Carrier 50RTP03-20 specifications Alarm

Page 55

APPENDIX A — WSHP SCREEN OPEN CONFIGURATION (cont)

SCREEN NAME

PASSWORD

POINT NAME

EDITABLE

RANGE

DEFAULT

NOTES

LEVEL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Defines the hysteresis applied above

 

 

 

SPT Occupied Alarm

X

2 - 20 ° F

5 ° F

the cooling and below the heating set

 

 

 

Hysteresis

points before an alarm condition will

 

 

 

 

 

 

 

 

 

 

 

 

 

occur

 

 

 

 

 

 

 

Used to calculate the delay time before

 

 

 

SPT Alarm Delay

X

0 - 30 min per degree

10 min

an alarm is generated after the alarm

 

 

 

 

 

 

 

condition occurs

 

 

 

SPT Unoccupied Low

X

35 - 90 ° F

45 ° F

Defines the fixed unoccupied

 

 

 

Alarm Temperature

ow SPT alarm limit

 

 

 

 

 

 

 

 

 

SPT Unoccupied High

X

45 - 100 ° F

95 ° F

Defines the fixed unoccupied

 

 

 

Alarm Temperature

high SPT alarm limit

 

 

 

 

 

 

 

 

 

SAT Low SAT

X

15 - 90 ° F

45 ° F

Defines the fixed minimum

 

 

 

Alarm Limit

SAT alarm limit

 

 

 

 

 

 

 

 

 

SAT High SAT

X

90 - 175 ° F

120 ° F

Defines the fixed maximum

 

 

 

Alarm Limit

SAT alarm limit

 

 

 

 

 

 

 

 

 

Condensate Overflow

 

 

 

Defines the delay time before an alarm

 

 

 

X

5 - 600 sec

10 sec

is generated after the alarm condition

 

 

 

Alarm Delay

 

 

 

 

 

 

occurs

 

 

 

 

 

 

 

 

 

 

Space Humidity Occupied

X

45% - 100%

100%

Defines the fixed occupied

 

 

 

High Alarm Limit

high space RH alarm limit

 

 

 

 

 

 

 

 

 

Space Humidity Alarm

 

 

 

Used to calculate the delay time before

Configuration

 

X

0 - 30 min per % RH

5 min

an alarm is generated after the alarm

 

Delay

 

 

 

 

 

 

condition occurs

 

 

 

 

 

 

 

 

Admin Password

Space Humidity Unoccu-

X

45% - 100%

100%

Defines the fixed unnoccupied

 

 

level access only

pied High Alarm Limit

high space RH alarm limit

 

 

 

 

 

 

Alarm

 

IAQ/Ventilation Occupied

X

0 - 9999 ppm

1100 ppm

Defines the fixed occupied high

Configuration

 

High Alarm Limit

space IAQ/Ventilation alarm limit

 

 

 

 

 

 

 

IAQ/Ventilation

 

 

 

Used to calculate the delay time before

 

 

 

X

0.1 - 1.0 min per ppm

0.25 min

an alarm is generated after the alarm

 

 

 

Alarm Delay

 

 

 

 

 

 

condition occurs

 

 

 

 

 

 

 

 

 

 

Rnet Sensor SPT Alarm

X

Ignore/Display

Ignore

Determines if the SPT alarm is

 

 

 

displayed on the local Rnet sensor

 

 

 

 

 

 

 

 

 

 

Rnet Sensor SAT Alarm

X

Ignore/Display

Ignore

Determines if the SAT alarm is

 

 

 

displayed on the local Rnet sensor

 

 

 

 

 

 

 

 

 

 

Rnet Sensor Compressor

 

 

 

Determines if the Compressor Lockout

 

 

 

X

Ignore/Display

Display

alarm is displayed on the local Rnet

 

 

 

Lockout Alarm

 

 

 

 

 

 

sensor

 

 

 

 

 

 

 

 

 

 

Rnet Sensor Condenser

 

 

 

Determines if the Condenser Water

 

 

 

X

Ignore/Display

Display

Temperature alarm is displayed on the

 

 

 

Water Temperature Alarm

 

 

 

 

 

 

local Rnet sensor

 

 

 

 

 

 

 

 

 

 

Rnet Sensor Condensate

 

 

 

Determines if the Condensate

 

 

 

X

Ignore/Display

Display

Overflow alarm is displayed on the

 

 

 

Overflow Alarm

 

 

 

 

 

 

local Rnet sensor

 

 

 

 

 

 

 

 

 

 

Rnet Sensor Dirty

X

Ignore/Display

Display

Determines if the Dirty Filter alarm is

 

 

 

Filter Alarm

displayed on the local Rnet sensor

 

 

 

 

 

 

 

 

 

Rnet Sensor Space

 

 

 

Determines if the High Space

 

 

 

X

Ignore/Display

Ignore

RH alarm is displayed on the

 

 

 

High Humidity Alarm

 

 

 

 

 

 

local Rnet sensor

 

 

 

 

 

 

 

Configuration

 

Loop Control Network

 

 

 

See TPI

 

Number

 

 

 

 

 

 

 

 

 

 

 

 

Loop Control Network

 

 

 

See TPI

 

 

Address

 

 

 

 

 

 

 

 

 

 

Linkage

 

Number of Linked Heat

 

 

 

See TPI

 

Pumps

 

 

 

 

 

 

 

 

 

 

 

LEGEND

 

 

 

 

 

BAS — Building Automation System

 

 

 

 

DCV — Demand Controlled Ventilation

 

 

 

 

ECM

Electronically Commutated Motor

 

 

 

 

IAQ

Indoor Air Quality

 

 

 

 

 

OAT

Outdoor Air Temperature

 

 

 

 

RH

Relative Humidity

 

 

 

 

 

SAT — Supply Air Temperature

 

 

 

 

 

SPT

Space Temperature

 

 

 

 

 

TPI

Third Party Integration

 

 

 

 

 

55

Image 55
Contents Safety Considerations ContentsGeneral InstallationPhysical Data Aquazone 50RTP03-20 Units Outside Air Water Condensate DimensionsIn/Out FPT Drain 03,04 12.57 x 18.95 x 11/4 10,12 11/2 In/Out FPT14,20 18.95 x 50RTP14,20 Unit Dimensions78.875 82.25 21.00 25.00 19.00 82.875 76.875 27.00 86.25 Return Air Transition Supply Air Transition Exterior50 RTP Install Condensate DrainWater Quality Guidelines Connect Electrical WiringFLA Hacr Electrical Data50RTP03 Blower Performance Data 50RTP04 Blower Performance Data 50RTP05 Blower Performance Data 50RTP06 Blower Performance Data 50RTP08 Blower Performance Data 3900 38004000 4100 50RTP10 Blower Performance Data4200 4600 43004400 450050RTP12 Blower Performance Data 6200 50RTP14 Blower Performance Data7000 64006600 680050RTP20 Blower Performance Data Rpm 940 956 976 996 1016 1036 1056 1076 1092 Turns Open 10,000ECR See legend and notes on 50RTP08-20 Units 50RTP03-06 UnitsHpwr A50-8557 Sizes Typical Control Wiring with Deluxe D and LON ControllerJ1 J8 J6J5AL1 A50 Units with Deluxe D and Wshp Open Multiple Protocol Controls Wshp Open Control Deluxe D Connect Low Voltage WiringCompressor-Stage Reversing Valve Fan 24Vac Hot 24Vac ComField Selectable Inputs Complete C Control Jumper Settings SeeDeluxe D Control Jumper Settings See PRE-START-UPDIP Switch Block S2 Accessory 2 Relay Options DIP Switch Block S2 Accessory 1 Relay OptionsOperating Limits Unit Start-Up Cooling ModeUnit Start-Up Heating Mode START-UPBACview6 Display Interface Unit Start-Up with Wshp Open ControlsPage Units with Aquazone Deluxe D Control Antifreeze Percentages by VolumeOperation Units with Aquazone Complete C ControlPage Auxiliary Modulating Hot Water/Steam Heating Reheat System Test Complete C Control LED Code Fault Descriptions Aquazone Deluxe D Control LED Indica Service’ to 4’ Refrigerant ChargingAir Coil Fan Motor Removal Replacing the Wshp Open Controller’s BatFP1 and FP2 Thermistor Location TroubleshootingOvercharged with refrigerant TroubleshootingAir temperature out of range Reduced or no water flowUnit Does Not Operate Sensor Appendix a Wshp Open Screen ConfigurationAlarm Status StatusConfiguration Appendix a Wshp Open Screen ConfigurationMaintenance System SettingsSchedule Service Appendix a Wshp Screen Open ConfigurationTest Electronically Commutated Motor Configuration ServiceAlarm Page Page Copyright 2010 Carrier Corporation II. START-UP 50RTP START-UP ChecklistCatalog No Form 50RTP-1SI Pg CL-2 10A Replaces New Heating Cycle AnalysisCooling Cycle Analysis Along Dotted Line