Schneider Electric Altivar 212 manual Configure the drive behaviour, 2129

Page 29

Configuration

Configure the drive behaviour

The drive trips in Err5 [Com RJ45 fault] or Err8 [Network error fault] if the communication was established and the card no longer receives messages from the network.

The response of the drive in the event of a BACnet communication interruption can be configured by the parameter [Com. fault setting] F851.

Access to the parameter

This parameter is accessible in the [COMMUNICATION MENU] COM submenu of [PROGRAMMING MENU] Programming mode.

Description

Parameter

Modbus

Setting

Default

Valid

 

address

 

 

setting

after

 

 

 

 

 

 

[Com. fault setting] (F851)

2129

0

[Ramp stp (F/Cmod)]

4

Setting

Communication detected fault

16#851

1

[No active]

 

 

setting

 

2

[Ramp stop]

 

 

 

 

3

[Freewheel]

 

 

 

 

4

[Err5 or Err8]

 

 

 

 

 

 

 

 

WARNING

LOSS OF CONTROL

If F851 is set to 1, communication control will be inhibited.

For safety reasons, inhibiting the communication interruption detection should be restricted to the debug phase or to special application.

Failure to follow these instructions can result in death, serious injury, or equipment damage.

WARNING

LOSS OF CONTROL

Know and understand the setting of parameter F851. This parameter controls the behavior of the drive in the event of a network communication loss. If the value of F851 is 0, 1, 2, or 3, the drive will not trip on an Err8.

Failure to follow these instructions can result in death, serious injury, or equipment damage.

S1A53844 01/2011

29

Image 29
Contents Altivar S1A53844 01/2011 Table of Contents Table of Contents Important Information Safety InformationAt a Glance About the BookHazard of Electric SHOCK, Explosion or ARC Flash S1A53844 01/2011 Introduction Introduction Topic Hardware setupWhats in this Chapter? RJ45 Pin out of the Open Style Modbus connectorCross section Tightening torquePin out of the RJ45 Modbus connector Connection via Open Style wiring systemPin Signal Open Style ReferenceConnection accessories Connection via RJ45 wiring systemConnecting cables RJ45 ReferenceProtection Against Interference PTC resistor value F646 Description of terminalsGND Hardware setup Configuration Access to the parameters Configuration of the communication parametersParameters Modbus Adjustment range Default Valid Address AfterParameters Modbus Setting Configuration of the control sourceControl by the Modbus network CommunicationParameters Setting Default ValidControl by the terminals, monitoring by the Modbus network Parameters Modbus Setting Default Valid Com channel choice F807 Communication Menu COM submenu Parameters Modbus Setting Default Valid AddressLI R selection F112 LI R selectionRemote spd ref 2 F207 Parameters LocationFrequency source VIA VIACommands CMOd Complete control diagramConfiguration Configuration of the indirect blocksConfiguration of the communication interruption Parameter Modbus Setting Default Valid Address Configure the drive behaviourCommunication detected fault 16#851 2129Configuration Modbus services Principle of the Modbus protocol RTU modeSlave Slave j Slave k Slave address Function code DataFunction 3, quantity = Modbus functions availableRead one word Status info Read indirect blockFunction 3, quantity = 1 Read indirect block of 2 parameters Write Single Register Function 16 = 16#10, quantity =1 Write multiple registersSpeed Setpoint Command word Frequency SetpointWrite indirect block Request 6C 7E Response Read Device Identification 43/14 Exception code Error responseModbus services Parameter list Setting of Max frequency FH Auto ramp AUI Disabled ManualReferring to the Altivar 212 programming manual GeneralList of control parameters Commands from serial communicationSetpoints from serial communication Outputs control from serial communicationStatus List of monitoring parametersFrequency and speed Current and torqueMaintenance Power and energyTrip and alarm codes ValuesBit Specifications Remarks CommandsCommand word FA00 Energy reset bit Command word 2 FA20Examples Over-current stall level change bitSpeed setpoint FA13 SetpointsFrequency setpoint FA01 Status word FE0I Fd01 StatusSetpoint mode status FE46 Command mode status FE45Status word 2 FE42 Fd42 Status word 3 FE49 Fd49Alarm of run time FE79 Trip and alarm codesAlarm code FC91 Code Value Description Hexadecimal number Decimal number Digital inputs status Fd06, FE06 Monitoring and control of I/O from communicationDigital outputs status Fd07, FE07 Bit Terminal name Function parameter titleAnalog outputs command FA51 Digital outputs command FA50Damper opening command Analog inputs values FE35, FE36F580 = 3 Drive model code F805 Model Voltage Power Rating Code FB05 Class FB72bit8Identification ATV212WU15N4C S1A53844 01/2011 Appendix RS485 standard Modbus 2-wire standard schematicSchematic diagram Migration Commissioning Migration ATV21 ATV212For example ATV212Modbus manualENS1A5384401 S1A53844 01/2011