication Outputs control from serial communicationList of monitoring parameters StatusFrequency and speed Current and torquePower and energy MaintenanceTrip and alarm codes ValuesCommand word FA00 CommandsBit Specifications Remarks Command word 2 FA20 Energy reset bitExamples Over-current stall level change bitFrequency setpoint FA01 SetpointsSpeed setpoint FA13 Status Status word FE0I Fd01Command mode status FE45 Setpoint mode status FE46Status word 2 FE42 Fd42 Status word 3 FE49 Fd49Alarm code FC91 Trip and alarm codesAlarm of run time FE79 Code Value Description Hexadecimal number Decimal number Monitoring and control of I/O from communication Digital inputs status Fd06, FE06Digital outputs status Fd07, FE07 Bit Terminal name Function parameter titleDigital outputs command FA50 Analog outputs command FA51Damper opening command Analog inputs values FE35, FE36F580 = 3 Identification Model Voltage Power Rating Code FB05 Class FB72bit8Drive model code F805 ATV212WU15N4C S1A53844 01/2011 Appendix Schematic diagram Modbus 2-wire standard schematicRS485 standard Migration For example Migration ATV21 ATV212Commissioning ATV212Modbus manualENS1A5384401 S1A53844 01/2011