APPENDIX A — WSHP SCREEN OPEN CONFIGURATION (cont)
SCREEN NAME | PASSWORD | POINT NAME | EDITABLE | RANGE | DEFAULT | NOTES | ||
LEVEL | ||||||||
|
|
|
|
|
|
| ||
|
|
|
|
|
|
| Defines the hysteresis applied above | |
|
|
| SPT Occupied Alarm | X | 2 - 20 ° F | 5 ° F | the cooling and below the heating set | |
|
|
| Hysteresis | points before an alarm condition will | ||||
|
|
|
|
|
| |||
|
|
|
|
|
|
| occur | |
|
|
|
|
|
|
| Used to calculate the delay time before | |
|
|
| SPT Alarm Delay | X | 0 - 30 min per degree | 10 min | an alarm is generated after the alarm | |
|
|
|
|
|
|
| condition occurs | |
|
|
| SPT Unoccupied Low | X | 35 - 90 ° F | 45 ° F | Defines the fixed unoccupied | |
|
|
| Alarm Temperature | ow SPT alarm limit | ||||
|
|
|
|
|
| |||
|
|
| SPT Unoccupied High | X | 45 - 100 ° F | 95 ° F | Defines the fixed unoccupied | |
|
|
| Alarm Temperature | high SPT alarm limit | ||||
|
|
|
|
|
| |||
|
|
| SAT Low SAT | X | 15 - 90 ° F | 45 ° F | Defines the fixed minimum | |
|
|
| Alarm Limit | SAT alarm limit | ||||
|
|
|
|
|
| |||
|
|
| SAT High SAT | X | 90 - 175 ° F | 120 ° F | Defines the fixed maximum | |
|
|
| Alarm Limit | SAT alarm limit | ||||
|
|
|
|
|
| |||
|
|
| Condensate Overflow |
|
|
| Defines the delay time before an alarm | |
|
|
| X | 5 - 600 sec | 10 sec | is generated after the alarm condition | ||
|
|
| Alarm Delay | |||||
|
|
|
|
|
| occurs | ||
|
|
|
|
|
|
| ||
|
|
| Space Humidity Occupied | X | 45% - 100% | 100% | Defines the fixed occupied | |
|
|
| High Alarm Limit | high space RH alarm limit | ||||
|
|
|
|
|
| |||
|
|
| Space Humidity Alarm |
|
|
| Used to calculate the delay time before | |
Configuration |
| X | 0 - 30 min per % RH | 5 min | an alarm is generated after the alarm | |||
| Delay | |||||||
|
|
|
|
|
| condition occurs | ||
|
|
|
|
|
|
| ||
| → | Admin Password | Space Humidity Unoccu- | X | 45% - 100% | 100% | Defines the fixed unnoccupied | |
|
| level access only | pied High Alarm Limit | high space RH alarm limit | ||||
|
|
|
|
| ||||
| Alarm |
| IAQ/Ventilation Occupied | X | 0 - 9999 ppm | 1100 ppm | Defines the fixed occupied high | |
Configuration |
| High Alarm Limit | space IAQ/Ventilation alarm limit | |||||
|
|
|
| |||||
|
|
| IAQ/Ventilation |
|
|
| Used to calculate the delay time before | |
|
|
| X | 0.1 - 1.0 min per ppm | 0.25 min | an alarm is generated after the alarm | ||
|
|
| Alarm Delay | |||||
|
|
|
|
|
| condition occurs | ||
|
|
|
|
|
|
| ||
|
|
| Rnet Sensor SPT Alarm | X | Ignore/Display | Ignore | Determines if the SPT alarm is | |
|
|
| displayed on the local Rnet sensor | |||||
|
|
|
|
|
|
| ||
|
|
| Rnet Sensor SAT Alarm | X | Ignore/Display | Ignore | Determines if the SAT alarm is | |
|
|
| displayed on the local Rnet sensor | |||||
|
|
|
|
|
|
| ||
|
|
| Rnet Sensor Compressor |
|
|
| Determines if the Compressor Lockout | |
|
|
| X | Ignore/Display | Display | alarm is displayed on the local Rnet | ||
|
|
| Lockout Alarm | |||||
|
|
|
|
|
| sensor | ||
|
|
|
|
|
|
| ||
|
|
| Rnet Sensor Condenser |
|
|
| Determines if the Condenser Water | |
|
|
| X | Ignore/Display | Display | Temperature alarm is displayed on the | ||
|
|
| Water Temperature Alarm | |||||
|
|
|
|
|
| local Rnet sensor | ||
|
|
|
|
|
|
| ||
|
|
| Rnet Sensor Condensate |
|
|
| Determines if the Condensate | |
|
|
| X | Ignore/Display | Display | Overflow alarm is displayed on the | ||
|
|
| Overflow Alarm | |||||
|
|
|
|
|
| local Rnet sensor | ||
|
|
|
|
|
|
| ||
|
|
| Rnet Sensor Dirty | X | Ignore/Display | Display | Determines if the Dirty Filter alarm is | |
|
|
| Filter Alarm | displayed on the local Rnet sensor | ||||
|
|
|
|
|
| |||
|
|
| Rnet Sensor Space |
|
|
| Determines if the High Space | |
|
|
| X | Ignore/Display | Ignore | RH alarm is displayed on the | ||
|
|
| High Humidity Alarm | |||||
|
|
|
|
|
| local Rnet sensor | ||
|
|
|
|
|
|
| ||
Configuration |
| Loop Control Network |
|
|
| See TPI | ||
| Number |
|
|
| ||||
|
|
|
|
|
|
| ||
| → |
| Loop Control Network |
|
|
| See TPI | |
|
| Address |
|
|
| |||
|
|
|
|
|
|
| ||
Linkage |
| Number of Linked Heat |
|
|
| See TPI | ||
| Pumps |
|
|
| ||||
|
|
|
|
|
|
| ||
| LEGEND |
|
|
|
|
| ||
BAS — Building Automation System |
|
|
|
| ||||
DCV — Demand Controlled Ventilation |
|
|
|
| ||||
ECM | — Electronically Commutated Motor |
|
|
|
| |||
IAQ | — Indoor Air Quality |
|
|
|
|
| ||
OAT | — Outdoor Air Temperature |
|
|
|
| |||
RH | — Relative Humidity |
|
|
|
|
| ||
SAT — Supply Air Temperature |
|
|
|
|
| |||
SPT | — Space Temperature |
|
|
|
|
| ||
TPI | — Third Party Integration |
|
|
|
|
|