Schneider Electric Altivar 212 manual Parameters Location, Remote spd ref 2 F207, Frequency source

Page 25

Configuration

Command by the Modbus network, setpoint by the Modbus network or the terminals switched to by a logic input

The commands come from the Modbus network.

The setpoint comes from the Modbus network if logic input R is OFF.

The setpoint comes from the terminals if logic input R is ON.

The function 38 [Frequency source] is assigned to the logic input R, F112 = 38.

The LOC/REM key is valid.

Below is the list of parameters that must be configured.

Access to the parameters

Parameters

Location

 

 

 

 

 

 

 

 

 

 

[Command mode sel] (CMOd)

[PROGRAMMING MENU] Programming mode

 

 

 

[Frequency mode sel] (FMOd)

 

 

 

 

 

 

 

 

 

 

 

[Com channel choice] (F112)

[I/O MENU] IO submenu of [PROGRAMMING MENU]

 

 

Programming mode.

 

 

 

 

 

 

 

 

[Remote spd ref 2] (F207)

[EXTENDED MENU] F---submenu of [PROGRAMMING

 

MENU] Programming mode.

 

 

 

 

 

 

 

 

 

[Com channel choice] (F807)

[COMMUNICATION MENU] COM submenu

 

 

 

 

of [PROGRAMMING MENU] Programming mode.

 

 

 

 

 

 

 

Description

 

 

 

 

 

 

 

 

 

 

 

Parameters

Modbus

Setting

Default

 

Valid

 

address

 

setting

 

after

 

 

 

 

 

 

[Command mode sel] (CMOd)

3

2 [Communication]

0

 

Setting

Remote mode start/stop control

16#3

Serial communication

 

 

 

 

 

 

 

 

 

[Frequency mode sel] (FMOd)

4

4 [Serial com ref.]

1

 

Setting

Remote mode primary speed reference source

16#4

Serial communication

 

 

 

 

 

 

 

 

 

[LI R selection] (F112)

274

38 [Frequency source]

6

 

Setting

R logic input function

16#112

Configured to Frequency reference

 

 

 

 

 

source switching

 

 

 

 

 

 

 

 

 

[Remote spd ref 2] (F207)

519

1 [VIA]: VIA

2

 

Setting

Remote mode secondary speed reference source

16#207

 

 

 

 

that may override the source selected by FMOd

 

 

 

 

 

 

 

 

 

 

 

[Com channel choice] (F807)

2055

0 [RJ45] or

1

 

Setting

Selection of Communication channel: via RJ45 or

16#807

1 [Open style]

 

 

 

Open style connector port

 

 

 

 

 

 

 

 

 

 

 

S1A53844 01/2011

25

Image 25
Contents Altivar S1A53844 01/2011 Table of Contents Table of Contents Important Information Safety InformationAt a Glance About the BookHazard of Electric SHOCK, Explosion or ARC Flash S1A53844 01/2011 Introduction Introduction Whats in this Chapter? Hardware setupTopic RJ45 Pin out of the Open Style Modbus connectorCross section Tightening torquePin out of the RJ45 Modbus connector Connection via Open Style wiring systemPin Signal Open Style ReferenceConnection accessories Connection via RJ45 wiring systemConnecting cables RJ45 ReferenceProtection Against Interference PTC resistor value F646 Description of terminalsGND Hardware setup Configuration Access to the parameters Configuration of the communication parametersParameters Modbus Adjustment range Default Valid Address AfterParameters Modbus Setting Configuration of the control sourceControl by the Modbus network CommunicationControl by the terminals, monitoring by the Modbus network Setting Default ValidParameters Parameters Modbus Setting Default Valid Com channel choice F807 Communication Menu COM submenu Parameters Modbus Setting Default Valid AddressLI R selection F112 LI R selectionRemote spd ref 2 F207 Parameters LocationFrequency source VIA VIACommands CMOd Complete control diagramConfiguration Configuration of the indirect blocksConfiguration of the communication interruption Parameter Modbus Setting Default Valid Address Configure the drive behaviourCommunication detected fault 16#851 2129Configuration Modbus services Principle of the Modbus protocol RTU modeSlave Slave j Slave k Slave address Function code DataRead one word Modbus functions availableFunction 3, quantity = Function 3, quantity = 1 Read indirect blockStatus info Read indirect block of 2 parameters Write Single Register Function 16 = 16#10, quantity =1 Write multiple registersWrite indirect block Command word Frequency SetpointSpeed Setpoint Request 6C 7E Response Read Device Identification 43/14 Exception code Error responseModbus services Parameter list Setting of Max frequency FH Auto ramp AUI Disabled ManualReferring to the Altivar 212 programming manual GeneralList of control parameters Commands from serial communicationSetpoints from serial communication Outputs control from serial communicationStatus List of monitoring parametersFrequency and speed Current and torqueMaintenance Power and energyTrip and alarm codes ValuesCommand word FA00 CommandsBit Specifications Remarks Energy reset bit Command word 2 FA20Examples Over-current stall level change bitFrequency setpoint FA01 SetpointsSpeed setpoint FA13 Status word FE0I Fd01 StatusSetpoint mode status FE46 Command mode status FE45Status word 2 FE42 Fd42 Status word 3 FE49 Fd49Alarm code FC91 Trip and alarm codesAlarm of run time FE79 Code Value Description Hexadecimal number Decimal number Digital inputs status Fd06, FE06 Monitoring and control of I/O from communicationDigital outputs status Fd07, FE07 Bit Terminal name Function parameter titleAnalog outputs command FA51 Digital outputs command FA50Damper opening command Analog inputs values FE35, FE36F580 = 3 Identification Model Voltage Power Rating Code FB05 Class FB72bit8Drive model code F805 ATV212WU15N4C S1A53844 01/2011 Appendix Schematic diagram Modbus 2-wire standard schematicRS485 standard Migration For example Migration ATV21 ATV212Commissioning ATV212Modbus manualENS1A5384401 S1A53844 01/2011