Parameter list
List of control parameters
These parameters are only in the RAM and not in the EEPROM, they return to initial values when the power is turned off, after the drive has been reseted, or when factory setting is done.
Commands from serial communication
| Parameter | Modbus | Range | Min. | Initial | Write during | EEPROM |
| description | address |
| setting unit | value | operation |
|
|
|
|
|
|
|
|
|
| Command word 1 (FA00) | 64000 | 0 to 65535 | - | 0 | Yes | None |
| from serial communication | 16#FA00 |
|
|
|
|
|
|
|
|
|
|
|
|
|
| Command word 2 (FA20) | 64032 | 0 to 65535 | - | 0 | Yes | None |
| from serial communication | 16#FA20 |
|
|
|
|
|
|
|
|
|
|
|
|
|
Setpoints from serial communication |
|
|
|
|
|
|
| Parameter | Modbus | Range | Min. | Initial | Write during | EEPROM |
| description | address |
| setting unit | value | operation |
|
|
|
|
|
|
|
|
|
| Frequency reference from serial comm. | 64001 | 0 to Max. | 0.01 Hz | 0 | Yes | None |
| (FA01) | 16#FA01 | frequency |
|
|
|
|
|
|
| (FH) |
|
|
|
|
|
|
|
|
|
|
|
|
| Speed reference from network (FA13) | 64019 | 0 to 24000 | 1 min | 0 | Yes | None |
|
| 16#FA13 |
| (1 rpm) |
|
|
|
|
|
|
|
|
|
|
|
Outputs control from serial communication |
|
|
|
|
|
|
Parameter | Modbus | Range | Min. | Initial | Write during | EEPROM |
description | address |
| setting unit | value | operation |
|
|
|
|
|
|
|
|
Terminal output data from comm. (FA50) | 64080 | 0 to 255 | 0 | 0 | Yes | None |
| 16#FA50 |
|
|
|
|
|
|
|
|
|
|
|
|
Analog output data from comm. (FA51) | 64081 | 0 to 1023 | 0 | 0 | Yes | None |
| 16#FA51 |
|
|
|
| |
|
| resolution) |
|
|
|
|
|
|
|
|
|
|
|
S1A53844 01/2011 | 45 |