Parameter list
Examples:
Run forward (CMOd and FMOd configured to serial communication)
FA00 = 16# 0400
Run reverse (CMOd and FMOd configured to serial communication)
FA00 = 16# 0600
Run forward, commands and setpoint from Modbus (irrespective of CMOd and FMOd)
FA00 = 16# C400
Run reverse, commands and setpoint from Modbus (irrespective of CMOd and FMOd)
FA00 = 16# C600
Command word 2 (FA20)
Bit | Function | 0 | 1 | Note |
|
|
|
|
|
0 | Reserved | - | - | - |
|
|
|
|
|
1 | Energy reset | No reset | Reset | Input energy (FE76) |
|
|
|
| Output energy (FE77) |
|
|
|
|
|
2 to 11 | Reserved | - | - | Do not set to "1" |
|
|
|
|
|
12 | OC stall 1 | OC stall 2 | OC1 (F601), OC2 (F185) | |
|
|
|
|
|
13 to 15 | Reserved | - | - | Do not set to "1" |
|
|
|
|
|
Energy reset (bit 1):
This command is enabled regardless of the command priority selection (bit 15 of common word (FA00)). It is necessary to reset it after the command is performed.
Over-current stall level change (bit 12):
This command word is enabled only when the communication command is enabled. Set Bit 15 of the Command word (FA00) to "1" [enabled].
This command word will be disabled is set (value 0), power is turned off or is reset, or factory setting [Parameter reset] (tYP) is selected.