Carrier 50RTP03-20 specifications 50RTP04 Blower Performance Data

Page 12

Table 5 — 50RTP04 Blower Performance Data

AIRFLOW

ESP

 

 

 

 

AIRFLOW (cfm) AT EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

(cfm)

0.0

0.1

0.2

0.3

 

0.4

0.5

0.6

0.7

0.8

0.9

1.0

1.1

 

1.2

1.3

1.4

1.5

 

 

 

 

bhp

0.27

0.31

0.34

0.37

 

0.40

0.42

0.45

0.48

0.52

0.55

0.58

0.60

 

0.63

0.66

0.70

0.73

1200

Sheave/Motor

B

B

A

A

 

A

A

A

A

A

A

A

C

 

C

C

C

C

rpm

750

800

845

890

 

935

975

1015

1055

1095

1135

1170

1205

 

1240

1275

1310

1345

 

 

 

 

Turns Open

5.0

4.0

5.0

4.0

 

3.5

3.0

2.5

1.5

1.0

0.5

0.0

3.0

 

2.5

2.0

1.5

1.5

 

bhp

0.35

0.38

0.41

0.43

 

0.45

0.47

0.53

0.59

0.64

0.67

0.70

0.72

 

0.75

0.78

0.80

0.83

1300

Sheave/Motor

B

A

A

A

 

A

A

A

A

A

A

C

C

 

C

C

C

C

rpm

810

850

890

930

 

970

1010

1050

1090

1125

1160

1195

1230

 

1265

1300

1330

1365

 

 

 

 

Turns Open

4.0

4.5

4.0

3.5

 

3.0

2.5

2.0

1.0

0.5

0.0

3.0

3.0

 

2.5

2.0

1.5

1.0

 

bhp

0.43

0.46

0.49

0.52

 

0.55

0.58

0.62

0.66

0.68

0.71

0.74

0.77

 

0.82

0.86

0.91

0.96

1400

Sheave/Motor

A

A

A

A

 

A

A

A

A

A

C

C

C

 

C

C

C

C

rpm

865

900

935

970

 

1010

1045

1085

1120

1155

1190

1220

1255

 

1290

1320

1355

1390

 

 

 

 

Turns Open

4.5

4.0

3.5

3.0

 

2.5

2.0

1.5

0.5

0.0

3.5

3.0

2.5

 

2.0

1.5

1.0

1.0

 

bhp

0.49

0.52

0.54

0.57

 

0.62

0.68

0.73

0.76

0.79

0.82

0.85

0.89

 

0.92

0.96

1.00

1.05

1500

Sheave/Motor

A

A

A

A

 

A

A

A

A

C

C

C

C

 

C

C

E

E

rpm

910

945

975

1010

 

1045

1080

1115

1150

1180

1215

1250

1280

 

1310

1345

1375

1405

 

 

 

 

Turns Open

3.5

3.5

3.0

2.5

 

2.0

1.5

1.0

0.0

3.5

3.0

2.5

2.0

 

2.0

1.5

1.0

0.5

 

bhp

0.62

0.65

0.67

0.70

 

0.72

0.75

0.78

0.82

0.86

0.89

0.94

1.00

 

1.04

1.08

1.13

1.18

1600

Sheave/Motor

A

A

A

A

 

A

A

A

C

C

C

C

E

 

E

E

E

E

rpm

960

985

1015

1050

 

1080

1115

1145

1175

1210

1240

1275

1305

 

1335

1365

1395

1425

 

 

 

 

Turns Open

3.0

2.5

2.5

2.0

 

2.0

1.5

0.5

3.5

3.0

2.5

2.5

2.0

 

1.5

1.0

0.5

0.5

 

bhp

0.74

0.77

0.80

0.83

 

0.85

0.88

0.90

0.93

0.95

1.00

1.06

1.11

 

1.17

1.22

1.27

1.31

1700

Sheave/Motor

A

A

A

A

 

A

A

C

C

C

E

E

E

 

E

E

E

E

rpm

1000

1030

1060

1090

 

1115

1150

1180

1210

1240

1270

1300

1330

 

1360

1390

1420

1445

 

 

 

 

Turns Open

2.5

2.0

1.5

1.5

 

1.0

1.0

3.5

3.0

3.0

2.5

2.0

1.5

 

1.0

1.0

0.5

0.0

 

bhp

0.83

0.87

0.90

0.94

 

0.98

1.02

1.06

1.09

1.14

1.18

1.23

1.28

 

1.32

1.36

1800

Sheave/Motor

A

A

A

A

 

A

E

E

E

E

E

E

E

 

E

E

rpm

1050

1075

1100

1125

 

1155

1185

1215

1245

1275

1300

1330

1360

 

1385

1415

 

 

 

 

Turns Open

2.0

1.5

1.0

0.5

 

0.5

3.5

3.0

2.5

2.5

2.0

1.5

1.0

 

1.0

0.5

 

bhp

0.97

1.00

1.03

1.08

 

1.12

1.16

1.20

1.25

1.29

1.34

1.38

1.42

 

1900

Sheave/Motor

A

D

D

E

 

E

E

E

E

E

E

E

E

 

rpm

1100

1120

1145

1175

 

1200

1225

1250

1280

1305

1335

1360

1385

 

 

 

 

 

Turns Open

1.0

1.0

0.5

3.5

 

3.0

3.0

2.5

2.0

2.0

1.5

1.0

1.0

 

 

bhp

1.13

1.17

1.20

1.24

 

1.28

1.32

1.36

1.40

1.44

 

2000

Sheave/Motor

D

D

E

E

 

E

E

E

E

E

 

rpm

1145

1170

1190

1215

 

1235

1260

1290

1315

1340

 

 

 

 

 

Turns Open

0.5

0.5

3.0

3.0

 

2.5

2.5

2.0

1.5

1.5

 

LEGEND

bhp — Brake Horsepower ESP — External Static Pressure

NOTES:

1.A = Standard RPM/Standard Motor, B = Low RPM/Standard Motor, C = High RPM/Standard Motor, D = Standard RPM/ Large Motor, E = High RPM/Large Motor

2.Unit shipped with standard drive package with drive sheave 2.5 turns open unless otherwise requested. Field adjustment may be required for specified CFM.

3.ISO/AHRI rating point with standard drive package and drive sheave open 3.0 turns at .30 ESP.

4.Performance data does not include drive losses and is based on sea level conditions.

5.All airflow is rated at lowest voltage if unit is dual rated, i.e., rated at 208 volts for 208-230 volt units.

12

Image 12
Contents Contents Safety ConsiderationsInstallation GeneralPhysical Data Aquazone 50RTP03-20 Units Dimensions Outside Air Water CondensateIn/Out FPT Drain 03,04 12.57 x In/Out FPT 18.95 x 11/4 10,12 11/250RTP14,20 Unit Dimensions 14,20 18.95 xReturn Air Transition Supply Air Transition Exterior 78.875 82.25 21.00 25.00 19.00 82.875 76.875 27.00 86.25Install Condensate Drain 50 RTPConnect Electrical Wiring Water Quality GuidelinesElectrical Data FLA Hacr50RTP03 Blower Performance Data 50RTP04 Blower Performance Data 50RTP05 Blower Performance Data 50RTP06 Blower Performance Data 50RTP08 Blower Performance Data 3800 39004000 50RTP10 Blower Performance Data 41004200 4300 44004500 460050RTP12 Blower Performance Data 50RTP14 Blower Performance Data 62006400 66006800 700050RTP20 Blower Performance Data 10,000 Rpm 940 956 976 996 1016 1036 1056 1076 1092 Turns OpenECR See legend and notes on 50RTP03-06 Units 50RTP08-20 UnitsHpwr A50-8557 Typical Control Wiring with Deluxe D and LON Controller SizesJ6J5 J1 J8AL1 A50 Units with Deluxe D and Wshp Open Multiple Protocol Controls Wshp Open Control Connect Low Voltage Wiring Compressor-StageReversing Valve Fan 24Vac Hot 24Vac Com Deluxe DComplete C Control Jumper Settings See Deluxe D Control Jumper Settings SeePRE-START-UP Field Selectable InputsDIP Switch Block S2 Accessory 1 Relay Options DIP Switch Block S2 Accessory 2 Relay OptionsUnit Start-Up Cooling Mode Unit Start-Up Heating ModeSTART-UP Operating LimitsUnit Start-Up with Wshp Open Controls BACview6 Display InterfacePage Antifreeze Percentages by Volume OperationUnits with Aquazone Complete C Control Units with Aquazone Deluxe D ControlPage Auxiliary Modulating Hot Water/Steam Heating Reheat System Test Complete C Control LED Code Fault Descriptions Service Aquazone Deluxe D Control LED IndicaRefrigerant Charging Air Coil Fan Motor RemovalReplacing the Wshp Open Controller’s Bat ’ to 4’Troubleshooting FP1 and FP2 Thermistor LocationTroubleshooting Air temperature out of rangeReduced or no water flow Overcharged with refrigerantUnit Does Not Operate Appendix a Wshp Open Screen Configuration Alarm StatusStatus SensorAppendix a Wshp Open Screen Configuration MaintenanceSystem Settings ConfigurationSchedule Appendix a Wshp Screen Open Configuration ServiceTest Configuration Service Electronically Commutated MotorAlarm Page Page Copyright 2010 Carrier Corporation 50RTP START-UP Checklist II. START-UPHeating Cycle Analysis Cooling Cycle AnalysisAlong Dotted Line Catalog No Form 50RTP-1SI Pg CL-2 10A Replaces New